Operating Instructions

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 105
Parameter Description Unit
User
Setting
Min
Default Max
Access
Level
P0340 Calculation of motor
parameters
- 0 0 4 2
P0350 Stator resistance (line-
to-line)
ohm 0.00001 4.0 2000.0 2
r0395 CO: Total stator
resistance [%]
% - - - 3
P0601 Motor temp. sensor - 0 0 2 3
P0610 Motor I2t temperature
reaction
- 0 2 2 3
P0640 Motor overload factor
[%]
% 10.0 150.0 400.0 2
P1910 Select motor data
identification
ohm 0 0 20 2
r1912 Identified stator
resistance
- - - - 2
Commands and Digital I/O (P0004=7)
Parameter Description Unit
User
Setting
Min Default
Max
Access
Level
r0000 Drive display (defined
in P0005)
- - - - X
r0002 Drive state (actual) - - - - 2
P0003 User access level to
parameters
- 0 1 4 1
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning
parameter filter
- 0 0 30 1
r0019 CO/BO: BOP control
word
- - - - 3
r0050 CO: Active command
data set