Installation Instructions

Document No. 129-371
Installation Instructions
October 2, 2009
Siemens Industry, Inc. http://www.sbt.siemens.com/hvp/drives Page 7 of 8
Table 5. Cable Cross-Sections for Input Voltage
Range 3
ø AC 208V and 230V through 240V.
Output
Rating
kW (hp)
Input Power Cable Motor Cable
Min.
Cross-
Section
AWG
(mm2)
Max.
Cross-
Section
AWG
(mm2)
Min.
Cross-
Section
AWG
(mm2)
Max.
Cross-
Section
AWG
(mm2)
0.37 (.50)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
0.55 (.75)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
0.75 (1.0)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
1.1 (1.5)
17 (1)
9 (6)
17 (1)
9 (6)
1.5 (2.0)
15 (1.5)
9 (6)
17 (1)
9 (6)
2.2 (3.0)
13 (2.5)
9 (6)
17 (1)
9 (6)
3 (4.0)
11 (4)
7 (10)
15 (1.5)
7 (10)
4 (5.0)
11 (4)
7 (10)
11 (4)
7 (10)
5.5 (7.5)
11 (4)
7 (10)
11 (4)
7 (10)
7.5 (10)
7 (10)
2 (35)
7 (10)
2 (35)
11 (15)
5 (16)
2 (35)
16 (5)
2 (35)
15 (20)
5 (16)
2 (35)
5 (16)
2 (35)
18.5 (25)
3 (25)
2 (35)
5 (16)
2 (35)
22 (30)
2 (35)
2 (35)
2 (35)
2 (35)
30 (40)
0 (50)
-5 (150)
0 (50)
-5 (150)
37 (50)
-2 (70)
-5 (150)
-2 (70)
-5 (150)
45 (60)
-2 (70)
-5 (150)
-3 (95)
-5 (150)
Table 7. Cable Cross-Sections for Input Voltage
Range 3
ø AC 500V through 600V.
Output
Rating
kW (hp)
Input Power Cable Motor Cable
Min.
Cross-
Section
AWG
(mm2)
Max.
Cross-
Section
AWG
(mm2)
Min.
Cross-
Section
AWG
(mm2)
Max.
Cross-
Section
AWG
(mm2)
0.75 (1.0)
17 (1)
7 (10)
17 (1)
7 (10)
1.1 (1.5)
17 (1)
7 (10)
17 (1)
7 (10)
1.5 (2.0)
17 (1)
7 (10)
17 (1)
7 (10)
2.2 (3.0)
17 (1)
7 (10)
17 (1)
7 (10)
3 (4.0)
17 (1)
7 (10)
17 (1)
7 (10)
4 (5.0)
17 (1)
7 (10)
17 (1)
7 (10)
5.5 (7.5)
15 (1.5)
7 (10)
15 (1.5)
7 (10)
7.5 (10)
13 (2.5)
7 (10)
13 (2.5)
7 (10)
11 (15)
11 (4)
7 (10)
11 (4)
7 (10)
15 (20)
9 (6)
2 (35)
9 (6)
2 (35)
18.5 (25)
9 (6)
2 (35)
9 (6)
2 (35)
22 (30)
7 (10)
2 (35)
7 (10)
2 (35)
30 (40)
5 (16)
2 (35)
5 (16)
2 (35)
37 (50)
3 (25)
2 (35)
5 (16)
2 (35)
45 (60)
3 (25)
-5 (150)
3 (25)
-5 (150)
55 (75)
0 (50)
-5 (150)
2 (35)
-5 (150)
75 (100)
-2 (70)
-5 (150)
0 (50)
-5 (150)
90 (125)
-2 (70)
-5 (150)
0 (50)
-5 (150)
Table 6. Cable Cross-Sections for Input Voltage
Range 3
ø AC 380V through 480V.
Output
Rating
kW (hp)
Input Power Cable Motor Cable
Min.
Cross-
Section
AWG
(mm2)
Max.
Cross-
Section
AWG
(mm2)
Min.
Cross-
Section
AWG
(mm2)
Max.
Cross-
Section
AWG
(mm2)
0.37 (.50)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
0.55 (.75)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
0.75 (1.0)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
1.1 (1.5)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
1.5 (2.0)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
2.2 (3.0)
17 (1)
9 (6)
17 (1)
9 (6)
3 (4.0)
17 (1)
9 (6)
17 (1)
9 (6)
4 (5.0)
17 (1)
9 (6)
17 (1)
9 (6)
5.5 (7.5)
13 (2.5)
7 (10)
13 (2.5)
7 (10)
7.5 (10)
11 (4)
7 (10)
11 (4)
7 (10)
0.37 (.50)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
0.55 (.75)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
0.75 (1.0)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
1.1 (1.5)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
1.5 (2.0)
17 (1)
13 (2.5)
17 (1)
13 (2.5)
2.2 (3.0)
17 (1)
9 (6)
17 (1)
9 (6)
3 (4.0)
17 (1)
9 (6)
17 (1)
9 (6)
4 (5.0)
17 (1)
9 (6)
17 (1)
9 (6)
5.5 (7.5)
13 (2.5)
7 (10)
13 (2.5)
7 (10)
7.5 (10)
11 (4)
7 (10)
11 (4)
7 (10)
11 (15)
9 (6)
7 (10)
9 (6)
7 (10)
15 (20)
7 (10)
2 (35)
7 (10)
2 (35)
18.5 (25)
7 (10)
2 (35)
7 (10)
2 (35)
22 (30)
5 (16)
2 (35)
5 (16)
2 (35)
30 (40)
3 (25)
2 (35)
3 (25)
2 (35)
37 (50)
3 (25)
2 (35)
2 (35)
2 (35)
45 (60)
2 (35)
-5 (150)
2 (35)
-5 (150)
55 (75)
-2 (70)
-5 (150)
-2 (70)
-5 (150)
75 (100)
-2 (70)
-5 (150)
-3 (95)
-5 (150)
90 (125)
-2 (70)
-5 (150)
-3 (95)
-5 (150)
Input Power Connection
WARNING:
Use only permanently wired input power
connections.
Connect input power to SED2 terminals L1, L2,
and L3.