Data Sheet for Product

SED2 VFD NEMA Type 3R Bypass/ Air Conditioner Submittal Sheet
Document No. 154-086
February 5, 2009
Siemens Industry, Inc. http://www.sbt.siemens.com/hvp/drives Page 3 of 7
Table 1. NEMA Type 3R Bypass and NEMA Type 3R Bypass with Air Conditioner
Output Current Ratings (Amps)Per NEC Motor Tables.
HP .5 .75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125
208V
2.3
3.9
5.5
10.4
16.7
22
28
42
54
68
80
104
130
154
240V
2.2
3.9
5.5
9.6
15.2
22
28
42
54
68
80
104
130
154
480V
1.1
2.1
3.0
4.8
7.6
11
14
21
27
34
40
52
65
77
96
124
156
575V
.9
1.4
2.1
3.9
6.1
9
11
17
22
27
32
41
52
62
77
99
125
NOTE: Drives are current rated devices. Verify that the listed ratings are ≥ the motor full load current rating.
Wiring Diagrams
Figure 2. NEMA Type 3R Bypass 120 Vac Control Circuit.