Startup Procedures
Siemens Building Technologies, Inc. 31
Quick Commissioning Procedure
Parameter P0010 is the Commissioning Parameter Filter. It allows you to select a group of parameters
that can be used for quick commissioning, including motor data, and motor ramp-up and ramp-down
settings.
It is important to use parameter P0010 to commission the SED2, P0003 to select the access level for
using parameters, and P0004 to filter the parameters according to their functionality. When
Commissioning Parameter Filter P0010 = 1, it initiates the quick commissioning procedure.
It is recommended that you use the quick commissioning procedure. However, experienced users may
commission the equipment without the P0004 filter functions.
At the end of the quick commissioning procedure, set parameter P3900 = 3. This setting performs the
necessary motor calculations and sets all remaining parameters (those not included in P0010 = 1) to the
factory default values. If 3900 is set to a value greater than 0, P0010 is automatically reset to 0.
(If P0010 = 1, the SED2 cannot start.) The process of performing motor calculations and setting all
parameters to factory default values is only possible via quick commissioning.
Parameter Description Action Setting/Default
P0003
User Access Level
Allows you to access more
parameters.
1 = Standard
2 = Extended
3 = Expert
1. Press to access parameter
r0000 and to enter the SED2
parameter mode.
2. Press
to advance to
parameter P0003.
3. Press
to access the
parameter values level.
4. Press
to advance to 3
(expert level).
5. Press
to confirm and save
the P0003=3 setting.
Setting = 3
Default = 1
NOTE:
Before starting quick commissioning, set P0003 = 3 to ensure all necessary parameters are available during quick
commissioning.