SED2 Advanced Operator Panel (AOP) Operating Instructions
SED2 AOP Operating Instructions 125-3206 Rev.
Rev. 2.0, May, 2007 NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document. All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license.
European Low Voltage Directive The SED2 VFD product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards: EN 60146-1-1 Semiconductor VFDs - General requirements and line commutated VFDs EN 60204-1 Safety of machinery - Electrical equipment of machine European Machinery Directive The SED2 VFD series does not fall under the scope of the Machinery Directive.
Table of Contents Table of Contents How to Use this Manual ................................................................................................ 1 Manual Organization .................................................................................................. 1 Manual Notations ....................................................................................................... 2 Where To Send Comments ......................................................................................
SED2 AOP Operating Instructons Timer Function ..............................................................................................................25 AOP Setup and Configuration .....................................................................................27 Setup Menu ................................................................................................................27 Backlighting .................................................................................................
How to Use this Manual How to Use this Manual The Advanced Operator Panel (AOP) enhances the user interface and communications capability of the SED2 Variable Frequency Drives (“SED2 VFD”). Manual Organization This manual contains the following sections: How to Use this Manual, describes the organization of this manual and symbols used throughout this manual. AOP Overview, shows the AOP main menu and details the AOP function keys.
SED2 AOP Operating Instructons Manual Notations Notation Symbol Meaning DANGER: Indicates that personal injury or loss of life may occur if you do not perform a procedure as specified. WARNING: Indicates that equipment damage, or loss of data may occur if you do not perform a procedure as specified. CAUTION: Indicates that equipment damage, or loss of data may occur if you do not perform a procedure as specified.
AOP Overview AOP Overview AOP Menu Structure The menus available on the AOP display depend on the currently active operating mode. The following diagram shows the menu structure when the AOP is in either the Local or Master operating mode.
SED2 AOP Operating Instructions Key Functions NOTE: This symbol is used throughout this manual to indicate a special keypad function. Key/ Function Functional Description Stops the motor. OFF1 Press this button to stop the SED2 within the selected ramp-down time. As part of the factory setting, this function is enabled for manual mode. OFF2 Press this button twice (or once with sustained pressure) to cause the motor to coast freely to a standstill.
AOP Overview Key/ Function Change Single Parameter Digit Functional Description Quickly change a single digit of a parameter value as follows: Ensure you are in the parameter value changing level. Press and the right hand digit blinks. If desired, press Press or to change the value of this digit. again and the next digit blinks. Perform Steps 3 and 4 until the required value appears. Press to leave the parameter value changing level. Siemens Building Technologies, Inc.
AOP Applications AOP issue A03/1.45 Y AOP issue A05/1.59 Y Y AOP issue B01/1.59 Y Y Y AOP issue B03/1.60 Y Y Y SED2 firmware 1.40 SED2 firmware 1.30 SED2 firmware 1.20 SED2 Valid Version Set Version 2.2 (August 7, 2006) SED2 firmware 1.15/1.17* AOP Start-Up & Initialization Y * These versions are no longer supported Y = Fully compatible = Not compatible Important Notes CAUTION: You can mount or remove the AOP while power is applied to the SED2 VFD.
AOP Overview If the AOP is the command source for the SED2, set USS Telegram Off Time for Serial Interface BOP Link P2014[1]=5000 (5 seconds). To do this, first set P0003=3. The P2014[1]=5000 setting causes the drive to trip if communications with the AOP control source is lost. If you have problems connecting to the SED2 drives, set the Auto Baud to OFF and the default baud rate to the same as the SED2. Power-on and Initialization 1.
SED2 AOP Operating Instructions Language Selection The AOP provides the capability to display information in five different languages. NOTE: Prior to language selection, the AOP has no control over the SED2 VFD. CAUTION: Memory Limitation: The delivered AOP supports English as well as four European languages: German, French, Spanish, and Italian. Due to internal memory limitations, you should delete one of these languages in order to upload the specified ten parameter sets that can be held on the AOP.
AOP Overview Quick Commissioning NOTE: Simultaneously press and , at any time, to display the main menu. The following table describes the main menu items. Menu Item Description Operate Displays the current status of the SED2 VFD/motor. Diagnostics Displays a recent fault history. Parameters Allows you to select a parameter group (similar to Parameter Filter P0004) and to configure individual parameters.
SED2 AOP Operating Instructions Use Press and to scroll through the parameters and to highlight Command Source P0700. to confirm the selection and the cursor advances to the parameter index. Use Press and to scroll through the indexes for P0700 and to highlight P0700[1] (index 1). to confirm the selection and the cursor advances to the parameter value. Use Press and to set P0700[1]=4 (USS on BOP/AOP local link). to confirm the setting and the cursor returns to the parameter.
