Data Sheet for Product

SED2 Variable Frequency Drives Submittal Sheet
Document No. 154-042
May 9, 2011
Siemens Industry, Inc. Page 3 of 7
Technical Data
Table 1. Drive Specifications.
Drive Specifications Description
Input voltage and power ranges
(3-phase)
208V and 230V to 240V, 3 ac±10%. 1 hp to 60 hp (3.9 amps to 154 amps)
380V to 480V, 3 ac ±10% 1 hp to 125 hp (2.1 amps to 178 amps)
500V to 600V, 3 ac ±10% 1 hp to 125 hp (2.1 amps to 125 amps)
Input frequency 47 Hz to 63 Hz
Output frequency 0 Hz to 150 Hz
Power factor 0.9
VFD degree of efficiency 96% to 97%
Switch-on current Less than nominal input current
Auxiliary supply 24V Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA
Overload capacity 110% for 60 seconds
Control method Linear, parabolic and programmable V/f; and flux current control low-power mode
PWM frequency 2k Hz to 16k Hz (adjustable in 2k Hz increments)
Fixed frequencies 15 programmable
Skip frequency bands 4 programmable
Setpoint resolution 0.01 Hz digital
0.01 Hz serial
10 bit analog
Digital inputs (sink/source) 6: fully programmable and scalable isolated digital inputs, switchable
Analog inputs 2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or
Ni 1000 input
Relay outputs 2: configurable 30 Vdc/5A (resistive), 250 Vac/2A (inductive)
Analog outputs 2: programmable (0/4 mA to 20 mA, or 0 Vdc to 10 Vdc)
Serial interface RS-485 transmission rate: Up to 38.4k Baud
Protocols: USS, P1 and N2
Protection level IP20
NEMA Type 1 with protective shield and gland plate installed
IP54/NEMA Type 12
Temperature ranges Operating: 14°F to 104°F (–10°C to 40°C)
Storage: –40°F to 158°F (–40°C to 70°C)
Humidity 95% rh, non-condensing
Operational altitudes Up to 3280 ft (1000m) above sea level without derating
Protection features Under-voltage, Over-voltage, Overload, Ground fault, Short circuit, Stall prevention,
Locked motor, Motor overtemperature l
2
t PTC, Over-temperature, Parameter PIN
protection.
Standards UL, cUL, CE, C-tick
CE conformity Conformity with EC Low Voltage Directive 73/23/EEC
NOTE: SED2 Compliance with EN61000-3-12:
From September 1st, 2005 all electrical apparatus covered by the EMC directive will have to comply with EN61000-
3-12 “Limits for harmonic currents produced by equipment connected to public low voltage systems with input
currents > 16A and =< 75 A per phase”.
Siemens variable speed drives of the product range SED2 (Micromaster 436) fulfill the requirements of the EN
61000-3-12 (without the need for external line reactors) regarding the THD values of Table 3 under the pre
condition of Rsce > 190. The required PWHD values will not be achieved. Due to this fact it is recommended to
apply for connection approval at the local electricity board.
The local electricity board will evaluate among many other data the content of the 5th harmonic current and the Line
Power Factor "Lambda”, which is the ratio of active power and apparent power.
Siemens frequency inverters are optimized in design and operation characteristics regarding energy efficiency and
less interference with line supplies.