Operating Instructions

Chapter 9 – SED2 Communications
Siemens Building Technologies, Inc. 95
Table 8. Point Database for Application 2722.
Point
Number
Point
Type
Descriptor
Factory
Default
(SI Units)
Engr.
Units (SI
Units)
Slope
(SI
Units)
Intercept
(SI Units)
On Text
Off
Text
{16} LAI RATED PWR 0 HP/KW .01 0 - -
{17} LAI OUTPUT
VOLTS
0 V 1 0 - -
20 LAO OVRD TIME 1 HRS 1 0 - -
{21} LDI FWD.REV FWD - 1 0 REV FWD
{22} LDO CMD
FWD.REV
FWD - 1 0 REV FWD
{23} LDI STOP.RUN STOP - 1 0 RUN STOP
{24} LDO CMD
STP.STRT
STOP - 1 0 START STOP
{25} LDI AT MAX FREQ NO - 1 0 MAX NO
{26} LDI CONTROL
MODE
SERIAL - 1 0 SERIAL LOCAL
{27} LDI ENABLED OFF - 1 0 ENABLED OFF
{28} LDI READY TO
RUN
OFF - 1 0 READY OFF
{29} LDO DAY.NIGHT DAY - 1 0 NIGHT DAY
30 LAO CURRENT LIM 1400 PCT .1 10 - -
31 LAO ACCEL TIME 1 500 SEC .02 0 - -
32 LAO DECEL TIME 1 500 SEC .02 0 - -
34 LDO SEL
HND.AUTO
AUTO - 1 0 AUTO HAND
{35} LDO RUN ENABLE ENABLE - 1 0 ENABLE OFF
40 LDO DIGITAL OUT
1
OFF - 1 0 ON OFF
41 LDO DIGITAL OUT
2
OFF - 1 0 ON OFF
{45} LAI ANALOG IN 1 0 PCT .1 -300 - -
{46} LAI ANALOG IN 2 0 PCT .1 -300 - -
{47} LAI ANALOG OUT
1
0 PCT .1 -100 - -
{48} LAI ANALOG OUT
2
0 PCT .1 -100 - -
{51} LAO FREQ REF 0 PCT 0.0061 0 - -
{52} LA1 FREQ
ACTUAL
0 PCT 0.0122 -100 - -