Operating Instructions

Start Up Procedures
Siemens Building Technologies, Inc. 33
Quick Commissioning Procedure, Continued
Parameter Description Action Setting/Default
P3900
End Quick
Commissioning
0 = End without motor
calculation or factory
reset.
1 = End with motor
calculation and factory
reset (recommended on
SED2 without bypass
option).
2 = End with motor
calculation and with I/O
reset.
3 = End with motor
calculation but without
I/O reset
(recommended with
SED2 with bypass
option).
1. Press
to advance to parameter
P3900.
2. Press
to access the parameter
values level.
3. Press
to advance to 3.
4. Press
to confirm the setting.
Setting = 3
Default = 0
NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is less than 0 on completion of commissioning, P0010 is automatically set back to 0.
3. If P0700 either indeed was changed during this process, programming of P0704 = 3 is required.