AOP Overview The AOP display the current status of the SED2 and motor. The following table explains information on this display. Table 1. Status Information of an AOP Display with an Operating SED2. Data Description STOPPED Indicates the motor connected to the SED2 is not running (pulses disabled). RUNNING Indicates the motor connected to the SED2 is running (pulses enabled). FAULT Indicates a fault condition has occurred. The SED2 is not running.
SED2 AOP Operating Instructions AOP Applications Single Drive Control Using the AOP Per default, the AOP is configured to work with only one SED2 in Local mode. In Local mode, the AOP normally mounts directly onto the SED2. The RS-232 and RS-485 ports handle communications. Full operator control of the SED2 is available with access to all normal drive and AOP internal parameters.
AOP Overview If using the AOP as the normal control means for the SED2 VFD, it is recommended that USS Telegram Off Time for Serial Interface BOP Link P2014[1]=5000. (To do this, first set User Access Level P0003=3 [expert]). The P2014[1]=5000 setting causes the drive to trip if communications with the AOP control source are lost. 3. With the SED2 VFDs powered-up on the network, connect and power-up the AOP on the PMK. 4. On start-up of the AOP, select Mode from the main menu.
Editing Parameters Editing Parameters Parameter Access Levels You can edit SED2 VFD parameters via the AOP. Access levels control access to the SED2 VFD parameters. A higher access level corresponds to a more sophisticated level of control techniques available for the SED2 VFD applications.
Editing Parameters 5. Press to confirm the new parameter value. The AOP returns to the parameter screen so you can select another parameter, if desired. Press to return to the r0000 display. Press again to return to the previous menu. Press for several seconds to return to the status screen (normal operating mode). The parameter value that has been changed is retained within the AOP‟s internal memory, but not sent to the SED2. Should power to the SED2 or AOP be interrupted, all changes are lost.
SED2 AOP Operating Instructions 6. Press to access the index value. Use highlight the desired index value. and to scroll through the index values and to 7. Press to confirm the new index value. The AOP returns to the parameter selection screen so you can select another parameter, if desired. 8. To edit another indexed parameter, repeat Steps 3 to 6. NOTES: Simultaneously press and , at any time, to return to the main menu.
Editing Parameters 2. In the Internal mode, scroll through the list of parameter sets until the AOP parameter set appears. Press to confirm the selection. 3. Press again to select All parameters. 4. Use to access the internal AOP parameters.
SED2 AOP Operating Instructions 1. From the main menu, use and to scroll through the list of options and to highlight the Upread item. Press to confirm the selection. Press to cancel the upload process. The AOP displays an upload/upread menu. NOTE: In master mode, the AOP prompts for selection of a specific SED2 VFD from a list of the networked SED2 VFDs. 2. Use and to scroll through the list of parameter sets and to highlight the parameter set into which information will be written.
Editing Parameters 1. From the main menu, use and to scroll through the list of options and to highlight the Download item. Press to confirm the selection. Press to cancel the download process. The AOP displays a download menu. NOTE: In master mode, the AOP prompts for selection of a specific SED2 VFD from a list of the networked SED2 VFDs. 2. Use and to scroll through the list of parameter sets and to highlight the parameter set from which information will be copied. Press to confirm the selection. 3.
AOP Operating Modes AOP Operating Modes Selecting an Operating Mode The mode menu allows you to select the desired AOP operating mode. The following table summarizes the AOP operating modes and lists associated main menu items.
AOP Operating Modes 2. Press to confirm the selected operating mode (press NOTE: to return to the main menu.) To exit an operating mode, either follow the on-screen instructions or return to the main menu and select the mode menu to choose a different operating mode. Operating in Local Mode On initial power-up or after a reset, the AOP defaults to the Local operating mode. The Local mode operates only with one SED2. You can change the operating mode via the mode menu.
SED2 AOP Operating Instructions Operating in Master Mode (Broadcast Operation) In master mode, the network controls the SED2 VFDs either individually or by broadcast operation. A broadcast operation can simultaneously start or stop all networked SED2 VFDs. While in broadcast operation, note the following AOP functions: Since parameters cannot be edited globally, does not function in a broadcast operation. and still function in a broadcast operation.
AOP Operating Modes NOTE: The parameter set from the inverter must be saved into the AOP or a default parameter set must be saved into the AOP before using the PC to AOP connection kit. 1. The AOP must be in SLAVE mode. AOP is slave to PC will display on the AOP. a. From the AOP main menu, highlight MODE using the up or down arrows. Press the P button. b. From the MODE menu, highlight SLAVE using the up or down arrows. Press the P button. c. When AOP will be slave to PC.
