Appendix B: SED2 Point Maps
Siemens Building Technologies, Inc. 121
Table 11. JCI N2 Point Cross Reference to SED2.
On
Text
Off
Text
Point
Number
Name
Default
Value
Units Notes
Or Range
SED2
Ref.
BI10 DIGITAL IN 3 0 No Override ON OFF r0722:2
BI11 DIGITAL IN 4 0 No Override ON OFF r0722:3
BI12 DIGITAL IN 5 0 No Override ON OFF r0722:4
BI13 DIGITAL IN 6 0 No Override ON OFF r0722:5
BI14 FWD REV 0 No Override FWD REV ZSW:14
BO1 CMD START 0 START STOP STW:0
BO2 RUN ENABLE 1 ENABLE OFF STW:3
BO3 FAULT ACK 0 ON OFF STW:7
BO4 HAND AUTO 0 HAND AUTO P0718
BO5 DIGITAL OUT 1 0 ON OFF P0731
BO6 DIGITAL OUT 2 0 ON OFF P0733
BO7 CMD FWD REV 0 REV FWD STW:11
BO8 ENABLE PID 0 ON OFF P2200
ADF1 ACCEL TIME 1 10.00 SEC 0.00 to 650.00 P1120
ADF2 DECEL TIME 1 10.00 SEC 0.00 to 650.00 P1121
ADF3 CURRENT LMT 150.0 PCT 10.0 to 400.0 P0640
ADF4 P GAIN 3.000 0.000 to 65.000 P2280
ADF5 I GAIN 0 SEC 0.000 to 60.000 P2285
ADF6 D GAIN 0 0.000 to 60.000 P2274
ADF7 FEEDBK GAIN 100.00 PCT 0.00 to 500.00 P2269
ADF8 LOW PASS 0 0.00 to 60.00 P2265
ADF9 PID SETP REF 0 PCT -200.0 to 200.0 P2240
ADF10 PID UP LMT 100.0 PCT -200.0 to 200.0 P2291
ADF11 PID LO LMT 0 PCT -200.0 to 200.0 P2292
ADF12 FREQ MAX 50.00 HZ 1.00 to 650.00 P2000
ADF13 RATED PWR 0 KW Read Only 0 to 327.67 r0206
ADF14 INVERTER VER 0 Read Only 0.00 to 327.67 r0018
ADI1 WDOG TIME 0 MS 9999 P2040