Installation Instructions

Document No. 129-373
Installation Instructions
October 2, 2009
Page 2 of 12 http://www.siemens.com/hvp/drives Siemens Industry, Inc.
Table 1. Bypass Frame Sizes and Power Ranges.
HP kW
208/240V
480V 575V
.5
A
A
C
.75
1
1.5
B
2
3
B
5
C
7.5
C
10
15
D
20
25
D D
30
E
40
F
50
E E
60
75
N/A F
F
100
125
HA1
N/A
Table 2. E-Bypass Output Current Ratings (Amps) Per NEC Motor Tables.
HP .5 .75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 HA1
208V
2.3
10.4
16.7
22
28
42
54
68
80
104
130
154
240V
2.2
9.6
15.2
22
28
42
54
68
80
104
130
154
480V
1.1
4.8
7.6
11
14
21
27
34
40
52
65
77
96
124
156
178
575V
.9 1.3 1.4 2.1 2.7 3.9 6.1 9 11 17 22 27 32 41 52 62 77 99 125
NOTE: Drives are current rated devices. Verify that the listed ratings are ≥ the motor full load current rating.