Operating Instructions

Commissioning
Siemens Building Technologies, Inc. 63
Parameter Description Action Setting/ Default
Quick Commissioning
0 = Ready to Run
1 = Quick
Commissioning
30 = Factory Setting
1. Press
to access
parameter r0000 and to
enter the SED2 parameter
mode.
2. Repeatedly press
to
advance to parameter
P0010.
3. Press
to access the
parameter values level.
4. Press
to advance
to 1.
5. Press
to confirm and
save the P0010=1 setting.
Setting = 1
Default = 0
P0010
NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is greater than 0 on completion of commissioning, P0010 is
automatically set back to 0.
Operation for Europe/
N. America
0 = 50 Hz, kW (Europe),
factory default
1 = 60 Hz, hp
(North America)
2 = 60 Hz, kW
(North America)
The setting of Motor
Frequency and Unit of
Measurement DIP switch 2
overrides P0100 settings 0
and 1.
See the Motor Frequency
and Unit of Measurement
DIP Switch Settings section
in this manual for details.
1. Press
to advance to
parameter P0100.
2. Press
to access the
parameter values level.
3. Press
to advance to 1.
4. Press
to confirm and
save the P0100=1 setting.
Setting = 1
Default = 0 or 1
(Default is
determined by
the setting of the
Motor
Frequency and
Unit of
Measurement
DIP switches.)
P0100
NOTES:
1. Stop the SED2 (that is, disable all pulses) before changing this parameter.
2. Changing P0100 resets all rated motor parameters, as well as other
parameters that depend on the rated motor parameters (such as P0340,
Calculation of Motor Parameters).