Operating Instructions
SED2 VFD Operation & Maintenance Manual
104 Siemens Building Technologies, Inc.
Parameter Description Unit
User
Setting
Min Default Max
Access
Level
r0209 Maximum inverter
current
A - - - 2
P1800 Pulse frequency kHz 2 4 16 2
r1801 CO: Act. switching
frequency
kHz - - - 3
P1820 Reverse output phase
sequence
- 0 0 1 2
Motor Data (P0004=3)
Parameter Description Unit
User
Setting
Min
Default Max
Access
Level
r0000 Drive display (defined
in P0005)
- - - - X
P0003 User access level to
parameters
- 0 1 4 1
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning
parameter filter
- 0 0 30 1
r0035 CO: Act. Motor
temperature
°C - - - 2
P0304 Rated motor voltage V 10 230 2000 1
P0305 Rated motor current A 0.01 3.25 10000.00 1
P0307 Rated motor power - 0.01 0.75 2000.00 1
P0308 Rated motor cosPhi - 0.000 0.000 1.000 2
P0309 Rated motor efficiency % 0.0 0.0 99.9 2
P0310 Rated motor frequency Hz 12.00 50.00 or 60.00 650.00 1
P0311 Rated motor speed 1/min 0 0 40000 1
r0313 Motor pole pairs - - - - 3