Operating Instructions

SED2 VFD Startup, Operation, and Maintenance Manual
Siemens Building Technologies, Inc. 106
Appendix A: Parameters,
Defaults, and Settings
Parameter Description Unit
User
Setting
Min Default Max
Access
Level
r0000
Drive display (defined in
P0005)
All
r0002 Drive state (actual) 3
P0003 User access level 0 1 4 1
P0004 Parameter filter 0 0 22 1
P0005 Display selection for r0000 2 21 2294 2
P0006 Display mode for r0000 0 2 4 3
P0010 Commissioning parameter filter
0 0 30 1
P0011
Lock for user-defined
parameter
0 0 65535 3
P0012 Key for user-defined parameter
0 0 65535 3
P0013 User-defined parameter 0 0 65535 3
r0018 Firmware version 3
r0019 CO/BO: BOP control word 3
r0020 CO: Actual frequency setpoint Hz 3
r0021 CO: Actual frequency Hz 3
r0022 Actual Rotor speed 1/min
3
r0024 CO: Actual output frequency Hz 3
r0025 CO: Actual output voltage V 3
r0026
CO: Actual DC link output
voltage
V 3
r0027 CO: Actual output current A 3
r0031 Actual torque Nm 3
r0032 Actual power 3
r0035 CO: Actual Motor temperature °C 3
r0039 CO: Energy consumption meter
kWh 3