Product Description
SED2 Variable Frequency Drives (VFDs) control
pumps and fans in HVAC applications.
Product Numbers
SED2Variable Frequency Drives (VFDs)
Frame Sizes and Power Ratings
SED2 IP20 and NEMA Type 1 frame sizes and
power ranges are as follows:
SED2 IP54/NEMA Type 12 frame sizes and power
ranges are as follows:
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not follow the
procedures as specified.
CAUTION:
Equipment damage, or loss of
data may occur if you do not
follow the procedures as
specified.
Table 1. SED2 Full Load Amp (FLA) Ratings.
Output Rating
Output Current Max (amps)
HP kW
208V and
230V to
240V
(3-Phase)
380V to
480V
(3-Phase)
500V to
600V
(3-Phase)
0.5
2.3
1.2
0.75
3.0
1.6
1.0
3.9
2.1
1.4
1.5
5.5
3.0
2.1
2.0
7.4
4.0
2.7
3.0
10.4
5.9
3.9
4.0
13.6
7.7
5.4
5.0
17.5
10.2
6.1
7.5
22.0
13.2
9.0
10.0
28.0
18.4
11.0
15.0
42.0
26.0
17.0
20.0
54.0
32.0
22.0
25.0
68.0
38.0
27.0
30.0
80.0
45.0
32.0
40.0
104.0
62.0
41.0
50.0
130.0
75.0
52.0
60.0
154.0
90.0
62.0
75.0
110.0
77.0
100.0
145.0
99.0
125.0
178.0
125.0