Operating Instructions

Start Up Procedures
Siemens Building Technologies, Inc. 31
Quick Commissioning Procedure, Continued
Parameter Description Action Setting/Default
P1000[1]**
Selection of Frequency
Setpoint
(Speed Command
Source)
Selects the frequency
setpoint source as follows:
1 = Motor potentiometer
setpoint/AOP
2 = Analog input
3 = Fixed frequency
4 = USS on BOP
Link/AOP
5 = USS on COM link
6 = CB (Communications
board or module) on COM
link/P1-N2
communications
1. Press
to advance to index [1],
IN001, HAND.
2. Press
to confirm index selection.
3. Press
to advance to 1.
4. Press
to confirm and save the
setting.
5. Press
again to return to the
parameter selection level.
Setting = 1
Default = 1
P1080
Minimum Motor
Frequency
0 Hz to 650 Hz
Minimum motor frequency
at which the motor will run
irrespective of the
frequency setpoint. This
value applies to both
clockwise and
counterclockwise rotation.
1. Press
to advance to parameter
P1080.
2. Press
to access the parameter
values level.
3. Press
to advance to desired value.
4. Press
to confirm and save the
setting.
Site Setting
(20% to 30%
Max)
Default = 10
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.