Operating Instructions

Troubleshooting
Siemens Building Technologies, Inc. 101
Error Cause Diagnosis and Remedy
Drive
Reaction
A0921, Analog
output
parameters not
set properly
Analog output parameters
must not be set to identical
values, as illogical values
would result.
Index 0: Parameter settings
for output identical.
Index 1: Parameter settings
for input identical.
Index 2: Parameter settings
for output do not correspond
to analog output type.
— —
A0922, No load
applied to
SED2
No load is applied to the
SED2.
Some functions may not work
as under normal load
conditions.
— —
A0923, Both
JOG left and
JOG right are
requested
Both JOG right and JOG left
have been requested. This
freezes the RFG (ramp function
generator) output frequency at
its current value.
— —
A0952, Belt
failure detected
Load conditions at the motor
indicate a belt failure or
mechanical fault.
No breakage, seizure, or
obstruction of SED2 train.
Correct operation of
external speed sensor, if
in use.