SED2 Variable Frequency Drives Operation & Maintenance Manual
SED2 VFD Operation & Maintenance Manual
SED2 Variable Frequency Drives Operation & Maintenance Manual 125-3202 Rev.
SED2 VFD Operation & Maintenance Manual
Rev. EA, November, 2006 NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document. All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license.
SED2 VFD Operation & Maintenance Manual
Table of Contents Table of Contents Chapter 1 — How To Use This Manual ....................................................................... 1 Manual Organization.................................................................................................. 1 Manual Notations ....................................................................................................... 2 Where To Send Comments .......................................................................................
SED2 VFD Operation & Maintenance Manual Chapter 5 — Commissioning....................................................................................... 23 DIP Switch Settings ................................................................................................... 24 Motor Frequency & Units of Measurement Switches ........................................... 24 Analog Input Switches .......................................................................................... 24 Prerequisites .......
Table of Contents Reversal of the Motor’s Direction of Rotation.................................................. 53 OFF Functions ...................................................................................................... 53 OFF1 ............................................................................................................... 53 OFF2 ............................................................................................................... 54 OFF3 .............................
SED2 VFD Operation & Maintenance Manual I/O, Point Database, and Parameters........................................................................ 89 Hardware Inputs and Outputs .............................................................................. 89 Point Database ..................................................................................................... 89 Ordering Notes .....................................................................................................
Table of Contents Operation with a Residual Current Device (RCD) ..................................................... 182 Appendix D: Programming .......................................................................................... 183 Bypassing the SED2 .................................................................................................. 183 Parameter setup for bypass function (commissioning) ........................................ 183 Hibernation Mode .................................
SED2 VFD Operation & Maintenance Manual VI Siemens Building Technologies, Inc.
Chapter 1 - How to Use This Manual How To Use This Manual This manual is written for the owner and user of Siemens Building Technologies Open Processor with York Driver, referred to as Open Processor for the remainder of this manual. It is designed to help you become familiar with the Open Processor and its applications. This manual is written for installers, technicians, service engineers, operators, and users of Siemens Building Technologies SED2 Variable Frequency Drives (“SED2 or SED2 drives”).
SED2 VFD Operation & Maintenance Manual Manual Notations Notation Symbol Meaning DANGER: Indicates that personal injury or loss of life may occur if you do not perform a procedure as specified. WARNING: Indicates that equipment damage, or loss of data may occur if you do not perform a procedure as specified. CAUTION: Indicates that equipment damage, or loss of data may occur if you do not perform a procedure as specified. NOTES: (no symbol) Provides other important information or helpful hints.
Chapter 2 – Safety Instructions Chapter 2 — Safety Instructions General The following general guidelines are provided for your safety, to prevent damage, and to extend the service life of the SED2 product and any connected equipment. Read this information carefully. Specific Warnings, Cautions, and Notes are provided in the relevant sections of this manual. WARNING: NOTE: • The SED2 uses hazardous voltages and controls potentially dangerous rotating mechanical parts.
SED2 VFD Operation & Maintenance Manual Repair Only Siemens service departments, repair centers authorized by Siemens Building Technologies, or authorized personnel who are fully acquainted with the SED2 may repair this equipment. Replace defective parts or components using original manufacturer parts. DANGER: Always disconnect the power source before opening the SED2.
Chapter 3 – Mechanical Installation Chapter 3 — Mechanical Installation Installation after Extended Storage After an extended period of storage, recharge the capacitors in the SED2. Calculate the storage time from the date of manufacture, and not from the date of delivery. The recharge procedure varies according to the storage period as follows: Period of Storage Required Action Preparation Time 1 year or less Recharging not required.
SED2 VFD Operation & Maintenance Manual Environmental Conditions Temperature: Maximum operating temperature: +104°F (+40°C) * Minimum operating temperature: +14°F (-10°C) * Be aware of the potential increase in temperature inside a control cabinet (derating is required). Humidity: Maximum 95% rh noncondensing Height Above Sea Level: If installing the SED2 at an altitude of higher than 3280 ft (1000 m), derating is required. Overheating/Ventilation: Install the SED2 vertically for optimum ventilation.
Chapter 3 – Mechanical Installation Mounting Dimensions and Mounting for SED2 Drives (IP20) Table 1. Overall Dimensions of SED2 (IP20). Dimensions in Inches (Millimeters). Frame Size Height Width Depth Mounting Specification Tightening Weight Torque lb (kg) lb-in (Nm) A 6.8 (173) 2.9 (73) 5.9 (149) 2 x M4 Bolts, Nuts, and Washers, or Connecting to DIN rail 22 (2.5) 2.9 (1.3) B 8.0 (202) 5.9 (149) 6.8 (172) 4 x M4 Bolts, Nuts, and Washers 22 (2.5) 7.5 (3.4) C 9.6 (245) 7.3 (185) 7.
SED2 VFD Operation & Maintenance Manual Dimensions and Mounting for SED2 Drives (NEMA Type 1) Table 2. Overall Dimensions of SED2 (NEMA Type 1) Drives Assembled with a Protective Shield and a Gland Plate. Dimensions in Inches (Millimeters). Frame Size 8 Height Width Depth Weight lb (kg) A 9.1 (231) 2.9 (73) 5.9 (149) 3.2 (1.5) B 11.8 (300) 5.9 (149) 6.8 (172) 8.3 (3.8) C 13.8 (351) 7.3 (185) 7.7 (195) 13.6 (6.2) D 24.6 (625) 10.8 (275) 9.6 (245) 37.5 (17.1) E 29.7 (754) 10.
Chapter 3 – Mechanical Installation Dimensions and Mounting for SED2 Drives (IP54, NEMA Type 12) Table 3. Overall Dimensions and Mounting Clearances for SED2 (IP54, NEMA Type 12). Dimensions in Inches (Millimeters). Overall Dimensions Mounting Clearance Frame Size Height Width Depth Top Bottom Sides Mounting Specification Tightening Torque lb-in (Nm) B 15.2 (385) 10.6 (270) 10.6 (268) 5.9 (150) 5.9 (150) 3.9 (100) 4 x M6 Bolts, Nuts, 44 and Washers (5) C 23.9 (606) 13.8 (350) 11.2 (284) 5.
SED2 VFD Operation & Maintenance Manual Chapter 4 – Electrical Installation DANGER: 10 • To ensure safe operation of the equipment, authorized persons must install and commission it in full compliance with the warnings, cautions, and notes in this manual. Authorized persons must also follow general and regional installation and safety regulations regarding work on sites with hazardous voltages (EN 50178) and relevant regulations for the correct use of tools and personal protective equipment.
Chapter 4 – Electrical Installation Motor Cable Length Maximum motor cable length is as follows: • 328 ft (100 m) for shielded cables • 164 ft (50 m) for unshielded cables NOTES: 1. For SED2 drives with EMC filters, the maximum cable length is 82 ft (25 m). For cables shorter than 82 ft (25 m), the EMC guideline for filtered devices does not apply. 2. If connecting multiple motors to one SED2, the total length of the individual motor cables must not exceed the maximum motor cable length. 3.
SED2 VFD Operation & Maintenance Manual Operation in Ungrounded Systems IP20: SED2 drives (IP20) can operate in ungrounded systems, and remain in operation when an input phase connects to ground. In the event of an output phase with a ground fault, the SED2 switches off and displays fault code F0001. NOTE: Operation in ungrounded systems is possible only using the SED2 (IP20) without filter. IP54: SED2 drives (IP54) cannot operate in ungrounded systems.
Chapter 4 – Electrical Installation 1 2 VFD0061R1 3 Figure 4. Disconnecting Y Capacitor in SED2 Frame Size B and C. ON 1 20 21 22 24 25 12 13 14 15 16 17 26 27 28 29 30 1 2 3 4 5 6 7 8 9 10 11 2 23 PE Torx driver T20 M4 Screw 5192Z 03en Figure 5. Disconnecting Y Capacitor in SED2 Frame Size D and E. Siemens Building Technologies, Inc.
SED2 VFD Operation & Maintenance Manual T30 Torx screwdriver VFD0063R1 M6 Figure 6. Disconnecting Y Capacitor in SED2 Frame Size F. Power and Motor Connections Warning and Safety Instructions DANGER: 14 • Always isolate the power cables before connecting them to the SED2. • Never switch on the SED2 with the cover open. • Always use insulated tools when working on the power and motor terminals. • Ensure that the terminal cover is replaced properly after connecting the power and motor cables.
Chapter 4 – Electrical Installation WARNING: • Verify that the SED2 and motor are correctly sized for the mains voltage. Ensure that the SED2 is suited for the motor output. • Check that the mains cables are correctly sized for the anticipated use. • Confirm that appropriate circuit breakers or fuses have been installed between the mains supply and the SED2. • Never use high-voltage insulation test equipment on any cables connected to the SED2.
SED2 VFD Operation & Maintenance Manual 1 1 VFD0068R1 2 3 Figure 8. Access to Connection Terminals for SED2 Frame Size B and C. 4 VFD0069R1 5 6 Figure 9. Access to Connection Terminals for SED2 Frame Size D and E. 1 2 4 6 3 VFD0070R1 5 Figure 10. Access to Connection Terminals for SED2 Frame Size F. 16 Siemens Building Technologies, Inc.
Chapter 4 – Electrical Installation Power and Motor Terminal Layout L3 R+ DC B- DC+ DC- L3 L2 L2 DC- DC+ B+ L1 L1 U V DC R+ B- U V W W PE (Ground) VFD0072R1 VFD0071R1 PE (Ground) Figure 11. Power and Motor Terminal Layout for SED2 Frame Size A. L1 L2 L3 DC- DC+ B+ DC R+ B- U V PE (Ground) Figure 12. Power and Motor Terminal Layout for SED2 Frame Size B and C. (Ground) Figure 13. Power and Motor Terminal Layout for SED2 Frame Size D and E.
SED2 VFD Operation & Maintenance Manual Tightening Torque for Connection Terminals Frame size A 9.7 (1.1) Tightening torque lb-in (Nm) B 13.3 (1.5) C 19.9 (2.25) D 88.5 (10) max. E 88.5 (10) max. F 442 (50) Cable Cross-Sections for Power and Motor Cables Table 4. Cable Cross-Sections for input Voltage Range 3 AC 200V through 240V. Output rating kW (hp) Min. crosssection of supply cable AWG (mm2) Max. crosssection of supply cable AWG (mm2) Min. cross-section of motor cable AWG (mm2) Max.
Chapter 4 – Electrical Installation Table 5. Cable Cross-Sections for input Voltage Range 3 AC 380V through 480V. Output rating kW Min. crosssection of supply cable AWG (mm2) Max. crosssection of supply cable AWG (mm2) Min. cross-section of motor cable AWG (mm2) Max. cross-section of motor cable AWG (mm2) 0.37 (.50) 17 (1) 13 (2.5) 17 (1) 13 (2.5) 0.55 (.75) 17 (1) 13 (2.5) 17 (1) 13 (2.5) 0.75 (1.0) 17 (1) 13 (2.5) 17 (1) 13 (2.5) 1.1 (1.5) 17 (1) 13 (2.5) 17 (1) 13 (2.5) 1.5 (2.
