Operating Instructions

Commissioning
Siemens Building Technologies, Inc. 73
Automatic Restart
CAUTION:
P1210 setting 2 through 7 can cause the motor to restart
unexpectedly.
Parameter Description Action Setting/ Default
P1210 Automatic Restart
Enables SED2 automatic
restart after a supply power
break or after a fault.
P1210 = 0, Disabled:
Automatic restart is disabled.
P1210 = 1, Trip reset after
power on (P1211 disabled:
The inverter will
acknowledge (reset) faults;
that is, it will reset a fault
when it is re-applied. This
means the inverter must be
fully powered down, a
brownout is not sufficient.
The inverter will not run
until the ON command has
been toggled.
P1210 = 2, Restart after
supply power blackout
(P1211 disabled):
The inverter will
acknowledge the fault
F0003 at power on after
blackout and will restart the
drive. It is necessary that
the ON command is wired
via digital input (DIN).
1. Press
to enter the
SED2 parameter mode
and to display r0000.
2. Press
to advance
to parameter P1210.
3. Press
to access the
parameter values level.
4. Press
to advance
to desired setting.
5. Press
to confirm
and save the setting.
Minimum: 0
Default: 1
Maximum:
5=Control Board
Version 1.20
or earlier
6=Control Board
Version 1.30
7=Control Board
Version 1.40
Suggested:
3=Control Board
Version 1.20
or earlier
6=Control Board
Version 1.30
7=Control Board
Version 1.40