Operating Instructions

SED2 VFD Startup, Operation, and Maintenance Manual
120 Siemens Building Technologies, Inc.
Table 11. JCI N2 Point Cross Reference to SED2.
On
Text
Off
Text
Point
Number
Name
Default
Value
Units Notes
Or Range
SED2
Ref.
AI1 FREQ OUTPUT 0 HZ No Override -650.00 to 650.00 r0024
AI2 SPEED 0 RPM No Override -16250 to 16250 r0022
AI3 CURRENT 0 A No Override 0 to 1638.35 r0027
AI4 TORQUE 0 NM No Override -3250.0 to 3250.0 r0031
AI5 DC BUS VOLTS 0 V No Override 0 to 32767 r0026
AI6 REFERENCE 0 HZ No Override -650.00 to 650.00 r0020
AI7 OUTPUT VOLTS 0 V No Override 0 to 32767 r0025
AI8 ANALOG IN 1 0 PCT No Override -300.0 to 300.0 r0754/0
AI9 ANALOG IN 2 0 PCT No Override -300.0 to 300.0 r0754/1
AI10 PI FEEDBACK 0 PCT No Override -100.0 to 100.0 r2266
AI11 ANALOG OUT 1 0 PCT No Override -100.0 to 100.0 r0774/0
AI12 ANALOG OUT 2 0 PCT No Override -100.0 to 100.0 r0774/1
AI13 PID SETP OUT 0 PCT No Override -100.0 to 100.0 r2250
AI14 PID OUTPUT 0 PCT No Override -100.0 to 100.0 r2294
AI15 ACTUAL PWR 0 KW No Override 0 to 327.67 r0032
AI16 TOTAL KWH 0 KWH No Override 0 to 32767 r0039
AI17 FREQ ACTUAL 0 PCT No Override -100.00 to 100.00 HIW
AO1 FREQ REF 0 PCT 0.00 to 100.00 HSW
BI1 ENABLED 0 No Override ON OFF ZSW:0
BI2 READY TO RUN 0 No Override READY OFF ZSW:1
BI3 STOP RUN 0 No Override RUN STOP ZSW:2
BI4 AT MAX FREQ 0 No Override MAX NO ZSW:10
BI5 CONTROL MODE 1 No Override SERIAL LOCAL ZSW:9
BI6 FAULT 0 No Override FAULT OK ZSW:3
BI7 WARNING 0 No Override WARN OK ZSW:7
BI8 DIGITAL IN 1 0 No Override ON OFF r0722:0
BI9 DIGITAL IN 2 0 No Override ON OFF r0722:1