SED2 VFD Operation & Maintenance Manual Table 6. Cable Cross-Sections for input Voltage Range 3 AC 500V through 600V. Output rating kW Min. crosssection of supply cable AWG (mm2) Max. crosssection of supply cable AWG (mm2) Min. cross-section of motor cable AWG (mm2) Max. cross-section of motor cable AWG (mm2) 0.75 (1.0) 17 (1) 7 (10) 17 (1) 7 (10) 1.1 (1.5) 17 (1) 7 (10) 17 (1) 7 (10) 1.5 (2.0) 17 (1) 7 (10) 17 (1) 7 (10) 2.2 (3.0) 17 (1) 7 (10) 17 (1) 7 (10) 3 (4.
Chapter 4 – Electrical Installation Star or Delta Motor Connection The required supply voltage and method of connection are indicated on the motor rating plate. In general, larger motors (400/690V) connect in a delta configuration and smaller motors (230/400V) connect in a star configuration (or wye “Y” configuration). See Figure 16. MOTOR TERMINALS VFD0029R2 U1 W2 V1 W1 U2 U1 V2 W2 V1 U2 W1 V2 Wye "Y" Figure 16. Delta and Star (Wye, Y) Motor Connections.
SED2 VFD Operation & Maintenance Manual D C /R + D C /B + 2 0 0 - 2 4 0 V 3 A C 3 8 0 - 4 8 0 V 3 A C 5 0 0 - 6 0 0 V 3 A C U L 1 L 2 V W L 3 P E B - F ilte r 3 P E P E M L 1 L 2 L 3 P E + 1 0 V D C 1 + 2 0 V D C 4 1 2 D / A L G -N i 1 0 0 0 V : 0 2 I: 0 4 - 1 - 1 - 2 - 2 0 V 0 V 0 m A 0 m A A O U T 1 3 A IN 1 2 6 D / A A O U T 2 1 1 L G -N i 1 0 0 0 V : 0 2 I: 0 4 - 1 - 1 - 2 - 2 0 V 0 V 0 m A 0 m A A / D 2 1 0 V 9 Is o la te d 5 0 m A @ (o u tp u t) 1 6 2 3 1 8 ..
Chapter 5 – Commissioning Chapter 5 — Commissioning WARNING: • Only authorized personnel trained in the setup, installation, commissioning, and operation of the SED2 may work on the product and plant. • SED2 drives operate at high voltages. In some components, operation of electrical equipment involves using dangerous voltages.
SED2 VFD Operation & Maintenance Manual DIP Switch Settings Motor Frequency & Units of Measurement Switches In all versions of the SED2, the DIP switches for selecting the motor frequency and North American or European units of measurement are located on the control board under the I/O module. (See Chapter 4, Access to Connection Terminals for I/O module and control board locations.
Chapter 5 – Commissioning ON DIP switches for setting mains frequency 1 2 DIP switches for analog inputs ON 20 21 22 23 24 25 1 2 1 2 3 4 5 6 7 8 9 5192Z13en 12 13 14 15 16 17 26 27 28 29 30 10 11 I/O module SED2 frame size A Figure 19. Location of DIP Switches.
SED2 VFD Operation & Maintenance Manual SED2 Operator Panels The SED2 includes the Basic Operator Panel (BOP) mounted as standard. An Advanced Operator Panel (AOP) is available as an option. Figure 20. Basic Operator Panel. NOTE: Figure 21. Advanced Operator Panel. The BOP or AOP can connect to or disconnect from the SED2 without switching off power.
Chapter 5 – Commissioning • Comments on current parameters, and error messages. • Communicates via RS-232 or RS-485 interfaces. • Loads and stores up to ten parameter sets. • Programmable with a PC without SED2 (PC- AOP kit required). • Diagnostics menu for troubleshooting. • Multi-drop capability to control up to 31 SED2 drives. • Seven-day timer switch with three switching operations per day. • Main menu can be invoked directly by pressing the Fn and P keys simultaneously.
SED2 VFD Operation & Maintenance Manual Operator Panel/Button Function Decrease value Description Press this button to decrease the current display value during parameter setting. In manual mode, this button decreases the speed (internal motor potentiometer). Press this button to do one of the following: Access to parameters • Access the parameters. • Exit a parameter by accepting its value. Press this button to display additional information. See the AOP Operating Instructions for details.
Chapter 5 – Commissioning Default Commissioning Settings Default settings for operation with the BOP are as follows: Parameter P0100 Description For USA or Europe power setting Default Value for North America (Europe) 0 = 50 Hz, kW (Europe), factory default 1 = 60 Hz, hp (North America) 2 = 60 Hz, kW (North America) The setting of Motor Frequency & Units of Measurement DIP switch 2 overwrites P0100 settings 0 and 1. See the DIP Switch Settings section for details. NOTES: 1.
SED2 VFD Operation & Maintenance Manual Parameter Description Default Value for North America (Europe) Selection of command source Index [0]: IN000=AUTO, 1st command data set Index [1]: IN001=HAND, 2nd command data set 0=Factory default setting 1=BOP (keypad) 2=Terminal Selection of frequency setpoint Index [0]: IN000=AUTO, 1st command data set Index [1]: IN001=HAND, 2nd command data set Selects the frequency setpoint source as follows: P1082 Max. motor frequency 60 Hz or 50 Hz (default).
Chapter 5 – Commissioning It is important to use parameter P0010 to commission the SED2, and P0003 to select the number of accessible parameters. Parameter P0010 allows you to select a group of parameters that can be used for quick commissioning. These include parameters for the motor data (Figure 22), and for the motor ramp-up and ramp-down settings. At the end of the quick commissioning procedure, select P3900.
SED2 VFD Operation & Maintenance Manual Quick Commissioning Procedure P0010 Start Quick Commissioning 0 = Ready to Run 1 = Quick Commissioning 30 = Factory Setting NOTE: P0010 must always be set back to 0 before operating the motor. However, if P3900 = 1 is set after commissioning, this is done automatically. User Setting P0100 Operation for Europe/ N.
Chapter 5 – Commissioning Setting Parameters with the BOP or AOP The following table describes the procedure for modifying parameter P1082, Maximum Motor Frequency. Use this table as a guide for setting all other parameters with the BOP. NOTE: You can change motor data parameters only if P0010=1. To start the motor, reset P0010=0. Modify P0004, parameter filter function: Step Action 1 Press 2 Repeatedly press 3 Press to access the parameter values level.
SED2 VFD Operation & Maintenance Manual Step Action Resulting display 6 Press to confirm and save the value. 7 Press to return to P0010. 8 Press to access the parameter values level. 9 to restore the value of Commissioning Parameter Filter Press P0010 to 0 (ready). Hz 10 to confirm and save the value, and to exit from the Press parameter values level. 11 Press 12 to revert to the standard motor display (as defined by Press the customer).
Chapter 5 – Commissioning Resetting SED2 Parameters to Factory Defaults 1. Set Parameter Commissioning Parameter Filter P0010=30 (factory setting). 2. Set Parameter Factory Reset parameter P0970=1 (parameter reset). 3. Press to restore the factory settings of the SED2. NOTES: 1. The reset process takes approximately 10 seconds. 2. The parameter list in Appendix A of this manual provides factory default settings. SED2 Operation with the BOP Prerequisites and Notes 1.
SED2 VFD Operation & Maintenance Manual 4. Use Reverse Output Phase Sequence parameter P1820 to change the direction of rotation. NOTE: An appropriately configured digital input can also change the direction of rotation. 5. Press to stop the motor. 5 or 10 Hz Test The 10 Hz test helps check the SED2. It verifies the direction of rotation and the basic functions of the SED2. This test also detects any faults related to power installation. Testing with the BOP 1. Restore the factory settings in the SED2.
Chapter 6 – Programming Chapter 6 — Programming Using the Parameters • Modify SED2 parameters using the BOP, the AOP, or the serial interface. Use the BOP or AOP to enter and modify parameters that define the required characteristics of the SED2, such as motor data, ramp times, and maximum and minimum frequency. • Read-only parameters are identified by the letter “r”, programmable parameters are identified by the letter “P”.
SED2 VFD Operation & Maintenance Manual NOTE: Some parameters are intended for commissioning only and can be viewed as a function of this filter. In order to set these parameters, P0010 must be set to 1 (quick commissioning). SED2 Parameter Indices Certain parameters have indices. The indices provide subsets of a particular parameter function. The indexes group together closely related parameter type information.
Chapter 6 – Programming P0004=22 PI Controller ss Level , Acce Ex pe 3=3 00 rt 0 P cess Level , Ac Ex =2 te 3 0 ss Lev e c el Ac P0003= 1, ard and St P0004=20 Communication P0004=3 Motor Data ed nd P0 0 P0004=21 Alarms, Warnings, and Monitoring P0004=2 Inverter Unit P0004=7 Commands and Digital IO P0004=13 Motor Control P0004=8 Analog IO P0004=12 Drive Features P0004=8, P0003=2 Parameters in Access Levels 1 and 2 associated with Analog IO are Available P0004=10 Setpoint Channel and Ramp Gener
SED2 VFD Operation & Maintenance Manual Drive Parameters P0003 User acces level P0010 Commissioning parameter filter r0026 VFD DC-link voltage r0039 - P0040 Energy consumption meter P0100 US / Europe r0206 - r0209 Performance data P1000 - P1028 Frequency setpoint P1080 - P1110 Frequency adjustment Motor Parameters r0021 - r0035 Motor performance data P0304 - P0313 Standard data P0340 Calculation of motor parameters P0601 - P0640 Motor protection P1910 Motor data identification P2000 Reference frequency 2
Chapter 6 – Programming SED2 Basic Functions Digital Inputs Stand-alone operation of the SED2 requires external switch-on and switch-off arrangements. The SED2 supports six-digital inputs, DIN1 through DIN6 (Figure 25), and can be extended to eight-digital inputs (DIN7 and DIN8) by using two analog inputs (AIN1 and AIN2). You can program the function of the digital inputs as required.
5192Z17en SED2 VFD Operation & Maintenance Manual 5 DIN1 DIN1 Function P0701 DIN2 7 DIN3 8 DIN4 16 DC- isolated 6 DIN2 Function P0702 DIN3 Function P0703 DIN5 17 DIN4 r0722 Status of Digital Inputs Function DIN6 9 PNP P0704 Isolated +24 V (Output) or 28 NPN Isolated 0 V (Output) DIN5 P0725 0 = active low 1 = active high Function P0705 DIN6 Function P0706 Figure 25. SED2 Digital Inputs 1 through 6.
Chapter 6 – Programming 1 2 2 3 DIN8 4 11 12 5192Z15 DIN7 1 Figure 26. Connection of Analog Inputs 1 and 2 as Digital Inputs 7 and 8. Index: Example for P0707, applies also to parameter P0708. P0707[0]: IN000 (AUTO)=1st command data set (CDS). P0707[1]: IN001 (HAND)=2nd command data set (CDS).
