Operating Instructions

Chapter 9 – SED2 Communications
Siemens Building Technologies, Inc. 101
Table 11. N2 Point Map.
On Text Off
Text
Point
Number
Name Default
Value
Units Notes
Or Range
SED2 Ref.
BO6 DIGITAL OUT 2 0 -- ON OFF P0733
BO7 CMD FWD REV 0 -- REV FWD STW:11
BO8 ENABLE PID 0 -- ON OFF P2200
ADF1 ACCEL TIME 1 10.00 SEC 0.00 to 650.00 P1120
ADF2 DECEL TIME 1 10.00 SEC 0.00 to 650.00 P1121
ADF3 CURRENT LMT 150.0 PCT 10.0 to 400.0 P0640
ADF4 P GAIN 3.000 -- 0.000 to 65.000 P2280
ADF5 I GAIN 0 SEC 0.000 to 60.000 P2285
ADF6 D GAIN 0 -- 0.000 to 60.000 P2274
ADF7 FEEDBK GAIN 100.00 PCT 0.00 to 500.00 P2269
ADF8 LOW PASS 0 -- 0.00 to 60.00 P2265
ADF9 PID SETP REF 0 PCT -200.0 to 200.0 P2240
ADF10 PID UP LMT 100.0 PCT -200.0 to 200.0 P2291
ADF11 PID LO LMT 0 PCT -200.0 to 200.0 P2292
ADF12 FREQ MAX 50.00 HZ 1.00 to 650.00 P2000
ADF13 RATED PWR 0 KW Read Only 0 to 327.67 r0206
ADF14 INVERTER VER 0 -- Read Only 0.00 to 327.67 r0018
ADI1 WDOG TIME 0 MS 9999 P2040
ADI2 DRIVE MODEL 0 -- Read Only 0 to 32767 r0200
ADI3 LAST FAULT 0 -- Read Only 0 to 32767 r0947
ADI4 1ST FAULT 0 -- Read Only 0 to 32767 r0947
ADI5 2ND FAULT 0 -- Read Only 0 to 32767 r0947
ADI6 3RD FAULT 0 -- Read Only 0 to 32767 r0947
ADI7 LAST WARNING 0 -- Read Only 0 to 32767 r2110