Operating Instructions
SED2 Conventional Bypass Option Operating Instructions
30 Siemens Building Technologies, Inc.
Quick Commissioning Procedure, Continued
Parameter Description Action Setting/Default
P1000[0]**
Selection of Frequency
Setpoint
(Speed Command
Source)
Selects the frequency
setpoint source as follows:
1 = Motor potentiometer
setpoint/BOP (keypad)
2 = Analog input
3 = Fixed frequency
setpoint
4 = USS on BOP
Link/AOP
5 = USS on COM link
6 = CB (Communications
board or module) on COM
link/P1-N2
communications
1. Press
to advance to parameter
P1000.
2. Press
to access the parameter
indexes.
3. Press
to advance to index [0],
IN000, AUTO.
4. Press
to confirm index selection.
5. Press
to advance to 2.
6. Press
to confirm and save the
setting.
Setting = 2
Default = 2
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.