Operating Instructions

SED2 VFD Startup, Operation, and Maintenance Manual
108 Siemens Building Technologies, Inc.
Parameter Description Unit
User
Setting
Min Default Max
Access
Level
P0409
Pulses per second at Rated
Frequency
1 25 500 3
P0501 Type of sensor 0 0 29 2
P0506 Parameter list 0 4000 3
P0507 Scalar values 0 1.0 9999.9 3
P0508 Unit 0 0 65535 3
P0509 String 0 0 65535 3
P0601 Motor temp. sensor 0 0 2 3
P0610 Motor I
2
t temperature reaction 0 2 2 3
P0640 Motor overload factor [%] % 10.0 110.0 400.0 3
P0700 Selection of command source 0
[0] 2,
[1] 1
6 1
P0701 Function of digital input 1 0
[0] 1,
[1] 0
99 2
P0702 Function of digital input 2 0
[0] 12,
[1] 0
99 2
P0703 Function of digital input 3 0 9 99 2
P0704 Function of digital input 4 0 15 99 2
P0705 Function of digital input 5 0 15 99 2
P0706 Function of digital input 6 0 15 99 2
P0707 Function of digital input 7 0 0 99 3
P0708 Function of digital input 8 0 0 99 3
P0718 CO/BO: Hand/Auto 0 0 1 3
r0722 CO/BO: Binary input values - - - 3
P0725 PNP/NPN digital inputs 0 1 1 3
P0731 BI: Function of digital output 1 0:0 52:3 4000:0 2
P0732 BI: Function of digital output 2 0:0 52:2 4000:0 2
r0747 CO/BO: State of digital outputs
3
P0748 Invert digital outputs 0 0 7 3
r0752
Actual input of ADC (analog
input) [V] or [mA]
2
P0753
Smooth time ADC (analog
input)
ms 0 100 10000 3