Operating Instructions
Startup Procedures
Siemens Building Technologies, Inc. 37
Parameter Description Action Setting/Default
P1000[0]**
Selection of Frequency
Setpoint
(Speed Command Source)
Selects the frequency setpoint
source as follows:
1 = Motor potentiometer
setpoint/BOP (keypad)
2 = Analog input
3 = Fixed frequency setpoint
4 = USS on BOP Link/AOP
5 = USS on COM link
6 = CB (Communications board
or module) on COM link/P1-N2
communications
1. Press
to advance to
parameter P1000.
2. Press to access the
parameter indexes.
3. Press
to advance to index
[0], IN000, AUTO.
4 Press
to confirm index
selection.
5. Press
to advance to 2.
6. Press
to confirm and save
the setting.
Setting = 2
Default = 2
P1000[1]**
Selection of Frequency
Setpoint
(Speed Command Source)
Selects the frequency setpoint
source as follows:
1 = Motor potentiometer
setpoint/AOP
2 = Analog input
3 = Fixed frequency
4 = USS on BOP Link/AOP
5 = USS on COM link
6 = CB (Communications board
or module) on COM link/P1-N2
communications
1. Press
to advance to index
[1], IN001, HAND.
2. Press
to confirm index
selection.
3. Press
to advance to 1.
4. Press
to confirm and save
the setting.
5. Press
again to return to the
parameter selection level.
Setting = 1
Default = 1
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.