SED2 Conventional Bypass Options Operating Instructions Item Number 125-3215, Rev.
SED2 VFD Conventional Bypass Option Operating Instructions
NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document. All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license. WARNING The Siemens Building Technologies, Inc.
Table of Contents Table of Contents How to Use this Manual................................................................................................1 Manual Organization..................................................................................................1 Manual Notations .......................................................................................................1 Where To Send Comments .......................................................................................
How to Use this Manual How to Use this Manual Manual Organization This manual contains the following sections: • How to Use this Manual describes the organization of this manual and the symbols used throughout this manual. • Safety Instructions provides general guidelines for your safety and to prevent equipment damage. • Conventional Bypass Option Overview describes the Conventional Bypass Option. • Operation Overview provides an overview of the Conventional Bypass Option operating modes.
SED2 Conventional Bypass Option Operating Instructions Reference Documents The following SED2 VFD documentation is available from your local Siemens Building Technologies, Inc. representative: • SED2 VFD Startup, Operation & Maintenance Manual (125-3201), operating instructions and procedures for the SED2. • SED2 VFD Parameter Reference Guide (125-3214). • SED2 Variable Frequency Drives Submittal Sheet (154-042) • SED2 VFD with Bypass Submittal Sheet (154-044) 2 Siemens Building Technologies, Inc.
Safety Instructions Safety Instructions The following general guidelines are provided for your safety, to prevent damage, and to extend the service life of the SED2 product and any connected equipment. Read this information carefully. Specific Warnings, Cautions, and Notes are provided in the relevant sections of this manual. WARNINGS: NOTE: • The SED2 uses hazardous voltages and controls potentially dangerous rotating mechanical parts.
SED2 Conventional Bypass Option Operating Instructions Conventional Bypass Option Overview General Description During normal operation in a typical application, the input and output contactors close and the SED2 operates the motor (Figure 1). The bypass contactor provides the ability to operate the motor on utility power and eliminate the VFD from the motor control circuit. VFD0008R1 Input Device Input Device Drive Drive Motor Motor 2 Contactor Bypass 3 Contactor Bypass Figure 1.
Operation Overview Operation Overview • • • • Drive Mode − Drive output contactor closes (and drive input contactor if supplied). The motor is controlled by the SED2 output. − Change the position of the "Drive-Off-Bypass" switch to OFF and the Bypass stops the SED2 by opening digital input 4, stop 3. Local Bypass Operation − Requires a jumper between bypass control terminals 7 and 8. Jumper is supplied from the factory. − The system goes to Bypass by closing the bypass contactor.
SED2 Conventional Bypass Option Operating Instructions Operation Overview, continued a. Safety Input • 6 − Requires a jumper between bypass control terminals 3 and 4. Jumper is supplied from the factory. − Contact must be closed for the motor to be run in either the Drive or Bypass modes. WARNING: This contact disconnects the 120 Vac control power circuit. Essential Service Mode − Closing between terminals 13 and 16 forces the bypass contactor to close regardless of the selected operation.
Installation Instructions Installation Instructions Environmental Conditions Install the Conventional Bypass Option in a heated, indoor controlled environment that is free of moisture and conductive contaminants such as condensation and dust. The air entering the unit for ventilation/cooling must be clean and free from corrosive gases. The ambient temperature must be between 14°F and 104°F (-10°C to 40°C) and the relative humidity must be 0% to 95% non-condensing. Mechanical Installation Inspection 1.
SED2 Conventional Bypass Option Operating Instructions Mounting 1. To ensure safe installation, verify that the surface of the mounting location is level. 2. Mount the Conventional Bypass Option vertically with the SED2 operator panel, Conventional Bypass option switches, and disconnect accessible. 18.0 (457) = Protective Shield 12.0 (305) Depth 11.3 (287) Depth 9.7 (244) 12.0 (305) 12.0 (305) 36.0 (914) 12.0 (305) 12.0 (305) Depth 8.3 (211) 36.0 (914) 24.0 (610) 12.0 (305) 49.0 (1245) 36.
Installation Instructions 1 (2.5) CONDUIT KNOCKOUTS (2) 3/4 (1.9) CONDUIT KNOCKOUTS (2) VFD0204R1 3-1/2 (8.9) 2-3/4 (7.0) 4-5/8 (11.8) 6-3/8 (16.2) 8-3/8 (21.3) Figure 4. Frame Sizes A and B Conduit Locations. Viewed from Bottom; Dimensions in Inches (Centimeters). 1 (2.5) CONDUIT KNOCKOUTS (2) 3/4 (1.9) CONDUIT KNOCKOUTS (2) 3-1/2 (8.9) VFD0205R1 1-5/8 (4.1) 4-5/8 (11.8) 6-3/8 (16.2) 8-3/8 (21.3) Figure 5. Frame Size C Conduit Locations.
SED2 Conventional Bypass Option Operating Instructions 1 (2.5) CONDUIT KNOCKOUTS (3) 3/4 (1.9) CONDUIT KNOCKOUT 3/8 (1) CONDUIT KNOCKOUT 3-1/2 (8.9) 4-1/2 4 (11.4) (10.2) 2-1/2 (6.4) VFD0206R1 7-3/8 (18.8) 9-3/8 (23.9) 10-3/8 (26.4) 13-1/8 (33.5) Figure 6. Frame Sizes D and E Conduit Locations. Viewed from Bottom; Dimensions in Inches (Centimeters) 7-3/8 (18.7) 13-5/8 11-7/8 (34.6) (30.1) 15-3/8 (39.1) 20-3/8 (51.7) VFD0203R1 4-1/4 (10.8) 3/4 (1.9) AND 1 (2.5) CONDUIT KNOCKOUTS (3) 3 (7.
Installation Instructions Electrical Installation See Figure 8 for all Conventional Bypass Option wiring and Figure 9 for Control Connections. 1. Route shielded twisted pair (recommended wire type) cable, 24 gauge minimum control wiring in conduit through knockout and into housing (Figures 10 and 11). Connect control wiring per job-specific drawings. NOTES: • Terminate shield at control device. • Control wiring is 12 to 26 AWG and tightening torque is 4.4 lb-in.
SED2 Conventional Bypass Option Operating Instructions OPTIONAL SUPPLEMENTARY POWER FUSES - MAIN SHORT CIRCUIT PROTECTION BY OTHERS DISCONNECT (SEE NOTE 1) OR BREAKER FU1 L1 1L1 (T1) (L1) POWER 1L2 SUPPLY L2 3 PHASE (T2) (L2) 60 Hz L3 1L3 (T3) GND (L3) (6) (3) (4) (1) (2) 2L3 OPTIONAL INPUT LINE REACTOR A2 B1 B2 C1 C2 S 3L3 OPTIONAL OUTPUT LOAD REACTOR VFD R A1 3L2 (4) (3) (6) (5) (5) 2L2 OPTIONAL DRIVE INPUT CONTACTOR M3 3L1 (2) (1) GND GND LUG M1 2L1 T L1 U L2 V L3 W U1 U A
Installation Instructions Control Connections DRIVE CONTROL TERMINATIONS RL2 COM RL2 NO EXTERNAL 0 TO 10V 2 3 - DIN4 ISO 24VDC AIN2+ AIN2- 7 8 9 10 11 RR 109 6 108 DIN3 5 105 DIN2 AIN1+ 4 DIN1 +0VDC 3 AIN1- +10VDC 2 - 4.
SED2 Conventional Bypass Option Operating Instructions SED 2 VFD MOTOR WIRING VIA KNOCKOUT DISCONNECT SWITCH (OR OPTIONAL CIRCUIT BREAKER) GROUND LUGS (2) INPUT POWER WIRING VIA KNOCKOUT T3 T2 T1 SED2 VFD L3 L2 L1 MOTOR OVERLOAD BYPASS CONTACTOR OUTPUT CONTACTOR OUTPUT CONTACTOR CTB1 BYPASS CONTACTOR CTBI DISCONNECT SWITCH OR CIRCUIT BREAKER T1T2T3 TRANSFORMER L1 L2 L3 MOTOR WIRING VIA KNOCKOUT VFD0159R1 VFD0123R1 MOTOR OVERLOAD GROUND LUGS (2) INPUT POWER WIRING VIA KNOCKOUT Figure 10
Installation Instructions Access to Drive Connection Terminals To access the mains power and motor terminals, remove the operator panel, cover, and I/O module. 1 5192J09 5192J08 1 Removing Operator Panel (BOP or AOP). 1 5192J16 2 Removing Terminal Cover. Figure 13. Access to Connection Terminals for SED2 Frame Size A. Siemens Building Technologies, Inc.
