Operating Instructions

Appendix B: SED2 Point Maps
Siemens Building Technologies, Inc 117
Appendix B: SED2 Point Maps
Table 10. SBT P1 Point Cross Reference to SED2.
Point
No.
Point
Type
Descriptor
Factory
Default
(SI
Units)
Eng.
Units
(SI
Units)
On Text
Off
Text
SED2
Reference
01 LAO CTLR ADDRESS 99 – SBT
02 LAO APPLICATION 2722 or
2742 *
– – SBT
03 LAI FREQ OUTPUT 0 HZ r0021
05 LAI SPEED 0 RPM
Calculated
based on
P0311
06 LAI CURRENT 0 A r0027
07 LAI TORQUE 0 NM r0031
08 LAI ACTUAL POWER 0 HP/
KW
– – r0032
09 LAI TOTAL KWH 0 KWH r0039
13 LAI DC BUS VOLT 0 V r0026
14 LAI REFERENCE 0 HZ r0020
16 LAI RATED PWR 0 HP/
KW
– – P0307
17 LAI OUTPUT VOLTS 0 V r0025
20 LAO OVRD TIME 1 HRS
21 LDI FWD.REV FWD – REV FWD r0054 bit 11
22 LDO CMD FWD.REV FWD – REV FWD P0842(2)
23 LDI STOP.RUN STOP – RUN STOP r0019 bit 1
24 LDO CMD STP.STRT STOP – START STOP P0840(2)
25 LDI AT MAX FREQ NO – MAX NO
26 LDI CONTROL MODE SERIAL – SERIAL LOCAL P0700(2)
27 LDI ENABLED OFF – ENABLED OFF r0052 bit 0
* 2722=Control Board Version 1.2 or earlier