Data Sheet for Product
Modbus RTU Interface Module for SED2 Technical Instructions
Document Number 155-767
February 25, 2009
Siemens Industry, Inc. Page 7
SED2 Parameter
Configuration
The Interface Module communicates with the SED2 VFD using the USS protocol
and the following parameter configuration:
• USS address set to 0
• USS baud rate set to 19.2K
• Parity set to Even
• Number of data bits set to 8
Configure SED2 VFD parameters to communicate with the MicroGate II, per Table 3.
Table 6. SED2 Parameter Settings to Communicate with the MicroGate II.
SED2
Parameter
Function Setting/Value
P0003 User Access Level 3 (Expert Level)
P0700[0] Command Source
5 if Starting/Stopping VFD from Modbus;
otherwise, DO NOT change.
P1000[0] Frequency Setpoint
Source
5 if Setting the Frequency from Modbus;
otherwise, DO NOT change.
P2009[0] USS Normalization 0 (Disabled)
P2010[0] USS Baud Rate 7 (19.2K baud)
P2011[0] USS Address 0
P2014[0] USS telegram off time
0 to Disable the USS Watchdog timer.
100 or greater to enable the USS Watchdog
timer.
NOTE: Do not set to a value from 1 to 99.
P2041[0] Protocol Selection for
RS485 port
0 (USS Protocol)