Operating Instructions

SED2 VFD Startup, Operation, and Maintenance Manual
118 Siemens Building Technologies, Inc.
Table 10. SBT P1 Point Cross Reference to SED2.
Point
No.
Point
Type
Descriptor
Factory
Default
(SI
Units)
Eng.
Units
(SI
Units)
On Text
Off
Text
SED2
Reference
28 LDI READY TO RUN OFF – READY OFF r0052 bit 1
29 LDO DAY.NIGHT DAY – NIGHT DAY SBT
30 LAO CURRENT LIM 1400 PCT r0067
31 LAO ACCEL TIME 1 500 SEC read P1120
32 LAO DECEL TIME 1 500 SEC read P1121
34 LDO
SEL HND.AUTO
(reference)
AUTO – AUTO HAND P1000(2)
35 LDO RUN ENABLE ENABLE – ENABLE OFF r0052 bit 0
40 LDO DIGITAL OUT 1 OFF – ON OFF
P0731(2) read
at r0747
41 LDO DIGITAL OUT 2 OFF – ON OFF
P0732(2) read
at r0747
45 LAI ANALOG IN 1 0 PCT r0754(0)
46 LAI ANALOG IN 2 0 PCT r0754(1)
47 LAI ANALOG OUT 1 0 PCT
48 LAI ANALOG OUT 2 0 PCT
51 LAO FREQ REF 0 PCT r0754(0)
52 LAI FREQ ACTUAL 0 PCT r0754(0)
53 LAO FREQ MAX 2450 HZ P1082
55 LAO PID SETP REF 8602 PCT r0754(0)
56 LAI PID SETP OUT 0 PCT r2294
57 LAO PID UP LMT 12288 PCT P2291
58 LAO PID LO LMT 8192 PCT P2292
59 LAI PID OUTPUT 0 PCT r2294
60 LAI PI FEEDBACK 0 PCT r2272
61 LAI P GAIN 0 PCT P2280
62 LAI I GAIN 0 PCT P2285
63 LAI D GAIN 0 PCT P2274
64 LDO ENABLE PID 0 ON OFF P2200