Operating Instructions

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 109
Parameter Description Unit
User
Setting
Min Default Max
Access
Level
P0757 Value x1 of ADC
scaling [V/mA]
- 50.0 0 150.0 2
P0758 Value y1 of ADC
scaling
% -99999.9 0.0 99999.9 2
P0759 Value x2 of ADC
scaling [V/mA]
- 50.0 150.0 150.0 2
P0760 Value y2 of ADC
scaling
% -99999.9 100.0 99999.9 2
P0761 Width of ADC
deadband [V/mA]
- 0 0 150.0 2
P0771 CI: DAC - 0:0 21:0 4000:0 2
P0773 Smooth time DAC ms 0 2 1000 3
r0774 Act. DAC value [V] or
[mA]
- - - - 2
P0776 Type of DAC - 0 1 1 3
P0777 Value x1 of DAC
scaling
% -99999.0 0.0 99999.0 2
P0778 Value y1 of DAC
scaling
- 0 0 20 2
P0779 Value x2 of DAC
scaling
% -99999.0 100.0 99999.0 2
P0780 Value y2 of DAC
scaling
- 0 20 20 2
P0781 Width of DAC
deadband
- 0 0 20 2
Setpoint Channel and Ramp Generator (P0004=10)
Parameter Description Unit
User
Setting
Min Default
Max
Access
Level
r0000 Drive display (defined
in P0005)
- - - - X