SED2 Conventional Bypass Option Operating Instructions 1 1 2 5192J13 3 VFD0068R1 4 5 6 Figure 14. Access to Connection Terminals for SED2 Frame Size B and C. Figure 15. Access to Connection Terminals for SED2 Frame Size D and E. 1 2 4 6 3 5 4 J1 92 51 Figure 16. Access to Connection Terminals for SED2 Frame Size F. 16 Siemens Building Technologies, Inc.
Installation Instructions Table 1. Wire Sizes and Tightening Torques for C-Bypass with 208V Drive. Circuit Breaker Bypass Frame HP kW Amps Size Part Number VBA10.5---- A 0.5 0.37 2.3 VBA10.7---- A 0.7 0.55 3.0 VBA11.0---- A 1.0 0.75 3.9 VBA11.5---- B 1.5 1.1 5.5 VBA12.0---- B 2.0 1.5 7.4 VBA13.0---- B 3.0 2.2 10.4 VBA15.0---- C 5.0 4.0 16.7 VBA17.5---- C 7.5 5.5 22.0 VBA110.---- C 10 7.5 28 VBA115.---- D 15 11.0 42 VBA120.---- D 20 15.0 54 VBA125.
SED2 Conventional Bypass Option Operating Instructions Table 2. Wire Sizes and Tightening Torques for C-Bypass with 230V - 240V Drive. Circuit Breaker Part Number Bypass Frame HP kW Amps Size VBA20.5---- A 0.5 0.37 2.2 VBA20.7---- A 0.7 0.55 3.0 VBA21.0---- A 1.0 0.75 3.9 VBA21.5---- B 1.5 1.1 5.5 VBA22.0---- B 2.0 1.5 6.8 VBA23.0---- B 3.0 2.2 9.6 VBA25.0---- C 5.0 4.0 15.2 VBA27.5---- C 7.5 5.5 22 VBA210---- C 10 7.5 28 VBA215---- D 15 11.
Installation Instructions Table 3. Wire Sizes and Tightening Torques for C-Bypass with 380V - 480V Drive. Circuit Breaker Part Number VBA30.5---VBA30.7---VBA31.0---VBA31.5---VBA32.0---VBA33.0---- Bypass Frame HP kW Amps Torque, Wire Wire Size lb-in Size* Size* (Nm) A A A A A B 0.5 0.7 1.0 1.5 2.0 3.0 0.37 0.55 0.75 1.1 1.5 2.2 1.1 1.6 2.1 3.0 3.4 4.8 VBA35.0---- B 5.0 4.0 7.6 VBA37.5---- C 7.5 5.5 11 VBA310---VBA315---VBA320---- C C C 10 15 20 7.5 11.0 15.
SED2 Conventional Bypass Option Operating Instructions Table 4. Wire Sizes and Tightening Torques for C-Bypass with 500V - 600V Drive. Part Number Bypass Frame HP Size kW Amps Circuit Breaker VBA40.5---- C 0.5 0.37 .9 VBA40.7---- C 0.7 0.55 1.3 VBA41.0---- C 1.0 0.75 1.4 VBA41.5---- C 1.5 1.1 2.1 VBA42.0---- C 2.0 1.5 2.7 VBA43.0---- C 3.0 2.2 3.9 VBA45.0---- C 5.0 4.0 6.1 VBA47.5---- C 7.5 5.5 9 VBA410.---- C 10 7.5 11 VBA415.---- C 15 11.
Startup Procedures Start Up Procedures Preparation Check Step ( ) 1. The SED2 is thoroughly tested at the factory. Verify that the drive is free of shipping and installation damage. Shipping damage is not covered by the Siemens warranty; claims must be filed directly with the shipping company as soon as possible. ( ) 2. Review the Startup, Operation, and Maintenance Manual (125-3201). Review option instructions and schematics shipped with the drive. ( ) 3.
