Operating Instructions
SED2 Conventional Bypass Option Operating Instructions
26 Siemens Building Technologies, Inc.
Quick Commissioning Procedure, Continued
Parameter Description Action Setting/Default
P0305*
Rated Motor Current
0A to 10,000A.
Rated motor current (A)
from motor nameplate.
1. Press
to advance to parameter
P0305.
2. Press
to access the parameter
values level.
3. Press
to advance to nominal
current.
4. Press
to confirm and save the
setting.
Setting =
Motor
nameplate
Default =
Varies by
model
P0307*
Rated Motor Power
0 kW or hp to 200 kW or
hp.
Rated motor power (kW or
hp) from motor nameplate.
If P0100 =1 (60 Hz, hp,
North America), then
motor power is in hp.
1. Press
to advance to parameter
P0307.
2. Press
to access the parameter
values level.
3. Press
to advance to nominal power.
4. Press
to confirm and save the
setting.
Setting =
Motor
nameplate
Default =
Varies
(hp/voltage
dependent)
* Motor related parameters.