5192Z29 SED2 VFD Operation & Maintenance Manual DIN1 = 0 DIN2 = 1 DIN3 = 1 DIN4 = 0 DIN5 = 1 DIN6 = 1 AIN1 = 0 AIN2 = 1 Figure 28. Example of the Display while Testing Input Signals using Parameter r0722. Digital Outputs Parameter Settings for DO1 and DO2 P0731 to P0732, Digital outputs 1 and 2 The available settings for each digital output is as follows: 52.0 52.1 52.2 52.3 52.4 52.5 52.6 52.7 52.8 52.9 52.A 52.B 52.C 52.D 52.E 52.F 53.0 53.1 53.2 53.3 53.4 53.5 53.6 53.7 53.8 53.A 53.
Chapter 6 – Programming Factory settings: P0731 52.3 Drive fault active P0732 52.7 Drive running Index: Example for P0731, applies also to parameter P0732. P0731[0]: IN000 (AUTO)=1st command data set (CDS). P0731[1]: IN001 (HAND)=2nd command data set (CDS).
SED2 VFD Operation & Maintenance Manual VFD 24V dc POWERED 0-20 mA DEVICE (Power consumption cannot exceed 100 mA) 2 3 mA 4 Power 9 28 1 5192Z19 SPEED POTENTIOMETER +10 V 2 0V 3 4.7kΩ Minimum AIN1+ A/D 4 AIN1- 10 AIN2+ 11 A/D AIN2- EXTERNAL 0-10V - 2 + 3 EXTERNAL 0-20 mA 2 3 4 Figure 29. SED2 Analog Inputs 1 and 2. Parameter Settings for AIN1 and AIN2 (Commissioning) P0756, Type of analog input P0756 defines the type of analog input and enables analog input monitoring.
Chapter 6 – Programming Index: P0756[0]: IN000=Analog input 1. P0756[1]: IN001=Analog input 2. Note on dependency: This function is disabled if the analog scaling block is programmed for negative output setpoints (see P0757 to P0760). Note on the monitoring function: If monitoring is enabled and the deadband is defined (P0761), a fault message appears (F0080) as soon as the analog input voltage drops below 50% of the deadband voltage.
SED2 VFD Operation & Maintenance Manual % ymax y2 (P0760) x1 (P0757) -10 -20 y1 (P0758) x2 10 (P0759) 20 V mA ymin Index: Example for P0757, applies also to parameters P0758 through P0760. P0757[0]: IN000=Analog input 1. P0757[1]: IN001=Analog input 2. P0761, Width of deadband (V/mA) for analog inputs P0761 defines the deadband for the analog inputs. Setting range: 0 to 10V, or 0 to 20 mA Factory setting: 0 NOTE: P0761[x] = 0: No enabled dead zone.
Chapter 6 – Programming Index: P0761[0]: IN000=Analog input 1. P0761[1]: IN001=Analog input 2. Analog Outputs SED2 converts status variables such as output frequency, motor voltage, or present motor current via D/A converters (DAC) within a scaleable range. The analog outputs then display their values NOTE: For accurate and consistent performance of SED2 analog outputs, if you are not connecting a NI 1000 sensor then terminals 10 and 4 (NI 1000) must connect to terminal 2 (0V).
SED2 VFD Operation & Maintenance Manual 21 24 25 26 27 Present output frequency (scaled to P2000, Reference Frequency), (factory setting). Present SED2 output frequency (scaled to P2000, Reference Frequency). Present output voltage (scaled to P2001, Reference Voltage). Present link voltage (scaled to P2001, Reference Voltage). Present output current (scaled to P2002, Reference Current). Index: P0771[0]: IN000=Analog output 1. P0771[1]: IN001=Analog output 2.
Chapter 6 – Programming P0777 to P0780, Define output characteristic P0777 to P0780 defines the output characteristic in %. The analog output scaling parameters (P0777 to P0781) set the output characteristics and they are configured according to the following curve. Points P1 (x1, y1) and P2 (x2, y2) are freely selectable. P0777: P0778: P0779: P0780: Defines x1 of the output characteristics (factory setting = 0.0). Defines y1 of the output characteristics (factory setting = 0).
SED2 VFD Operation & Maintenance Manual Index: P0781[0]: IN000=Analog output 1. P0781[1]: IN001=Analog output 2. % ymax y2 -10 -20 x1 { { x2 P761 10 20 V mA y1 ymin Frequency Setpoint (P1000) Default setting: Analog input terminal 3/2 (AIN+/AIN–, 0 to 10V corresponds to 0 to 50/60 Hz). Index: P1000[0]: IN000 (AUTO)=1st command data set (CDS). P1000[1]: IN001 (HAND)=2nd command data set (CDS). Additional settings: See P1000 (in the Appendix A: Parameter Reference List section of this document).
Chapter 6 – Programming Index: P0700[0]: IN000 (AUTO)=1st command data set (CDS). P0700[1]: IN001 (HAND)=2nd command data set (CDS). Start Motor Default setting: Terminal 5 (DIN 1, high). Additional settings: See Selection of Command Source parameter P0700 and Function of Digital Inputs 1 to 8 parameters P0701 through P0708. NOTE: The ramp-up and ramp-down smoothing times influence the motor's start and stop behavior.
SED2 VFD Operation & Maintenance Manual NOTES: 1. The ON and the consecutive OFF1 command must have the same source. 2. If the ON/OFF1 command is set for more than one digital input, only the last set digital input is valid; for example, DIN3 is enabled. OFF2 This command causes a free coasting of the motor to standstill (impulses for the power section of the SED2 are disabled). NOTE: The OFF2 command may have one or several sources. By default, the OFF2 command source is set to BOP/AOP.
Chapter 6 – Programming V/f control with FCC for textile applications, P1300=6 A combination of P1300 = 1 and P1300 = 5. Communications The SED2 includes an integral RS-485 serial interface. The optional door mounting kit for the BOP/AOP includes an integral RS-232 interface. USS, P1, and N2 protocols are implemented as part of the series. See Chapter 9 in this manual for more details.
SED2 VFD Operation & Maintenance Manual Parameter Settings for the PID Controller (Commissioning) NOTE: The setpoint and the actual signal value display as a percentage (%). Make sure that the two signals match each other. FIXED SETPOINTS 1-15: EXTERNAL SETPOINT: P2201 – P2215 Enter fixed setpoint. The setpoint is active if switching command ON is sent to Digital Input 1 (DIN1). Analog input See Analog Inputs section for the parameter settings.
Chapter 6 – Programming Belt Failure Detection without Sensor (P2181) SED2 Fan Motor 5192Z22en Figure 32. Belt Failure Detection without Sensor (P2181). This function allows for monitoring power transmission components such as drive belts. The function can also detect motor overload, such as in the case of a jam.
SED2 VFD Operation & Maintenance Manual Parameter Settings for Belt Failure Detection without Sensor (Commissioning) P2182 to P2184, Frequency limit value The three frequency limit values F1, F2, and F3 determine a reasonable division across the required torque area. Set the values desired in the manual mode using and write down the corresponding torque values via parameter r0031. and and read Factory setting: 5, 30, 50 Hz.
Chapter 6 – Programming Belt Failure Detection with Sensor (P0400) Ventilator SED2 Motor Sensor 5192Z23de Figure 34. Belt Failure Detection with Sensor (P0400). A simple sensor (inductive sensor) mounted to the drive unit (such as for a fan) supplies one pulse for each rotation. The pulse train generated this way, which can vary from 1 to 20,000 pulses per minute, is sent to SED2 digital input DIN5. The frequency resulting from the pulse train is compared to the present output frequency of the SED2.
SED2 VFD Operation & Maintenance Manual P2181, Belt failure detection mode Set the desired reaction of drive belt failure detection via parameter P2181. Possible settings: 0 Belt failure detection disabled (factory setting). 1 Warn low torque/speed. 2 Warn high torque/speed. 3 Warn high/low torque/speed. 4 Trip low torque/speed. 5 Trip high torque/speed. 6 Trip high/low torque/speed. Suggested setting: 1 Warn low torque/speed.
Chapter 6 – Programming Mains voltage Variable speed drive Pressure sensor to PID input of variable speed drive M1 M2 5192Z24en MV Motor starter MV: Motor, speed-controlled by SED2. M1: Motor, controlled by digital output relay 1 DOUT1. M2: Motor, controlled by digital output relay 2 DOUT2. Figure 35. Staging Pumps.
SED2 VFD Operation & Maintenance Manual Total Power t Motor MV, controlled by SED2 Power 100% t Motor M1, switched by relay 1 Power 100% t Motor M2, switched by relay 2 Power 100% t Figure 37. Diagram From Motor Staging. 62 Siemens Building Technologies, Inc.
Chapter 6 – Programming Parameter Settings for Motor Staging (Commissioning) In general, the factory settings can be used. P2371, Selection of external motor configuration Max. 2 pumps can be added.
SED2 VFD Operation & Maintenance Manual P2375, Delay on motor destaging Time that error (P2374) must exceed hysteresis before staging occurs. Setting range: 0 to 650 seconds Factory setting: 30 seconds P2376, Delay override on motor staging/destaging The value of P2376 is set as a percentage of the PID setpoint. If the PID error (P2273) exceeds this value, a motor is switched on or off, regardless of the delay timers (P2374 and P2375).
Chapter 6 – Programming 5192D04en f Max. freq. VSD freq. Staging freq. Min. freq. f PID Off Relay On t PID On Max. freq. VSD freq. Staging freq. Min. freq. t PID Off Relay Off PID On P0731, Function of Digital output 1, relay 1 (DOUT1) Parameter r2379 (relay 1 to motor 1). Factory setting: 52.3 = SED2 fault enabled P0732 Digital output 2, relay 2 (DOUT2) Parameter r2379 (relay 2 to motor 2) Factory setting: 52.
SED2 VFD Operation & Maintenance Manual The temperature sensor can connect as follows to the analog inputs: Ni 1000 on AIN 1: Connection terminals: 2/4 SED2 T Ni1000 5192Z26 Figure 38. Temperature Control with Ni 1000 Sensor. Ni 1000 on AIN 2: Connection terminals: 2/11 When connecting a Ni 1000 sensor, no other input signal can be processed on the same input, even if terminals 3/10 for an analog signal of 0 to 10V are free.
Chapter 6 – Programming Example: Ni 1000 on AIN1: P0757[0] = –50°C P0758[0] = –50% P0759[0] = 150°C P0760[0] = 150% Factory settings: P0757 = 0 P0758 = 0.0 P0759 = 10 P0760 = 100 Other Typical HVAC Applications The following table lists commonly defined settings for desired operations: Parameter Application P0718 Selects if Hand or Auto occurs after a power-on. P0748 Inverts operation of digital outputs. P1020 – P1028 Fix frequency. See also the Digital Inputs section.