SED2 Conventional Bypass Option Operating Instructions Check Step ( ) 12. Record any other connections to the drive by terminal number to determine if special programming is required. ( ) 13. If applicable, verify that the building automation system logic is ready to perform adequately for start, stop, and speed command functions. This concludes the preparation process for SED2 startup.
Start Up Procedures ( ) 9. To start the Drive, press and then (green start key). The drive will ramp up to “10 HZ” (or minimum speed). Verify that the direction of motor rotation is correct. NOTE: If the direction of motor rotation is wrong, turn the Drive-Off-Bypass switch to OFF; and turn Power Off! Wait for five minutes. Swap wires on the motor terminals (T1(u), T2(v)) or on the output terminals of the motor overload relay.
SED2 Conventional Bypass Option Operating Instructions Check ( Step ) 17. Verify that running at full speed will NOT damage the system. Run the motor in bypass by turning the Drive-Off-Bypass switch to BYPASS. Record all the phase voltages and currents at this time to ensure that they are balanced and within ratings. ( ) 18. Turn the Drive-Off-Bypass switch to DRIVE and set panel to auto start/stop. Check speed references from application specific devices for appropriate operation.
Start Up Procedures Quick Commissioning Procedure, Continued Parameter P0010 Description Quick Commissioning 0 = Ready to Run Action Setting/Default 1. Press to access parameter r0000 and to enter the SED2 parameter mode. Setting = 1 Default = 0 1 = Quick Commissioning 30 = Factory Setting 2. Repeatedly press parameter P0010. to advance to to access the parameter 3. Press values level. 4. Press to advance to 1. to confirm and save the 5. Press P0010 = 1 setting. NOTES: 1.
SED2 Conventional Bypass Option Operating Instructions Quick Commissioning Procedure, Continued Parameter P0305* P0307* Description Rated Motor Current Action Setting/Default 0A to 10,000A. 1. Press P0305. Rated motor current (A) from motor nameplate. to access the parameter 2. Press values level. Rated Motor Power 0 kW or hp to 200 kW or hp. to advance to parameter 3. Press current. to advance to nominal 4. Press setting. to confirm and save the 1. Press P0307.
Start Up Procedures Quick Commissioning Procedure, Continued Parameter P0308*, or P0309 Description Rated Motor cosPhi (P308), or Rated Motor Efficiency (P0309) 0.000 to 1.00 (P0308) or 0.0 to 99.9 (P0309) Rated motor cosPhi or motor efficiency from motor nameplate. Action 1. Press to advance to parameter P0308 or P0309. to access the parameter 2. Press values level. to advance to nominal cosPhi 3. Press or motor efficiency. 4. Press setting. to confirm and save the 1. Press P0310.
SED2 Conventional Bypass Option Operating Instructions Quick Commissioning Procedure, Continued Parameter P0311* Description Rated Motor Speed Action Setting/Default to advance to parameter 0 to 40,000 1/min 1. Press P0311. Rated motor speed (rpm) from motor nameplate. to access the parameter 2. Press values level. A setting of 0 causes an internal calculation of this value. 3. Press speed. to advance to nominal motor 4. Press setting. to confirm and save the 1. Press P0640.
Start Up Procedures Quick Commissioning Procedure, Continued Parameter P0700(0)** Description Action Selection of Command Source (Start Command) 1. Press P0700. to advance to parameter Selects the command source as follows: 2. Press indexes. to access the parameter Setting/Default Setting = 2 Default = 2 0 = Factory default setting 1 = BOP (keypad) 2 = Terminal digital input to advance to index [0], 3. Press IN000, AUTO. 4 = USS on BOP link (AOP) 4. Press to confirm index selection.
SED2 Conventional Bypass Option Operating Instructions Quick Commissioning Procedure, Continued Parameter P1000[0]** Description Selection of Frequency Setpoint (Speed Command Source) Selects the frequency setpoint source as follows: 1 = Motor potentiometer setpoint/BOP (keypad) 2 = Analog input 3 = Fixed frequency setpoint 4 = USS on BOP Link/AOP 5 = USS on COM link Action Setting/Default 1. Press P1000. to advance to parameter 2. Press indexes.
