Operating Instructions

SED2 VFD NEMA Type 3R/3RHE Bypass Operating Instructions
40 Siemens Building Technologies, Inc.
Parameter Description Action Setting/Default
P3900
End Quick Commissioning
0 = End without motor calculation
or factory reset.
1 = End with motor calculation
and factory reset (recommended
on SED2 without bypass option).
2 =End with motor calculation
and with I/O reset.
3 =End with motor calculation but
without I/O reset (recommended
with SED2 with bypass option).
1. Press
to advance to
parameter P3900.
2. Press to access the
parameter values level.
3. Press
to advance to 1.
4. Press
to confirm the
setting.
Setting = 1
Default = 0
NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.
3. If P0700 either indeed was changed during this process, programming of P0704 = 3 is required.