SED2 AOP Operating Instructions 2. Open EasyComm. In the Drive Properties field, set as seen below: Set the Bus Address to the Parameter Set number (within the AOP) to be backed up or restored. NOTE: The parameter set stored in location 00 cannot be backed up via EasyComm. 3. Go online (RAM or EEPROM) with EasyComm as if connecting to a VFD directly. See the EasyComm Operating Manual (125-3360) for further information. 4. Backup or Restores are completed the same way as if connected to a VFD directly.
SED2 AOP Operating Instructions Timer Function NOTES: 1. Before using the timer function as a control method, set the AOP real time clock as described in the Set Time/Date section. 2. Setting a timing event for „every day‟, configures the same event for each day of the week separately. To clear an „every day‟ event, you must clear the event individually from each day. 3. When multiple events must be cleared from the Timer function, it may be easier to reset the AOP as described in the AOP Reset section. 4.
SED2 AOP Operating Instructions In general, use the following keys to set the timer: Press and Press to confirm the input. to scroll through input ranges. to cancel the input and to return to the previous entry. From the main menu, use and to scroll through the list of options and to highlight the Timer item. Press to confirm the selection. The AOP displays the timer screen. Use and to enable (ON) or disable (OFF) the AOP timer function.
SED2 AOP Operating Instructions AOP Setup and Configuration Setup Menu Using the Setup option from the AOP main menu, you can personalize the following characteristics of the AOP: Backlighting Welcome Text Screen Contrast Parameter Set Names (Expert Level and above only) Large Numbers User Defined Text Cursor Type Set Time/Date (Service Level only) Start Help AOP Reset Use the following procedure to access the Setup menu: 1.
SED2 AOP Operating Instructions 4. When you select ON for backlighting timer, the AOP displays a backlighting time setting screen. Use and to set the timer period of inactivity (in seconds). Press to confirm the setting and the AOP returns to the setup menu. NOTE: Simultaneously press and at any time to display relevant help screens. Setting the AOP Timer When in local or master mode, you can access the timer feature from the main menu.
AOP Setup & Configuration Large Number Display You can configure the AOP for a large-number display of the SED2 VFD frequency. In the Large Number Display mode, you can temporarily switch to normal display mode (4 lines) with the keys and . After an adjustable time delay, the display switches back to large characters. Use the following procedure to activate the large number display: Use Press and to highlight the Large Numbers option on the setup menu. to confirm the selection.
SED2 AOP Operating Instructions Welcome Text Use the following procedure to edit the welcome text that displays on the AOP at power-up: Use and to highlight Welcome Text option on the setup menu. Press to confirm the selection. The AOP displays a welcome text screen. Use and to select an ON or OFF welcome text status. Press to cancel this selection and to return to the setup menu. Press to confirm the selection and the AOP displays a text screen with the first character highlighted.
AOP Setup & Configuration Parameter Set Names Use the following procedure to edit the names associated with the ten AOP parameter sets. NOTE: This editing option is not available in the standard access level. Use and to highlight the Parameter Set Names option on the setup menu. Press to confirm the selection. The AOP displays a parameter set name screen. 2. Use and to scroll through the parameter sets and to highlight the name needing editing.
SED2 AOP Operating Instructions AOP Reset WARNING: The AOP reset function enables the deletion of all parameter sets and settings, internal faults, and message logs stored in the AOP. 1. Use and to highlight the AOP Reset option on the setup menu. Press to confirm the selection. The AOP displays an AOP reset screen. 2. Use and to select ON or OFF to enable or disable the AOP reset function respectively. Press to confirm the selection. Press to cancel this selection and to return to the setup menu. 3.
AOP Faults & Warnings AOP Faults and Warnings NOTE: If a fault/warning condition occurs on a SED2 VFD(s) to which an AOP connects, a fault/warning code displays with a description of the relevant fault/warning. For a list of fault/warning codes, see the SED2 VFD Operations & Maintenance Manual, (125-3202) Fault Indication/Fault Screen 1.
SED2 AOP Operating Instructions Multiple Faults If a SED2 VFD or network of VFDs reports more than one fault condition, the AOP displays all fault messages by cycling through them until they are all cleared. See Fault Indication/Fault Screen in this chapter to acknowledge each fault message.
AOP Faults & Warnings Siemens Building Technologies, Inc.
SED2 AOP Operating Instructions Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 Tel: +1 847-215-1000 Fax +1 847-215-1093 Siemens Building Technologies, Ltd. 2185 Derry Road West Mississauga, Ontario Canada L5N 7P6 Tel: +1 905-799-9937 Siemens Building Technologies AG Gubelstrasse 22 CH-6301 Zug Tel: +41 41 724 24 24 Fax +41 41 724 35 22 Siemens Building Technologies Ltd.