SED2 VFD Operation & Maintenance Manual Chapter 7 — Troubleshooting Troubleshooting Using the Operator Panel If the motor does not start with the ON command: • Check if Commissioning Parameter Filter P0010=0 (factory setting). • Check if there is a valid ON signal. • Check if Selection of Command Source parameter P0700=2 (for digital input control) or P0700=1 (for BOP control).
Chapter 7 – Troubleshooting Fault Codes Error F0001, Overcurrent F0002, Overvoltage Cause • Motor power (P0307) is greater than SED2 power (P0206). • Motor lead short circuit. • Earth faults. • DC link voltage (r0026) exceeds trip level. • Overvoltage can be caused either by too high main supply voltage or if motor is in regenerative mode. • Regenerative mode can be caused by fast ramp downs or if the motor is driven from an active load.
SED2 VFD Operation & Maintenance Manual Error F0004, SED2 Overtemperature Cause • Ventilation is inadequate. • The fan is inoperative. • The ambient temperature is too high. Diagnosis/Remedy Reaction Off2 Check the following: • The fan must turn when the SED2 is running. • The pulse frequency must be set to a lower value. • The ambient temperature could be higher than specified for the SED2. • The SED2 is overloaded. • The duty cycle is outside the tolerance.
Chapter 7 – Troubleshooting Error F0022, Power stack fault Cause Diagnosis/Remedy Reaction Off2 The fault is caused by the following events: (1) dc link overcurrent =short circuit of IGBT. (2) short circuit of dc link chopper (3) earth fault. Frame sizes A to C = (1),(2),(3). Frame sizes D to E = (1),(2). Frame size F = (2). Since all these faults are assigned to one signal on the power stack, it is not possible to establish which one actually occurred.
SED2 VFD Operation & Maintenance Manual Error F0041, Motor data identification failure Cause Diagnosis/Remedy • Motor data identification failed 0: SED2. • Alarm value = 0: Load is missing 1-40: Check if the motor data in P0304 to P0311 are correct. • Alarm value = 1: Current limit value reached during identification. Check the type of motor wiring required (star, delta). • Alarm value = 2: Identified stator resistance less than 0.1% or more than 100%.
Chapter 7 – Troubleshooting Error Cause Diagnosis/Remedy Reaction F0051, Parameter EEPROM fault • Read or write failure while saving non-volatile parameter Reset SED2 to factory setting and reparameterize Off2 F0052, Power stack fault • Read failure for power stack information or invalid data. Exchange SED2. Off2 F0053, I/O EEPROM fault • Read failure for I/O EEPROM information or invalid data. Check the data. Off2 F0054, Wrong I/O print • I/O print is not connected. Check data flow.
SED2 VFD Operation & Maintenance Manual Error F0450, BIST tests failure Cause Alarm value: 1. Some power section tests have failed. Diagnosis/Remedy The drive may run, but some functions do not work properly. Reaction Off2 Replace the drive. 2. Some control board tests have failed. 4. Some functional tests have failed. 8. Some I/O module tests have failed. 16.Internal RAM failed on powerup check.
Chapter 7 – Troubleshooting Reading Faults • OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK, 1=Fault). • LAST FAULT (r0947(0)) shows the code for the most recent fault. Resetting Faults • Press • OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK, 1=Fault). It can be acknowledged with FAULT ACK (r0054, bit 7). Setting FAULT ACK (r0054, bit 7) resets the fault (1=Reset Fault). NOTE: to reset a fault condition.
SED2 VFD Operation & Maintenance Manual Error A0503, Undervoltage limit A0504, SED2 overtemperature Cause • Main power failed. Reaction Check the main supply voltage. -- Check the following: -- The main power and consequently the DC link voltage (r0026) are below the defined threshold value. • The warning level of the SED2 heat sink temperature (r0037) is exceeded. This results in a reduced pulse frequency and/or a reduced output frequency (dependent on parameter setting in (P0610).
Chapter 7 – Troubleshooting Error A0910, Vdc (max.) controller disabled A0911, Vdc (max.) controller enabled A0912, Vdc (min) controller enabled Cause • Vdc maximum controller disabled as not able to keep the DC link voltage (r0026) within threshold limits. • Permanent supply overvoltage. • Occurs if the motor is driven by a load forcing the motor to go into energy recovery operation. • Occurs during rampdown of very high duty cycles. • Vdc maximum controller is enabled.
SED2 VFD Operation & Maintenance Manual Error Cause • DAC parameters must not be set to identical values, as illogical values would result. • Index 0: Parameter settings for output identical. • Index 1: Parameter settings for input identical. • Index 2: Parameter settings for output do not correspond to DAC type. • No load is applied to the SED2. • Some functions may not work as under normal load conditions.
Chapter8 – Technical Data Specification Options Chapter 8 — Technical Data Specification Options General Specifications Specification Operating temperature ranges Description IP20 and NEMA Type 1: 14°F to 104°F (–10°C to 40°C) IP54 and NEMA Type 12: 14°F to 104°F (–10°C to 40°C) Storage temperature –40°F to 158°F (–40°C to 70°C) Humidity 95% relative humidity — non-condensing. Altitude Up to 3280 ft (1000 m) above sea level without performance decrease.
SED2 VFD Operation & Maintenance Manual Specification Digital inputs Description 6 (potential-free) inputs (extendable to 8) Freely programmable and possible changeover (sink, source) Terminals used: 5, 6, 7, 8, 16, 17 Min. input current: 6 mA (actual: 8 mA) at ≥15V Logical 0 = <3V, logical 1 = >13V Max. input voltage: 33V Analog outputs Number: 2 Can be changed over for 0 to 10V or 0/4 to 20 mA, (programmable scaling/parameter). Factory setting: 0 to 10V.
Chapter8 – Technical Data Specification Options Dimensions and Weights Dimensions and weight (frame sizes A to C, IP20) Frame size WxHxD Inches (mm) Weight lb (kg) A 2.9 (73) x 6.8 (173) x 5.9 (149) 2.9 (1.3) B 5.9 (149) x 8.0 (202) x 6.8 (172) 7.5 (3.4) C 7.3 (185) x 9.6 (245) x 7.7 (195) 12 (5.5) D 10.8 (275) x 20.5 (520) x 9.6 (245) 35 (16) E 10.8 (275) x 25.6 (650) x 9.6 (245) 44 (20) F 13.8 (350) x 33.5 (850) x 12.
SED2 VFD Operation & Maintenance Manual 200V to 240V, ± 10%, 3 phase Output power (variable torque) IP code Max. input current 3 phase Max. output current Frame size Part Number kW hp IP A A 3 4 20 15.6 13.6 C SED2-3/22X 4 5 20 20.1 17.5 C SED2-4/22X 5.5 7.5 20 26.3 22 C SED2-5.5/22X 7.5 10 20 36.4 28 C SED2-7.5/22X 11 15 20 46 42 D SED2-11/22X 15 20 20 60 54 D SED2-15/22X 18.5 25 20 75 68 D SED2-18.
Chapter8 – Technical Data Specification Options 380V to 480V, ± 10%, 3 phase Output power (variable torque) IP code Max. input current 3 phase Max. output current Frame size Part Number kW hp IP A A 37 50 20 83 75 E SED2-37/32X 45 60 20 99 90 E SED2-45/32X 55 75 20 121 110 F SED2-55/32X 75 100 20 160 145 F SED2-75/32X 90 125 20 196 178 F SED2-90/32X 1.1 1.5 54 4.2 3 B SED2-1.1/35X 1.5 2 54 5.8 4 B SED2-1.5/35X 2.2 3 54 7.5 5.9 B SED2-2.
SED2 VFD Operation & Maintenance Manual 500V to 600V, ± 10%, 3 phase Output power (variable torque) IP code Max. input current 3 phase Max. output current Frame size Part Number kW hp IP A A 2.2 3 20 4.4 3.9 C SED2-2.2/42X 3 4 20 6.3 5.4 C SED2-3/42X 4 5 20 6.9 6.1 C SED2-4/42X 5.5 7.5 20 9.4 9 C SED2-5.5/42X 7.5 10 20 12.6 11 C SED2-7.5/42X 11 15 20 18.1 17 C SED2-11/42X 15 20 20 24.9 22 C SED2-15/42X 18.5 25 20 30 27 D SED2-18.
Chapter8 – Technical Data Specification Options 500V to 600V, ± 10%, 3 phase Output power (variable torque) IP code Max. input current 3 phase Max. output current Frame size Part Number kW hp IP A A 75 100 54 109 99 F SED2-75/45X 90 125 54 138 125 F SED2-90/45X Options Depending on the application, various options are available for the SED2.
SED2 VFD Operation & Maintenance Manual PC – AOP Kit (SED2-PC-AOP-KIT): Allows for programming the AOP independent of the SED2 from a PC, or to download or upload complete sets of parameters. The kit consists of a 3 m long cable and a power supply unit (to supply power to the AOP). The kit does not include the AOP. 86 Siemens Building Technologies, Inc.
Chapter 9 – SED2 Communications Chapter 9 — SED2 Communications Overview The SED2 drives are a family of inverters that are built, sold, and serviced by Siemens Building Technologies, Inc.- Adjustable Frequency Drives Group (SBT-Drives). Siemens Building Technologies has a Protocol 1 (P1) communication driver, FLN connection, and point database that is built into their drives and allows them to coexist on an APOGEE network with other floor level network (FLN) devices.
SED2 VFD Operation & Maintenance Manual RS-232 and RS-485 Serial Interfaces Serial communications use carefully defined hardware and software protocols. The software protocol defines the baud rate, word length, and meaning of the signal, and can be defined by designers for their particular needs. Standards can also be specially developed, but most users adopt an existing standard. Typical standards are RS-232 and RS-485. These standards define voltages, impedance, etc. but not the software protocol.
Chapter 9 – SED2 Communications • Check the drive address. All drives on a bus must have unique addresses, even if they are in local control. The drives will always reply to a valid message, even if serial control is not enabled. I/O, Point Database, and Parameters Hardware Inputs and Outputs For a complete list of SED2 hardware inputs and outputs, see other sections of this manual. The field panel can access selected I/O to the SED2.
SED2 VFD Operation & Maintenance Manual Table 7. Set-up Parameters. Parameter Number/Name Value P0003: User access Level Set to 3 to allow access to required parameters. P2040: CB telegram off time Set to 0 (watchdog disabled) to tell the SED2 to start looking for communication via the setting of P2041. P2041 (index 0): CB parameter Set to 1 for FLN (P1) control. (Set to 2 for FLN (N2) control.) P0918: CB address Set to 99 for (P1) addressing of the device.
Chapter 9 – SED2 Communications Strategies for FLN (P1) Monitoring – Several SED2 parameters are available for monitoring purposes. These include both binary and analog data.
SED2 VFD Operation & Maintenance Manual When using this strategy, the point to unbundle and command for the setpoint is FREQ REF (Point 51). FREQ REF (Point 51) has a slope of 0.006103516, which corresponds to a value of 16384 (4000h)=100%. Unbundle PI FEEDBACK (Point 60) to monitor the control variable (water temperature). These points are provided with units of percent, where 0% and 100% correspond to the range of the sensor that measures the control variable.
