Operating Instructions

SED2 VFD Startup, Operation, and Maintenance Manual
114 Siemens Building Technologies, Inc.
Parameter Description Unit
User
Setting
Min Default Max
Access
Level
P2184 Belt threshold frequency 3 Hz 0.00 50.00 650.00 2
P2185 Upper torque threshold 1 Nm 0.0 99999.0 99999.0 3
P2186 Lower torque threshold 1 Nm 0.0 0.0 99999.0 3
P2187 Upper torque threshold 2 Nm 0.0 99999.0 99999.0 3
P2188 Lower torque threshold 2 Nm 0.0 0.0 99999.0 3
P2189 Upper torque threshold 3 Nm 0.0 99999.0 99999.0 3
P2190 Lower torque threshold 3 Nm 0.0 0.0 99999.0 3
P2191 Belt failure speed tolerance Hz 0.00 3.00 20.00 3
P2192 Time delay for belt failure s 0 10 65 3
r2197 CO/BO: Monitoring word 1 3
r2198 CO/BO: Monitoring word 2 3
P2200 BI: Enable PID controller 0:0 0:0 4000:0 3
P2201 Fixed PID setpoint 1 % -200.00 0.00 200.00 3
P2202 Fixed PID setpoint 2 % -200.00 10.00 200.00 3
P2203 Fixed PID setpoint 3 % -200.00 20.00 200.00 3
P2204 Fixed PID setpoint 4 % -200.00 30.00 200.00 3
P2205 Fixed PID setpoint 5 % -200.00 40.00 200.00 3
P2206 Fixed PID setpoint 6 % -200.00 50.00 200.00 3
P2207 Fixed PID setpoint 7 % -200.00 60.00 200.00 3
P2208 Fixed PID setpoint 8 % -200.00 70.00 200.00 3
P2209 Fixed PID setpoint 9 % -200.00 80.00 200.00 3
P2210 Fixed PID setpoint 10 % -200.00 90.00 200.00 3
P2211 Fixed PID setpoint 11 % -200.00 100.00 200.00 3
P2212 Fixed PID setpoint 12 % -200.00 110.00 200.00 3
P2213 Fixed PID setpoint 13 % -200.00 120.00 200.00 3
P2214 Fixed PID setpoint 14 % -200.00 130.00 200.00 3
P2215 Fixed PID setpoint 15 % -200.00 130.00 200.00 3
P2216 Fixed PID setpoint mode-Bit 0 1 1 3 3
P2217 Fixed PID setpoint mode-Bit 1 1 1 3 3
P2218 Fixed PID setpoint mode-Bit 2 1 1 3 3
P2219 Fixed PID setpoint mode-Bit 3 1 1 3 3