Operating Instructions
Start Up Procedures
Siemens Building Technologies, Inc. 29
Quick Commissioning Procedure, Continued
Parameter Description Action Setting/Default
P0700(0)**
Selection of Command
Source
(Start Command)
Selects the command
source as follows:
0 = Factory default setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link
(AOP)
5 = USS on COM link
6 = CB (Communications
board or module) on COM
link (P1/N2)
1. Press
to advance to parameter
P0700.
2. Press
to access the parameter
indexes.
3. Press
to advance to index [0],
IN000, AUTO.
4. Press
to confirm index selection.
5. Press
to advance to 2.
6. Press
to confirm and save the
setting.
Setting = 2
Default = 2
NOTE:
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1
to 2 resets all digital inputs to default settings.
P0700[1]**
Selection of Command
Source
(Start Command)
Selects the command
source as follows:
0 = Factory default setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link
(AOP)
5 = USS on COM link
6 = CB (Communications
board or module) on COM
link (P1/N2)
1. Press
to advance to index [1],
IN001, HAND.
2. Press
to confirm index selection.
3. Press
to advance to 1.
4. Press
to confirm and save the
setting.
5. Press
again to return to the
parameter selection level.
Setting = 1
Default = 1
NOTE:
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1
to 2 resets all digital inputs to default settings.
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.