Chapter 9 – SED2 Communications Slaving the Drive CAUTION: This strategy is not normally recommended because you are using the network communications to close the loop. Delays due to network traffic can cause control to be degraded or lost, and depending on the setup of the drive, if there is a problem with the network, the drive may cause physical damage to the HVAC system by winding up to its maximum or dropping off to its minimum speed.
SED2 VFD Operation & Maintenance Manual Digital Inputs – Use DIGITAL IN 1 through DIGITAL IN 6 (Points 71 through 76) to monitor the status of the SED2 digital inputs from the field panel. This is useful when the SED2 is programmed for control of drive functions (start/stop, fault reset, off, etc.) via the SED2 control terminal strip. Over the P1 serial link, you can monitor a control sequence that requires receipt of a contact closure on the SED2 terminal strip.
Chapter 9 – SED2 Communications Table 8. Point Database for Application 2722. Factory Default (SI Units) Engr. Units (SI Units) RATED PWR 0 HP/KW .01 0 - - LAI OUTPUT VOLTS 0 V 1 0 - - 20 LAO OVRD TIME 1 HRS 1 0 - - {21} LDI FWD.REV FWD - 1 0 REV FWD {22} LDO CMD FWD.REV FWD - 1 0 REV FWD {23} LDI STOP.RUN STOP - 1 0 RUN STOP {24} LDO CMD STP.
SED2 VFD Operation & Maintenance Manual Table 8. Point Database for Application 2722. Factory Default (SI Units) Engr. Units (SI Units) Slope (SI Units) Point Number Point Type 53 LAO FREQ MAX 2450 HZ 0.02 1 - - {55} LAO PID SETP REF 8602 PCT 0.0244 -200 - - {56} LAI PID SETP OUT 0 PCT 0.0122 -100 - - 57 LAO PID UP LMT 12288 PCT 0.0244 -200 - - 58 LAO PID LO LMT 8192 PCT 0.0244 -200 - - {59} LAI PID OUTPUT 0 PCT 0.
Chapter 9 – SED2 Communications Table 8. Point Database for Application 2722. Point Number Point Type Descriptor Factory Default (SI Units) Engr. Units (SI Units) 0 - Slope (SI Units) Intercept (SI Units) Off Text On Text WARNING {99} LAO ERROR STATUS 1 0 - - 1. Points not listed are not used in this application. 2. A single value in a column means that the value is the same in English units and in SI units. 3.
SED2 VFD Operation & Maintenance Manual Table 9. Point Cross Reference to the SED2 Drive. Point Number Descriptor Parameter 34 SEL HND.
Chapter 9 – SED2 Communications Table 9. Point Cross Reference to the SED2 Drive. Point Number Descriptor Parameter 96 WARNING r0052 bit 7 97 LAST WARNING r2110 (0) N2 Bus Connections The connections for the N2 network (Table 10) are located on the terminal block. Table 10. N2 Bus Connections. Terminal Pin No. Terminal Name N2 Bus Connection 29 P+ N2+ 30 N- N2- 28 Iso 0V Ref N2 Implementation Notes 1. Overriding of AI and BI points is not supported.
SED2 VFD Operation & Maintenance Manual Table 11. N2 Point Map. Point Number Name Default Value Units Notes On Text Off Text SED2 Ref. Or Range AI7 OUTPUT VOLTS 0 V No Override 0 to 32767 r0025 AI8 ANALOG IN 1 0 PCT No Override -300.0 to 300.0 r0754/0 AI9 ANALOG IN 2 0 PCT No Override -300.0 to 300.0 r0754/1 AI10 PI FEEDBACK 0 PCT No Override -100.0 to 100.0 r2266 AI11 ANALOG OUT 1 0 PCT No Override -100.0 to 100.
Chapter 9 – SED2 Communications Table 11. N2 Point Map. Point Number Name Default Value Units Notes On Text Off Text SED2 Ref. Or Range BO6 DIGITAL OUT 2 0 -- ON OFF P0733 BO7 CMD FWD REV 0 -- REV FWD STW:11 BO8 ENABLE PID 0 -- ON OFF P2200 ADF1 ACCEL TIME 1 10.00 SEC 0.00 to 650.00 P1120 ADF2 DECEL TIME 1 10.00 SEC 0.00 to 650.00 P1121 ADF3 CURRENT LMT 150.0 PCT 10.0 to 400.0 P0640 ADF4 P GAIN 3.000 -- 0.000 to 65.000 P2280 ADF5 I GAIN 0 SEC 0.
SED2 VFD Operation & Maintenance Manual Appendix A: Parameter Reference List P0004 Parameter Filters/Categories Quick Commissioning (P0010=1) Parameter Description Unit User Setting Min Default Access Level Max r0000 Drive display (defined in P0005) - - - - X P0003 User access level to parameters - 0 1 4 1 P0010 Commissioning parameter filter - 0 0 30 1 P0100 Europe/North America power settings [kW or hp] - 0 0 2 1 P0304 Rated motor voltage V 10 230 2000 1 P0305
Appendix A: Parameter Reference List Parameter Description Unit User Setting Min Default Access Level Max P1082 Max. Frequency Hz 0.00 50.00 650.00 1 P1120 Ramp-up time s 0.00 10.00 650.00 1 P1121 Ramp-down time s 0.00 10.00 650.
SED2 VFD Operation & Maintenance Manual Parameter Description Unit User Setting Min Default Access Level Max r0209 Maximum inverter current A - - - 2 P1800 Pulse frequency kHz 2 4 16 2 r1801 CO: Act.
Appendix A: Parameter Reference List Parameter Description Unit User Setting Default Min Access Level Max P0340 Calculation of motor parameters - 0 0 4 2 P0350 Stator resistance (lineto-line) ohm 0.00001 4.0 2000.0 2 r0395 CO: Total stator resistance [%] % - - - 3 P0601 Motor temp. sensor - 0 0 2 3 P0610 Motor I2t temperature reaction - 0 2 2 3 P0640 Motor overload factor [%] % 10.0 150.0 400.
SED2 VFD Operation & Maintenance Manual Parameter Description Unit User Setting Min Default Access Level Max r0052 CO/BO: Act. status word 1 - - - - 2 r0053 CO/BO: Act. status word 2 - - - - 2 r0054 CO/BO: Act. control word 1 - - - - 3 r0055 CO/BO: Add. act.
Appendix A: Parameter Reference List Parameter Description P0732 BI: Function of digital output 2 r0747 Unit Min Default Access Level Max 0.0 52.7 4000.0 2 CO/BO: State of digital outputs - - - 3 P0748 Invert digital outputs - 0 0 7 3 P0809 Copy Command Data Set - 0 0 2 2 P0810 BI: CDS bit 0 (Local/Remote) - 0:0 718:0 4095:0 2 P1020 BI: Fixed freq. selection Bit 0 0:0 0:0 4000:0 3 P1021 BI: Fixed freq.
SED2 VFD Operation & Maintenance Manual Parameter Description Unit User Setting Min Default Access Level Max P2221 BI: Fixed PID setp. select Bit 1 - 0:0 0:0 4000:0 3 P2222 BI: Fixed PID setp. select Bit 2 - 0:0 0:0 4000:0 3 P2223 BI: Fixed PID setp. select Bit 3 - 0:0 0:0 4000:0 3 P2226 BI: Fixed PID setp. select Bit 4 - 0:0 722:4 4000:0 3 P2228 BI: Fixed PID setp.
Appendix A: Parameter Reference List Parameter Description Unit User Setting Min Default Access Level Max P0757 Value x1 of ADC scaling [V/mA] - 50.0 0 150.0 2 P0758 Value y1 of ADC scaling % -99999.9 0.0 99999.9 2 P0759 Value x2 of ADC scaling [V/mA] - 50.0 150.0 150.0 2 P0760 Value y2 of ADC scaling % -99999.9 100.0 99999.9 2 P0761 Width of ADC deadband [V/mA] - 0 0 150.
SED2 VFD Operation & Maintenance Manual Parameter Description Unit User Setting Min Default Access Level Max P0003 User access level to parameters - 0 1 4 1 P0004 Parameter filter - 0 0 22 1 P0010 Commissioning parameter filter - 0 0 30 1 P1000 Selection of frequency setpoint - 0 2 77 1 P1001 Fixed frequency 1 Hz -650.0 0.00 650.00 2 P1002 Fixed frequency 2 Hz -650.0 0.00 650.00 2 P1003 Fixed frequency 3 Hz -650.0 0.00 650.
Appendix A: Parameter Reference List Parameter Description Unit User Setting Min Default Access Level Max P1019 Fixed frequency mode- Bit 3 1 1 3 3 r1024 CO: Act. fixed frequency Hz - - - 3 P1025 Fixed frequency mode – Bit 4 - 1 1 3 3 P1027 Fixed frequency mode – Bit 5 - 1 1 3 3 P1031 Setpoint memory of the MOP 0 0 1 2 P1032 Inhibit reverse direction of MOP 0 1 1 2 P1040 Setpoint of the MOP -650.00 5.00 650.00 2 r1050 CO: Act. Output freq.
SED2 VFD Operation & Maintenance Manual Drive Features (P0004=12) Parameter Description Unit User Setting Min Default Access Level Max r0000 Drive display (defined in P0005) - - - - X P0003 User access level to parameters - 0 1 4 1 P0004 Parameter filter - 0 0 22 1 P0005 Display selection for r0000 - 2 21 2294 2 P0006 Display mode for r0000 - 0 2 4 3 P0010 Commissioning parameter filter - 0 0 30 1 P0011 Lock for user-defined parameter - 0 0 65535 3 P0
Appendix A: Parameter Reference List Parameter Description Unit User Setting Min Default Access Level Max P1240 Configuration of Vdc controller - 0 1 3 3 P1260 Source of changeover - 0 0 7 2 P1261 Contactor control word - - - - 2 P1262 Bypass dead time - 0 1.000 20.000 2 P1263 De-bypass time - 0 1.000 300.0 2 P1264 Bypass time - 0 1.0 300.0 2 P1265 Mains frequency - 12.00 50.0 650.0 2 P1266 Bypass command - 0:0 0:0 4000.
SED2 VFD Operation & Maintenance Manual Parameter Unit Description User Setting Min Default Access Level Max r0031 Actual torque - - - - 3 r0032 Actual power - - - - 3 r0056 CO/BO: Status of motor control - - - 3 r0061 Actual rotor speed - - - 3 r0086 CO: Act. active current A - - - 3 P1300 Control mode - 0 0 23 2 P1310 Continuous boost % 0.0 50.0 250.0 2 P1311 Acceleration boost % 0.0 0.0 250.0 2 P1312 Starting boost % 0.0 0.0 250.
Appendix A: Parameter Reference List Parameter Description Unit User Setting Min Default Access Level Max P0927 Parameter changeable via 0 15 15 2 r0967 Control word 1 - - - - 3 r0968 Statue word 1 - - - - 3 P0971 Transfer data from RAM to EEPROM - 0 0 1 3 P2000 Reference frequency V 1.00 50.00 650.00 2 P2001 Reference voltage A 10 1000 2000 3 P2002 Reference current - 0.10 0.10 10000.
