Operating Instructions

SED2 Conventional Bypass Option Operating Instructions
6 Siemens Building Technologies, Inc.
Operation Overview, continued
a. Safety Input
Requires a jumper between bypass control terminals 3 and 4. Jumper is supplied from
the factory.
Contact must be closed for the motor to be run in either the Drive or Bypass modes.
WARNING:
This contact disconnects the 120 Vac control power circuit.
Essential Service Mode
Closing between terminals 13 and 16 forces the bypass contactor to close regardless of
the selected operation.
All calls to open the bypass contactor are ignored except the opening of this contact or
the removal of main power.
WARNING:
All calls to open the bypass include ignoring of the tripping of the
mechanical overload and opening of the safety input. This procedure should
be performed with extreme care.