Data Sheet for Product

Submittal Sheet
Document No. 154-086
February 5, 2009
SED2 VFD NEMA Type 3R Bypass/Air Conditioner
http://www.sbt.siemens.com/hvp/drives Siemens Industry, Inc.
Description
The NEMA Type 3R Bypass with Air Conditioner allows
SED2 to be employed in a harsh environment.
The SED2 is designed specifically for HVAC applications
and supports a variety of digital and analog I/O and provides
built-in PID features to control pumps and fans. For
information on the family of SED2 VFDs, see the SED2
Variable Frequency Drives Submittal Sheet (154-042).
Features
Bypass Power
3-Contactor: Input, Output, and Bypass
Overload protection in bypass mode.
Step-down transformer with fused primary and
secondary.
Contactors electrically and mechanically
interlocked.
Drive test function.
Complete electrical isolation of drive.
Input Device
Fused disconnect (optional).
All doors are interlocked and padlockable.
Circuit breaker.
Reactor Options
Line reactor mounted in bypass enclosure.
Line reactor supplied separately (in NEMA Type
3R enclosure).
Load reactor (in NEMA Type 3R enclosure)
supplied separately.
Air Conditioner
NEMA Type 4.
Cooling capacity of 1,000 to 20,000 BTUH.
Digital temperature controller.
Active condensate management system.
Unit efficiency.
Compressor Protection System.
Bypass Control
Auto Bypass
Relay logic allows user to send the motor to bypass
mode based on the drive’s programmable relay.
Enable Input
Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
Common Remote Start/Stop
Can be used in both drive and bypass mode.
Essential Services Mode
Typically used for smoke purge; the motor goes to
bypass regardless of the selected mode.
No call to stop will have an effect, including open
safety or stop commands.
Only turning the power off or opening this contact
will stop the motor.
Bypass Door Mounted Control Devices
3-Contactor Units
Drive-Off-Bypass selector
Bypass pilot light
Drive Test On-Off selector

Summary of content (7 pages)