Start Up Procedures Quick Commissioning Procedure, Continued Parameter P1000[1]** Description Selection of Frequency Setpoint (Speed Command Source) Selects the frequency setpoint source as follows: 1 = Motor potentiometer setpoint/AOP 2 = Analog input 3 = Fixed frequency 4 = USS on BOP Link/AOP Action 1. Press to advance to index [1], IN001, HAND. 2. Press to confirm index selection. 3. Press to advance to 1. 4. Press setting. to confirm and save the Setting/Default Setting = 1 Default = 1 5.
SED2 Conventional Bypass Option Operating Instructions Quick Commissioning Procedure, Continued Parameter P1082 Description Maximum Motor Frequency 0 Hz to 650 Hz Maximum motor frequency at which the motor will run regardless of the frequency setpoint. This value applies to both clockwise and counterclockwise rotation. Action 1. Press P1080. Setting/Default to advance to parameter to access the parameter 2. Press values level. 3. Press to advance it desired value. 4. Press setting.
Start Up Procedures Quick Commissioning Procedure, Continued Parameter P3900 Description End Quick Commissioning 0 = End without motor calculation or factory reset. 1 = End with motor calculation and factory reset (recommended on SED2 without bypass option). Action 1. Press P3900. to advance to parameter Setting/Default Setting = 3 Default = 0 2. Press to access the parameter values level. 3. Press to advance to 3. 4. Press to confirm the setting. 2 = End with motor calculation and with I/O reset.
SED2 Conventional Bypass Option Operating Instructions Additional Parameter Settings NOTE: If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP display alternately shows setpoint values and the actual value (0 Hz). Flying Start Parameter P1200 Description Flying Start Starts SED2 into a spinning motor by rapidly changing the output frequency of the SED2 until the actual motor speed is found. Then, the motor runs up to setpoint using the normal ramp time.
Start Up Procedures Flying Start, Continued Parameter P1202 Description Motor Current: Flying Start Defines search current used for flying start. Value is in % based on the rated motor current (P0305). Action 1. Press to enter the SED2 parameter mode and to display r0000. 2. Press P1202. 3. to access the parameter Press values level. 4. Press value. to advance to desired 5. Press setting.
SED2 Conventional Bypass Option Operating Instructions Automatic Restart CAUTION: Settings 2 through 7 can cause the motor to restart unexpectedly. Parameter P1210 Description Automatic Restart Enables SED2 restart after a supply power break or after a fault. P1210 = 0, Disabled: Automatic restart is disabled. P1210 = 1, Trip reset after power on (P1211 disabled: The inverter will acknowledge (reset) faults; that is, it will reset a fault when it is re-applied.
Start Up Procedures Automatic Restart, Continued Parameter Description P1210 (Continued) P1210 = 4, Restart after supply power brownout (P1211 disabled): For these settings it is fundamental that the drive only restarts if it has been in a RUN state at the time of the fault (F0003). The inverter will acknowledge the fault and will restart the drive after a blackout or brownwout.
SED2 Conventional Bypass Option Operating Instructions Automatic Restart, Continued Parameter Description P1210 (Continued) P1210 = 7, Restart after supply power brown/blackout or fault (P1211 enabled): This setting is for use where an external bypass system or process is interlocked with a relay that is set to P0731/P0732=52.3 (fault). The inverter functions the same as P1210=6 (trip on brownout, blackout or fault) but uses P1211 and only sets the fault bit P0731/P0732=52.
Start Up Procedures Automatic Restart, Continued Parameter P1211 P1212 P1213 Description Number of Restart Attempts Specifies the number of times SED2 will attempt to restart after supply power brownout or fault, if P1210 automatic restart is activated. Time to First Restart Selects the time (seconds) before the SED2 is restarted for the first time if P1210 automatic restart is activated.
