Operating Instructions
Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 111
Parameter Description Unit
User
Setting
Min Default
Max
Access
Level
P1019 Fixed frequency mode-
Bit 3
- 1 1 3 3
r1024 CO: Act. fixed
frequency
Hz - - - 3
P1025 Fixed frequency mode
– Bit 4
- 1 1 3 3
P1027 Fixed frequency mode
– Bit 5
- 1 1 3 3
P1031 Setpoint memory of the
MOP
- 0 0 1 2
P1032 Inhibit reverse direction
of MOP
- 0 1 1 2
P1040 Setpoint of the MOP Hz -650.00 5.00 650.00 2
r1050 CO: Act. Output freq. of
the MOP
- - - - 3
r1078 CO: Total frequency
setpoint
Hz - - - 3
P1080 Min. Frequency Hz 0.00 0.00 650.00 1
P1082 Max. