Operating Instructions
SED2 VFD Operation & Maintenance Manual
96 Siemens Building Technologies, Inc.
Table 8. Point Database for Application 2722.
Point
Number
Point
Type
Descriptor
Factory
Default
(SI Units)
Engr.
Units (SI
Units)
Slope
(SI
Units)
Intercept
(SI Units)
On Text
Off
Text
53 LAO FREQ MAX 2450 HZ 0.02 1 - -
{55} LAO PID SETP REF 8602 PCT 0.0244 -200 - -
{56} LAI PID SETP
OUT
0 PCT 0.0122 -100 - -
57 LAO PID UP LMT 12288 PCT 0.0244 -200 - -
58 LAO PID LO LMT 8192 PCT 0.0244 -200 - -
{59} LAI PID OUTPUT 0 PCT 0.0122 -100 - -
{60} LAI PI FEEDBACK 0 PCT 0.0122 -100 - -
61 LAI P GAIN 0 PCT 0.002 0 - -
62 LAI I GAIN 0 PCT 2 0 - -
63 LAI D GAIN 0 PCT 2 0 - -
64 LDO ENABLE PID 0 - 1 0 ON OFF
66 LAI FEEDBK GAIN 0 PCT 0.02 0 - -
68 LAI LOW PASS 0 0.01 0 - -
{71} LDI DIGITAL IN 1 0 - 1 0 ON OFF
{72} LDI DIGITAL IN 2 0 - 1 0 ON OFF
{73} LDI DIGITAL IN 3 0 - 1 0 ON OFF
{74} LDI DIGITAL IN 4 0 - 1 0 ON OFF
{75} LDI DIGITAL IN 5 0 - 1 0 ON OFF
{76} LDI DIGITAL IN 6 0 - 1 0 ON OFF
80 LAO WDOG TIME 0 10 0 - -
83 LAI INVERTER
VER
0 - 0.01 0 - -
84 LAI DRIVE
MODEL
0 - 1 0 - -
{90} LAI LAST FAULT 0 - 1 0 - -
{91} LAI 1ST FAULT 0 - 1 0 - -
{92} LAI 2ST FAULT 0 - 1 0 - -
{93} LAI 3ST FAULT 0 - 1 0 - -
{94} LDI OKFAULT 0 - 1 0 FAULT OK
{95} LDO FAULT ACK 0 - 1 0 ON OFF
{96} LDI WARNING 0 - 1 0 WARN OK
{97} LAI LAST 0 - 1 0 - -