SED2 Conventional Bypass Option Operating Instructions Pulse Frequency Parameter P1800 Description Pulse Frequency Sets pulse frequency (kHz) of power switches in SED2. The frequency can be changed in increments of 2 kHz. Pulse frequencies > 4 kHz selected on 380V to 480V units reduce the maximum continuous motor current. Action 1. Setting/Default Press to enter the SED2 parameter mode and to display r0000. 2. Press P1800. 3. to access the parameter Press values level. 4. Press value.
Start Up Procedures Motor Data Identification Parameter P1910 Description Motor Data Identification Performs stator resistance measuring. 0 = Disabled. 1 = Identification of Rs with parameter change. Action 1. Press to enter the SED2 parameter mode and to display r0000. 2. Press P1910. 3. to access the parameter Press values level. 4. Press 2 = Identification of Rs without parameter change. 3 = Identification of the saturation characteristic with parameter change.
SED2 Conventional Bypass Option Operating Instructions Motor Data Identification Continued Parameter P1910 (Continued) Description Action 6. Press Setting/Default to advance to setting P1910=3. Press save the setting. to confirm and When P1910=3, Alarm 0541 (motor data identification active) is output and internally P0340 is set to 2. Initiate the measuring operation with a continuous (steady-state) ON command.
Start Up Procedures Reset to Factory Defaults Parameter P0010 P0970 Description Reset to Factory Default Resets SED2 parameters to the factory defaults. Action 1. to enter the SED2 Press parameter mode and to display r0000. 2. Press P0010. 3. to access the parameter Press values level. 4. Press to advance to 30. 5. Press setting. to confirm and save the 6. Press P0970. to go to parameter 7. to access the parameter Press values level. 8. Press to advance to 1. 9. Press setting.
SED2 Conventional Bypass Option Operating Instructions Required SED2 Parameter Settings The factory programs the following SED2 parameters before shipping. If these parameters are changed or if the SED2 is ever reset to factory default, you must reset these parameters as follows: Parameter Setting P0704 in000 3 P0704 in001 3 NOTES: 1. The SED2 Fault must always be programmed as a fault. Do not change the SED2 fault relay for other uses via P0731. 2.
Technical Specifications Technical Specifications Table 5. C-Bypass Specifications. Specifications Description 208V, 3AC ± 10% 240V, 3AC ± 10% Input Voltage (3-phase) 480V, 3AC ± 10% 575V, 3 AC ± 10% Operating: 14°F to 104°F (-10°C to 40°C) Temperature Storage: -40°F to 158°F (-40°C to 70°C) Humidity 0 to 95% rh, non-condensing Table 6. Drive Specifications. Drive Specifications Description Input voltage and power ranges (3 phase) Amps 200V to 240V, 3 AC ± 10%. 1/2 hp to 60 hp (2.
SED2 Conventional Bypass Option Operating Instructions Table 7. Drive Specifications.
Wiring Diagrams Wiring Diagrams ' $ # ! & & 8.
SED2 Conventional Bypass Option Operating Instructions Control Terminals DRIVE CONTROL TERMINATIONS RL2 COM RL2 NO EXTERNAL 0 TO 10V 2 3 - ISO 24VDC AIN2+ AIN2- 7 8 9 10 11 RR 109 DIN4 6 108 DIN3 5 105 DIN2 AIN1+ 4 DIN1 +0VDC 3 AIN1- +10VDC 2 - 4.
Troubleshooting Troubleshooting Description of Problem Possible Cause Commanding the SED2 to start closes the bypass contactor. SED2 required programming for bypass operation has not been programmed in the VFD. Make appropriate VFD programming changes. See Required SED2 Parameter Setting. Contactors do not close. • Main input short circuit protection has opened. • Control power fuse has opened. • Safety circuit is open. • Motor overload needs to be reset. • Loose control wire connection.
SED2 Conventional Bypass Option Operating Instructions Fuses Verify that 120 Vac power is available on the secondary side of the Conventional Bypass Option power transformer. If power is not proper, check the Conventional Bypass Option components, such as: • Power transformer • Power transformer fuses (F1, F2, and F3). Table 8 provides fuse replacement information. Table 8. Fuse Replacement Information. Bypass Option Part Number Primary Fuse (F1 and F2) Secondary Fuse (F3) VBA10.5… to VBA17.
Troubleshooting Siemens Building Technologies, Inc.