SED2 VFD Operation & Maintenance Manual Parameter Description Unit User Setting Min Default Access Level Max P0004 Parameter filter - 0 0 22 1 P0010 Commissioning parameter filter - 0 0 30 1 r0947 Last fault code - - - - 2 r0948 Fault time - - - - 3 r0949 Fault value - - - - 3 P0952 Total number of faults - 0 0 0 3 P2100 Alarm number selection - 0 0 65535 3 P2101 Stop reaction value - 0 0 4 3 r2110 Warning number - - - - 2 P2111 Total n
Appendix A: Parameter Reference List Parameter Description Unit User Setting Min Default Access Level Max P2189 Upper torque threshold Nm 3 0.0 99999.0 99999.0 2 P2190 Lower torque threshold Nm 3 0.0 0.0 99999.0 2 P2191 Belt failure speed tolerance Hz 0.00 3.00 20.
SED2 VFD Operation & Maintenance Manual Parameter Description Unit User Setting Min Default Access Level Max P2206 Fixed PID setpoint 6 % -200.00 200.00 2 P2207 Fixed PID setpoint 7 % -200.00 200.00 2 P2208 Fixed PID setpoint 8 % -200.00 200.00 2 P2209 Fixed PID setpoint 9 % -200.00 200.00 2 P2210 Fixed PID setpoint 10 % -200.00 200.00 2 P2211 Fixed PID setpoint 11 % -200.00 200.00 2 P2212 Fixed PID setpoint 12 % -200.00 200.
Appendix A: Parameter Reference List Parameter Description Unit User Setting Min Default Access Level Max r2250 CO: Output setpoint of PID-MOP % - - - 2 P2253 CI: PID setpoint - 0:0 0:0 4000:0 2 P2254 CI: PID trim - 0:0 0:0 4000:0 3 P2261 PID setpt. filter - 0.00 0.00 60.00 3 r2262 CO: Act. PID filtered setpoint % - - - 2 P2264 CI: PID feedback - 0:0 755:0 4000:0 2 P2265 PID feedback filter timeconstant s 0.00 0.00 60.00 2 P2267 Max.
SED2 VFD Operation & Maintenance Manual Parameter Description Unit User Setting Min Default Access Level Max r2294 CO: Act. PID output % - - - 2 P2303 PID output offset - 0.00 0.0 4000.
Appendix A: Parameter Reference List Factory settings (P0010=30) Parameter Description Unit User Setting Min Default Access Level Max P0003 User access level - 0 1 4 1 P0010 Commissioning Parameter filter - 0 0 30 1 P0970 Factory reset - 0 0 1 1 Siemens Building Technologies, Inc.
SED2 VFD Operation & Maintenance Manual Parameter List r0000 Min: Note: r0002 Level X Drive display (defined in P0005) Def: - Pressing the "Fn" button for 2 seconds allows you to view the values of DC link voltage, output current, output frequency, and chosen r0000 setting (defined in P0005).
Appendix A: Parameter Reference List Level 3 P0006 Display mode for r0000 Enum: 0=In Ready state alternate between setpoint and output freq. In run display output freq. 3=In Ready state alternate between r0002 value and r0020 value. In run display r0002 value 1=In Ready state display setpoint. In run display output freq. 4=In all states just display P0005 Min: 0 Def: 2 Max: 4 2=In Ready state alternate between P0005 value and r0020 value. In run display P0005 value.
SED2 VFD Operation & Maintenance Manual Dependency: First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined parameter. Then, set P0003 to 0 to activate the user-defined list. When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
Appendix A: Parameter Reference List r0025 Min: - r0026[2] r0035 Max: - Level 2 Def: - Max: - Level 3 Def: - Max: - Level 3 Def: - Max: - Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe/North America). Level 2 CO: Act. Motor temperature Min: - r0039 Def: - CO: Act. Power Min: - Dependency: Level 2 CO: Act. Torque Min: - r0032 Max: - CO: Act. output current Min: - r0031 Def: - CO: Act. OuDC linktput voltage Min: - r0027 Level 2 CO: Act.
SED2 VFD Operation & Maintenance Manual Level 2 r0052 CO/BO: Act.
Appendix A: Parameter Reference List r0054 Min: Bit Fields: Level 3 CO/BO: Act.
SED2 VFD Operation & Maintenance Manual Level 3 r0056 CO/BO: Status of motor control Bit Fields: Bit00 Init.
Appendix A: Parameter Reference List Stop drive first (that is, disable all pulses) before you change this parameter. P0010=1 (commissioning mode) enables changes to be made. Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (see P0340-calculation of motor parameters). Note: r0200 P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see table above).
SED2 VFD Operation & Maintenance Manual Level 1 P0307 Rated motor power Dependency: If P0100=1 ([kW],frequency default 50 Hz), values will be in [hp]-see diagram P0304 (rating plate). Min: 0.01 Def: 0.75 Max: 2000.00 Changeable only when P0010=1 (quick commissioning). P0308 Min: 0.000 Dependency: Level 2 Rated motor cosPhi Def: 0.000 Max: 1.000 Changeable only when P0010=1 (quick commissioning). Visible only when P0100=0 or 2, (motor power entered in [kW]).
Appendix A: Parameter Reference List P0340 Min: 0 Data: Def: 0 Max: 4 Calculates various motor parameters, including: Motor weight Enum: Level 2 Calculation of motor parameters P0344 (Level 3) Stator resistance P0350 (Level 2) Magnetization time P0346 (Level 3) Reference frequency P2000 (Level 2) Demagnetization time P0347 (Level 3) Reference current P2002 (Level 3). 0=No calculation 3=Calc. V/f and vector control 1=Complete parameterization 4=Calc. only controller setting 2=Calc.
SED2 VFD Operation & Maintenance Manual Setting: 0=No sensor selected 10=Sensor type QBE63 DP01 20=Sensor type 0 to 10 INCH WC 1=Sensor type QBE620 P1 11=Sensor type QBE63 DP02 21=Sensor type 0 to 10 PSI 2=Sensor type QBE620 P10 12=Sensor type QBE63 DP05 22=Sensor type 0 to 15 PSI 3=Sensor type QBE620 P16 13=Sensor type QBE63 DP1 23=Sensor type 0 to 25 PSI 4=Sensor type QBE620 P25 14=Sensor type QBE63 DP4 24=Sensor type 0 to 30 PSI 5=Sensor type QBE620 P40 15=Sensor type 0 to 1 INCH WC 25
Appendix A: Parameter Reference List Dependency: P0610 If no sensor is selected, motor temperature monitoring occurs based on the estimated value of the thermal motor model. Min: 0 Enum: P0640 Level 3 Motor I2t temperature reaction Def: 2 Max: 2 0=No reaction, warning only 1=Warning and Imax reduction (results in reduced output 2=Warning and trip freq.) (F0010) Level 2 Motor overload factor [%] Min: 10.0 Def: 150.0 Max: 400.
SED2 VFD Operation & Maintenance Manual Level 2 P0703[2] Function of digital input 3 Detail: See P0701 (function of digital input1). P0704[2] Function of digital input 4 Detail: See P0701 (function of digital input1). P0705[2] Function of digital input 5 Detail: See P0701 (function of digital input1). P0706[2] Function of digital input 6 Min: 0 Min: 0 Min: 0 Min: 0 Def: 9 Level 2 Def: 15 Def: 15 Max: 99 Level 2 Def: 15 See P0701 (function of digital input1).
Appendix A: Parameter Reference List Bit Fields Bit00 Digital input 1 0 OFF, 1 ON Bit01 Digital input 2 0 OFF, 1 ON Bit02 Digital input 3 0 OFF, 1 ON Bit03 Digital input 4 0 OFF, 1 ON Bit04 Digital input 5 0 OFF, 1 ON Bit05 Digital input 6 0 OFF, 1 ON Bit06 Digital input 7 (via ADC 1) 0 OFF, 1 ON Bit07 Digital input 8 (via ADC 2) 0 OFF, 1 ON Note: Segment is lit when signal is active.
SED2 VFD Operation & Maintenance Manual Level 3 r0747 CO/BO: State of digital outputs Bit Fields: Bit00 Digital output 1 energized 0 NO, 1 YES Bit01 Digital output 2 energized 0 NO, 1 YES Min: - Dependency: Def: - Max: - Bit 0 0=relay de-energized/contacts open 1=relay energized/contacts closed Level 3 P0748 Invert digital outputs Bit Fields: Bit00 Invert digital output 1 0 NO, 1 YES Bit01 Invert digital output 2 0 NO, 1 YES Bit02 Invert digital output 3 0 NO, 1 YES Mi
Appendix A: Parameter Reference List Index: r0755[0] : IN000 Analog input 1 (ADC 1) r0755[1] : IN001 Analog input 2 (ADC 2) Note: This value is used as an input to analog BICO connectors. ASPmax represents the highest analog setpoint (this may be at 10V) ASPmin represents the lowest analog setpoint (this may be at 0V) Details: See parameters P0757 to P0760 (ADC scaling) P0756[2] Type of ADC Min: 0 Data: Level 2 Def: 0 Max: 5 Defines type of analog input and also enables analog input monitoring.
SED2 VFD Operation & Maintenance Manual P0759[2] Level 2 Value x2 of ADC scaling [V/mA] Min: 50.0 Def: 150.0 Index: P0759[0] : IN000 Analog input 1 (ADC 1) P0760[2] Value y2 of ADC scaling Max: 150.0 P0759[1] : IN001 Analog input 2 (ADC 2) Level 2 Min: -99999.9 Def: 100.0 Max: 99999.9 Index: P0760[0] : IN000 Analog input 1 (ADC 1) Dependency: Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.
Appendix A: Parameter Reference List Note: P0777[2] The analog output is designed as a current output with a range of 0 to 20 mA. The two analog output channels must be of the same type, that is, both channels are current outputs with a range of 0 to 20 mA or both channels are defined as voltage outputs with a range of 0 to 10V. Level 2 Value x1 of DAC scaling Min: -99999.0 Def: 0.0 Max: 99999.0 Data: Defines x1 output characteristic in [%].
SED2 VFD Operation & Maintenance Manual P0918 Level 2 CB address Min: 0 Data: Def: 3 Max: 65535 Defines address of CB (communication board) or address of the other option modules. There are two ways to set the bus address: 1. via DIP switches on the PROFIBUS module 2. via a user-entered value Note: Possible PROFIBUS settings: 1 ...
Appendix A: Parameter Reference List Index: r0947[0] : Recent fault trip --, fault 1 r0947[3] : Recent fault trip -1, fault 4 r0947[6] : Recent fault trip -3, fault 7 r0947[1] : Recent fault trip --, fault 2 r0947[4] : Recent fault trip -2, fault 5 r0947[7] : Recent fault trip -3, fault 8 r0947[2] : Recent fault trip -1, fault 3 r0947[5] : Recent fault trip -2, fault 6 Dependency: Index 2 used only if second fault occurs before first fault is acknowledged.
SED2 VFD Operation & Maintenance Manual Level 3 r0967 Control word 1 Bit Fields: Bit00 ON/OFF1 0 NO, Bit01 OFF2: Electrical stop 0 YES, 1 NO Bit02 OFF3: Fast stop 0 YES, 1 NO Bit03 Pulse enable 0 NO, 1 YES Bit04 RFG enable 0 NO, 1 YES Bit05 RFG start 0 NO, 1 YES Bit06 Setpoint enable 0 NO, 1 YES Bit07 Fault acknowledge 0 NO, 1 YES Bit08 JOG right 0 NO, 1 YES Bit09 JOG left 0 NO, 1 YES Bit10 Control from PLC 0 NO, 1 YES Bit11 Reverse (setpoi
Appendix A: Parameter Reference List Dependency: First set P0010=30 (factory settings) Stop drive (that is, disable all pulses) before you can reset parameters to default values. Note: The following parameters retain their values after a factory reset: P0918 (CB address) P2010 (USS baud rate) P2011 (USS address) P0971 Level 3 Transfer data from RAM to EEPROM Min: 0 Def: 0 Enum: 0=Disabled Note: All values in RAM are transferred to EEPROM.
SED2 VFD Operation & Maintenance Manual Enum: Index: 0=No main setpoint 40=No main setpoint + USS on BOP link 1=MOP setpoint 41=MOP setpoint + USS on BOP link 2=Analog setpoint 42=Analog setpoint + USS on BOP link 3=Fixed frequency 43=Fixed frequency + USS on BOP link 4=USS on BOP link 44=USS on BOP link + USS on BOP link 5=USS on COM link 45=USS on COM link + USS on BOP link 6=CB on COM link 46=CB on COM link + USS on BOP link 7=Analog setpoint 2 47=Analog setpoint 2 + USS on BOP link 10
Appendix A: Parameter Reference List P1001 Level 2 Fixed frequency 1 Min: -650.0 Data: Def: 0.00 Max: 650.00 There are three types of fixed frequencies: Direct selection (P0701-P0706=15) In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are active together, the selected frequencies are summed, for example, FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
SED2 VFD Operation & Maintenance Manual 3 10.00 8 35.00 13 60.00 4 15.00 9 40.00 14 65.00 5 20.00 10 45.00 15 65.00 P1016 – P1019 Fixed frequency mode-Bit 0 through 3 Details: Parameter P1016 defines the mode of Bit 0, Parameter P1017 defines the mode of Bit 1, Parameter P1018 defines the mode of Bit 2, and Parameter P1019 defines the mode of Bit 3. Enum: 1=Direct selection Note: See table in P1001 (fixed frequency 1) for a description of how to use fixed frequencies.
Appendix A: Parameter Reference List P1027 Level 3 Fixed frequency mode – Bit 5 Min: 1 Def: 1 Max: 3 Enum: 1=Direct selection Details: See parameter P1001 for description of how to use fixed frequencies. P1028[2] 2=Direct selection + ON command Level 3 BI: Fixed freq. selection Bit 5 Min: 0:0 Index: 3=Binary coded selection + ON command Def: 722:5 P1028[0] : IN000 (AUTO) 1st. Command data set (CDS) Max: 4000:0 P1028[1] : IN001 (HAND) 2nd.
SED2 VFD Operation & Maintenance Manual Note: Value set here is valid both for clockwise and for anticlockwise rotation. Under certain conditions (for example, ramping, current limiting), motor can run below minimum frequency. P1082 Level 1 Max. Frequency Min: 0.00 Def: 50.00 Max: 650.00 Dependency: Limited internally to 200 Hz or 5 * rated motor frequency (P0305) when P1300 >= 20 (control mode=vector control). The value is displayed in r0209 (maximum frequency).
Appendix A: Parameter Reference List Level 1 P1120 Ramp-up time Details: Setting the ramp-up time too short can cause the inverter to trip (overcurrent). Min: 0.00 Def: 10.00 Max: 650.00 If an external frequency setpoint with set ramp rates is used (for example, from a PLC), the best way to achieve optimum drive performance is to set ramp times in P1120 and P1121 slightly shorter than those of the PLC. P1121 Level 1 Ramp-down time Min: 0.00 Def: 10.00 Max: 650.
SED2 VFD Operation & Maintenance Manual Note: Useful for motors with high inertia loads. Settings 1 to 3 search in both directions. Settings 4 to 6 search only in direction of setpoint. Flying start must be used in cases where the motor may still be turning (for example, after a short mains break) or can be driven by the load. Otherwise, overcurrent trips will occur P1202 Min: 50 Details: Level 3 Motor-current: Flying start Def: 100 Max: 200 Defines search current used for flying start.
Appendix A: Parameter Reference List P1213 Min: 0 P1230[2] Def: 30 Max: 1000 Level 3 BI: Enable DC braking Min: 0:0 Details: Level 2 Restart time increment Def: 0:0 Max: 4000:0 Enables DC braking via a signal applied from an external source. Function remains active while external input signal is active. DC braking causes the motor to stop rapidly by applying a DC braking current (current applied also holds shaft stationary).
SED2 VFD Operation & Maintenance Manual Dependency: Active after OFF1/OFF3 command. Note: Increasing the value will generally improve braking performance; however, if you set the value too high, an overcurrent trip may result. Level 3 P1240 Configuration of Vdc controller Details: The Vdc controller dynamically controls the DC link voltage to prevent overvoltage trips on high inertia systems.
Appendix A: Parameter Reference List P1266 Min: 0:0 P1270[2] Def: 0:0 Max: 4000:0 Level 2 BI: Enable essential service Min: 0:0 P1300 Level 2 BI: Bypass command Def: 0:0 Max: 4000:0 Level 2 Control mode Min: 0 Def: 0 Max: 23 Details: Controls relationship between speed of motor and voltage supplied by inverter. Enum: 0 =V/f with linear charac.
SED2 VFD Operation & Maintenance Manual Dependency: Setting in P0640 (motor overload factor [%]) limits boost. Note: Acceleration boost can help to improve response to small positive setpoint changes. P1312 Starting boost Min: 0.0 Details: Level 2 Def: 0.0 Max: 250.0 Applies a constant linear offset (in [%] relative to P0305 (rated motor current)) to active V/f curve (either linear or quadratic) after an ON command and is active until setpoint is reached for the first time.
Appendix A: Parameter Reference List Level 2 P1800 Pulse frequency Details: Sets pulse frequency of power switches in inverter. The frequency can be changed in steps of 2 kHz. Min: 2 Def: 4 Max: 16 Pulse frequencies > 4 kHz selected on 380 to 480V units reduce the maximum continuous motor current. Dependency: Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency).
SED2 VFD Operation & Maintenance Manual Enum: 0=Disabled 1=Identification of all parameters with parameter change 2=Identification of all parameters without parameter change 3=Identification of saturation curve with parameter change Dependency: 6=Identification of Tdead (r1926) without parameter change 7=Identification of Rs (r1912 ) without parameter change 8=Identification of Xs (r1915) without parameter change 9=Identification of Tr (r1913) without parameter change 4=Identification of saturation cur
Appendix A: Parameter Reference List Min: 0 Def: 0 Max: 1 Enum: 0=Disabled 1=Enabled Index: P2009[0] : Serial interface COM link P2009[1] : Serial interface BOP link Note: If enabled, the main setpoint (word 2 in PZD) is not interpreted as 100%=4000H, but as "absolute" instead (for example, 4000H=16384 means 163.84 Hz ).
SED2 VFD Operation & Maintenance Manual Note: The control words can be viewed as bit parameters r2032 and r2033. P2051[8] CI: PZD to CB Min: 0:0 Settings: Level 3 Def: 52:0 Max: 4000:0 Status word 1=52 CO/BO: Act.
Appendix A: Parameter Reference List P2101[3] Min: 0 Details: Level 3 Stop reaction value Def: 0 Max: 4 Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction). This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
SED2 VFD Operation & Maintenance Manual Details: Sets belt failure detection mode. This function allows detection of mechanical failure of the drive train, for example, a broken drive belt. It can also detect conditions which cause an overload, such as a jam. Two methods are provided of detecting the failure. The fist is achieved by comparing the actual frequency/torque curve with a programmed envelope (see P2182P2190). If the curve falls outside the envelope, a warning or trip is generated.
Appendix A: Parameter Reference List P2186, P2188, P2190 Lower torque threshold 1, 2, and 3 Min: 0.0 Level 2 Def: 0.0 Max: 99999.0 Details: Lower limit threshold value for comparing actual torque. Note: See P2182 (belt threshold frequency). P2191 Belt failure speed tolerance Level 2 Min: 0.00 Def: 3.00 Max: 20.00 Details: P2191 defines the allowed speed variation bandwidth between the inverter frequency, and the speed reference from the pulse train.
SED2 VFD Operation & Maintenance Manual Bit Fields: P2200[2] Bit00 | n,filtered r2169 | < P2157 0 NO, 1 YES Bit01 | n,filtered r2169 | > P2157 0 NO, 1 YES Bit02 | n,filtered r2169 | < P2159 0 NO, 1 YES Bit03 | n,filtered r2169 | > P2159 0 NO, 1 YES Bit04 | n,set | < P2161 0 NO, 1 YES Bit05 n,set > 0 0 NO, 1 YES Bit06 Motor blocked 0 NO, 1 YES Bit07 Motor stalled 0 NO, 1 YES Bit08 | I,act r0068 | < P2170 0 NO, 1 YES Bit09 |T,act| > P2174 and setpoint reached
Appendix A: Parameter Reference List Details: Defines Fixed PID Setpoint 1. In addition, you can set any of the digital input parameters to Fixed PID Setpoint via the digital inputs (P0701-P0706). There are three selection modes for the PID fixed setpoint: Direct selection (P0701=15 or P0702=15, etc.). In this mode of operation, 1 digital input selects one PID fixed setpoint. Direct selection with ON command (P0701=16 or P0702=16, etc.).
SED2 VFD Operation & Maintenance Manual P2216, P2217, P2218, P2219 3 20.00 8 70.00 13 120.00 4 30.00 9 80.00 14 130.00 5 40.00 10 90.00 15 130.00 Min: 1 Def: 1 Enum: 1=Direct selection P2220[2] BI: Fixed PID setp. select Bit 0 Min: 0:0 Settings: Level 3 Fixed PID setpoint mode-Bit 0, Bit 1, Bit 2, and Bit 3 Max: 3 2=Direct selection + ON command 3=Binary coded selection + ON command Level 3 Def: 0:0 Max: 4000:0 722.0=Digital input 1 (requires P0701 set to 99, BICO) 722.
Appendix A: Parameter Reference List Note: r2224=100% corresponds to 4000 hex. P2225 Fixed PID setpoint mode-Bit 4 Level 3 Min: 1 Def: 1 Enum: 1=Direct selection P2226[2] BI: Fixed PID setp. select Bit 4 2=Direct selection + ON command Min: 0:0 Settings: Max: 2 3=Binary coded selection + ON command Level 3 Def: 722:4 Max: 4000:0 722.0=Digital input 1 (requires P0701 set to 99, BICO) 722.1=Digital input 2 (requires P0702 set to 99, BICO) 722.
SED2 VFD Operation & Maintenance Manual Level 2 P2232 Inhibit rev. direct. of PID-MOP Details: Inhibits reverse setpoint selection when PID motor potentiometer is chosen either as a main setpoint of additional setpoint (using P1000) Enum: 0=Reserve direction is allowed Note: Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease frequency either by using digital inputs or motor potentiometer up/down buttons.
Appendix A: Parameter Reference List Settings: 755= Analog input 1 2224 =Fixed PI setpoint (see P2201 to P2207) Index: P2254[0] : IN000 (AUTO) 1st. Command data set (CDS) P2261 PID setpoint filter time constant Min: 0.00 Note: 0=no smoothing r2262 CO: Act. PID filtered setpoint Min: - P2254[1] : IN001 (HAND) 2nd. Command data set (CDS) Level 3 Def: 0.00 Max: 60.00 Level 2 Def: - Details: Displays PID setpoint in [%] after smoothing. Note: r2262=100% corresponds to 4000 hex.
SED2 VFD Operation & Maintenance Manual Level 3 P2270 PID feedback function selector Details: Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269 (gain applied to PID feedback).
Appendix A: Parameter Reference List Dependency: If P term=0, I term acts on the square of the error signal. Note: If the system is prone to sudden step changes in the feedback signal, P term should normally be set to a small value (0.5) with a faster I term for optimum performance. The D term (P2274) multiplies the difference between the present and previous feedback signal thus accelerating the controller reaction to an error that appears suddenly.
SED2 VFD Operation & Maintenance Manual P2304 Level 2 PID Opening time Min: 0 Def: 60 Note: See P2305 (PID actuator closing time). P2305 PID Closing time Min: 0 Level 2 Def: 60 Note: See P2304 (PID actuator opening time).
Appendix A: Parameter Reference List Level 2 P2376 Delay override Details: Error as a percentage of setpoint that if exceeded will begin staging without delay. P2377 Delay override lockout timer Min: 0.0 Def: 25.0 Min: 0 Max: 200.0 Level 2 Def: 30 Max: 650 Details: Time for which delay override is prevented after a motor has been staged or destaged. P2378 Staging frequency f, %fMax Min: 0.0 Level 2 Def: 50.0 Max: 120.
SED2 VFD Operation & Maintenance Manual Details: Performs calculations necessary for optimized motor operation. After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically reset to their original value 0.
Appendix B: Mechanical Installation Appendix B: Mechanical Installation SED2 (IP20) Filters Dimensions B I K I K G J J A H A H G B C C 5192J04 5192J03 Filter for Frame Sizes B and C Filter for Frame Size A Frame Size A B C G H I J K A 7.9 (200) 2.9 (73) 1.7 (44) 2.4 (60) 6.3 (160) 2.2 (56) 7.4 (187) 0.9 (22) B 8.4 (213) 5.9 (149) 2.0 (51) 5.4 (138) 6.9 (174) 4.7 (120) 7.9 (200) 1.0 (24) C 9.6 (245) 7.3 (185) 22 (56) 6.9 (174) 8.0 (204) 6.2 (156) 9.1(232) 1.
SED2 Operation & Maintenance Manual Addendum Appendix C: Electrical Installation EMC-Compatibility NOTE: The Siemens Building Technologies SED2 Variable Frequency Drives are shipped without EMC line filters. (The EMC filter is most commonly used in Europe.) Where local codes or customer/installation requirements dictate, separately orderable line filters are available. More stringent Class B line filters are also available for most models.
Appendix C: Electrical Installation Motor cables should be as short as possible and should not exceed 82 ft (25 m). Connect the neutral conductor of all motors controlled by a SED2 drive directly to the ground connection (PE) of the respective SED2. • Use ribbon cables, as they have lower impedance at high frequencies. • Check that the contactors in the control cabinet are suppressed, either with RC circuits for AC contactors or flywheel diodes for DC contactors.
SED2 Operation & Maintenance Manual Addendum Motor SED2 u v w BMS Remove cable insulation Min. 16 mm² (4 AWG)... compensating cable Grounding rail Min.200 mm (7.8 inches).... between control cables, motor cables and mains cables Mains power supply L1 L2 L3 PE Min.10 mm² (6 AWG)... Motor cable PE: min.10 mm² (6 AWG)... 5192Z04en Install all cables on the same side of the plate Control cables Figure 41. Routing Control, Mains, and Motor Cables. 176 Siemens Building Technologies, Inc.
Appendix C: Electrical Installation 1. Incoming mains cable 71 2. Control cable 3. Motor cable L1 L2 L3 4. Footprint filter 5. Metal backplate 5 4 6. Use suitable cable clamps to ensure good conductive contact between the shield of the motor and control cables and the metal backplate. 7. Connect the motor cable shield to . 6 2 3 5192J10 Figure 42. Cable Routing for SED2 Frame Size A with Footprint Filter. Siemens Building Technologies, Inc.
SED2 Operation & Maintenance Manual Addendum Shield connected with tube clips Motor cable Incoming mains voltage 5192J21us Figure 43. Cable Routing for SED2 (IP20) Frame Size D through F with EMC Filter. 178 Siemens Building Technologies, Inc.
Appendix C: Electrical Installation Power Connection for Drives with a Built-in EMC Filter SED2 drives (frame sizes A, B, and C) can include a built-in, prewired, EMC footprint filter. Route and connect the mains power to the terminals of the footprint filter. Incoming mains voltage L1 L2 L3 Ground 5192J15en Filter Filter output Figure 44. Connecting Mains Power to Footprint Filter for SED2 Frame Sizes A through C. Siemens Building Technologies, Inc.
SED2 Operation & Maintenance Manual Addendum 5192J18 SED2 drives (frame sizes D, E, and F) include a built-in, prewired, EMC filter. Route and connect the mains power to the terminals of the filter. 5192J19 4x 6x Figure 45. Connecting Mains Power to Filter for SED2 Frame Sizes D through F. 180 Siemens Building Technologies, Inc.
Appendix C: Electrical Installation L3 L2 L1 EMC filter L3 U L2 V L1 PE Motor SED2 U V W W PE 5192Z12en 3-Phase Figure 46. Typical Power Wiring for SED2 with EMC Filter. Connecting Multiple Motors 5192Z10 SED2 The SED2 can control several motors in parallel as long as all of the motors have the same power rating. When multiple motors connect to the SED2 in parallel, the motors cannot operate individually. NOTES: 1.
SED2 Operation & Maintenance Manual Addendum Operation with a Residual Current Device (RCD) If a residual current device (also called a GLCI or RCCB) is connected, the SED2 operates with no interruptions under the following conditions: • A RCD, Type B is used. • The RCD must have a threshold current of 300 mA. • The neutral conductor in the system must be grounded. • Each RCD supplies only one SED2 (an no other loads).
Appendix D: Programming Appendix D: Programming Bypassing the SED2 There are applications demanding maximum motor output. Additionally, there are applications requiring a SED2 bypass system for safety reasons. For these cases, the SED2 has an integrated bypass function. Mains supply SED2 Parameter setup for bypass function (commissioning) P1260, Source of changeover control Defines the possible sources for changing over to bypass/contactor operating mode.
SED2 Operation & Maintenance Manual Addendum r1261, Contactor control word r1261 is a read parameter for the bypass/contactor function. It shows how the motor is driven as follows: Bit 00, Motor supplied by Drive: 0=Yes 1=No Bit 01, Motor supplied by Mains: 0=Yes 1=No P1262, Bypass dead time Time delay between switching contactors (SED2 to bypass/contactor and vice versa) to allow motor to demagnetize (Figure 49).
Appendix D: Programming P1264, Bypass time Time delay before a request to switch to mains is executed (Figure 49). Setting range: 0 to 300 second Recommended setting: 1 second (default). 5192D03en Complete parameter setting by changing over to automatic control. Alarm (Bypass request) Bypass contactor VSD contactor P1264 P1262 P1263 P1262 t (s) Figure 49. Bypass Timing Diagram. Siemens Building Technologies, Inc.
SED2 Operation & Maintenance Manual Addendum Hibernation Mode If the SED2 reaches the hibernation setpoint in PID operating mode, the P2391 hibernation timer starts. After the timer expires, the SED2 drives the output frequency of the ramp to 0 Hz. f Output [Hz ] Drive frequency PID frequency P2392 Restart freq. P2390 Hibernation freq. Min. freq. Time [s] Restart P2391 Hibernation timer Hibernation mode PID error [% ] 0% Time [s] max.
Appendix D: Programming Parameter Settings for Hibernation Mode (commissioning) P2390, Hibernation frequency Hibernation frequency setpoint (frequency that the motor output will turn off). Setting range: 0 to 200% Recommended setting: Value 15 to 20% greater than the minimum frequency. The hibernation function is disabled if the hibernation frequency is set to 0 (factory setting). P2391, Hibernation timer Set the desired time T1 to T3, before hibernation mode starts (see Figure 50).
SED2 Operation & Maintenance Manual Addendum Appendix E: BiCo (Binector and Connector) Data Set Functions Introduction The SED2 provides user access levels, set by parameter P0003. User access level 1 gives access to the most frequently used parameters. User access level 2 gives access to more advanced parameters. For example, P0701 sets the function of Digital Input 1 with possible values such as: 1=ON right 12=Reverse 15=Fixed frequency, etc .
Appendix E: BiCo Data Set Functions NOTE: If P0701, P0702, P0703 or P0704 are set to 99, it is not possible to change them to another value and the drive must be reset to factory defaults. 1. Since digital input 2 is "open" to BiCo settings, a new value of 722.1 now appears in P0731. The value 722.1 means "connect to digital input 2" (722.0 = connect to digital input 1, 722.2 = connect to digital input 3, etc.). Set P0731 to 722.1. 2. Run the SED2 using input 1 and operate the value using input 2.
SED2 Operation & Maintenance Manual Addendum 3. Define the source of the fixed frequencies by setting P1020=722.0, P1021=722.1, P1022=722.2. (This defines the source of each frequency as digital input 1, 2, and 3.) 4. Define the mode of operation by setting P1016, P1017, P1018 = 2. (This sets the mode of operation of fixed frequencies to 'select fixed frequency and ON right command'. 5. Select JOG ramp times instead of normal ramp times by setting P1124 = 722.2.
Appendix E: BiCo Data Set Functions Siemens Building Technologies, Inc.
SED2 Operation & Maintenance Manual Addendum Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 Tel: +1 847-215-1000 Fax +1 847-215-1093 Siemens Building Technologies, Ltd.. 2 Kenview Blvd. Brampton, Ontario Canada L6T 5E4 Tel: +1 905-799-993 Siemens Building Technologies AG Gubelstrasse 22 CH-6301 Zug Tel: +41 41 724 24 24 Fax +41 41 724 35 22 Siemens Building Technologies Ltd.