Installation Instructions

Table Of Contents
Document No. 129-374
Installation Instructions
October 2, 2009
Page 10 of 11 http://www.siemens.com/hvp/drives Siemens Industry, Inc.
Table 4. Wire Sizes and Tightening Torques for C-Bypass with 380V to 480V Drive.
Part
Number
Bypass
Frame
Size
HP kW Amps
Circuit Breaker
Disconnect
Switch
Overload Ground Lug
Wire
Size *
Torque,
lb-in
(Nm)
Wire
Size *
Torque,
lb-in
(Nm)
Wire
Size *
Torque,
lb-in
(Nm)
Range,
Amps
Max
Backup
Fuse,
Amps
Wire
Size *
Torque,
lb-in
(Nm)
VBA30.5---- A 0.5 0.37
1.1 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
.7 - 1.0
4 14-2 35 (4)
VBA30.7---- A 0.7 0.55
1.6 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
1.1 - 1.6
6 14-2 35 (4)
VBA31.0---- A 1.0 0.75
2.1 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
1.4 - 2.0
8 14-2 35 (4)
VBA31.5---- A 1.5 1.1
3.0 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
2.2 - 3.2
12 14-2 35 (4)
VBA32.0---- A 2.0 1.5
3.4 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
2.8 - 4
16 14-2 35 (4)
VBA33.0---- B 3.0 2.2
4.8 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
3.5 - 5
20 14-2 35 (4)
VBA35.0---- B 5.0 4.0
7.6 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(.8 - 1.2)
7 - 10
40 14-2 35 (4)
VBA37.5---- C 7.5 5.5
11 14-10 Cu 32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
9 - 12
45 14-2 35 (4)
VBA310---- C 10 7.5
14 14-10 Cu 32 (3.6) 18-10
13 to17
(1.5 - 1.7)
14-10
18 - 22
(2 - 2.5)
11 - 16
60 14-2 35 (4)
VBA315---- C 15 11.0
21 14-10 Cu
20 - 60
(2.2 - 6.8)
14-8
17 - 22
(1.9 - 2.5)
14-10
18 - 22
(2 - 2.5)
17 - 22
80 14-2 35 (4)
VBA320---- C 20 15.0
27 10-1/0 Cu
20 - 60
(2.2 - 6.8)
14-8
17 - 22
(1.9 - 2.5)
18-3
27 - 40
(3.1 - 4.5)
22 - 32
125 14-2 35 (4)
VBA325---- D 25 18.5
34 10-1/0 Cu
20 - 60
(2.2 - 6.8)
14-6
22 - 27
(2.5 - 3.1)
18-3
27 - 40
(3.1 - 4.5)
28 - 40
150 14-2 35 (4)
VBA330---- D 30 22.0
40 10-1/0 Cu
20 - 60
(2.2 - 6.8)
14-6
22 - 27
(2.5 - 3.1)
18-3
27 - 40
(3.1 - 4.5)
28 - 40
150 14-2 35 (4)
VBA340---- D 40 30.0
52 10-1/0 Cu
20 - 60
(2.2 - 6.8)
14-6
22 - 27
(2.5 - 3.1)
18-3
27 - 40
(3.1 - 4.5)
40 - 50
200 14-2 35 (4)
VBA350---- E 50 37.0
65 10-1/0 Cu
20 - 60
(2.2 - 6.8)
12-1
22 - 27
(2.5 - 3.1)
10-1/0
36 - 53
(4.1 - 6)
57 - 75
300 14-2 35 (4)
VBA360---- E 60 45.0
77 3-3/0 Cu 80 (9) 12-1
22 - 27
(2.5 - 3.1)
10-1/0
36 - 53
(4.1 - 6)
70 - 90
350 14-2 35 (4)
VBA375---- F 75 55.0
96 3-3/0 Cu 80 (9) 12-1
22 - 27
(2.5 - 3.1)
10-1/0
36 - 53
(4.1 - 6)
80 - 100
400 14-2/0 50 (5.6)
VBA3100---
-
F 100 75.0
124
6 - 350
kcmil Cu
120 - 275
(14 - 31.1)
6 - 350
kcmil
120 - 275
(13.5 - 31.1)
6-3/0
124 - 210
(14 - 23.7)
50 - 200 800 14-2/0 50 (5.6)
VBA3125---
-
F 125
90.0
156
6 - 350
kcmil Cu
120 - 275
(14 - 31.1)
6 - 350
kcmil
120 - 275
(13.5 - 31.1)
6-3/0
124 - 210
(14 - 23.7)
50 - 200 800 14-2/0 50 (5.6)
VBA3125---
HA1
F 90.0
178
6 - 350
kcmil Cu
120 - 275
(14 - 31.1)
6 - 350
kcmil
120 - 275
(13.5 - 31.1)
6-3/0
124 - 210
(14 - 23.7)
50 - 200 800 14-2/0 50 (5.6)
* Wire Size in AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum, 600 Vac.