Operating Instructions
AOP Overview
Siemens Building Technologies, Inc. 7
If the AOP is the command source for the SED2, set USS Telegram Off Time for Serial
Interface BOP Link P2014[1]=5000 (5 seconds). To do this, first set P0003=3. The
P2014[1]=5000 setting causes the drive to trip if communications with the AOP control source
is lost.
If you have problems connecting to the SED2 drives, set the Auto Baud to OFF and the
default baud rate to the same as the SED2.
Power-on and Initialization
1. On initial power-up, the AOP performs internal self tests and displays a welcome screen.
2. After establishing initial AOP-to-SED2 VFD communications, the Start Help screen(s) appear.
If the current AOP display language is acceptable, continue with the Start Help section.
If you need to change the current AOP display language, continue with the Language
Selection section.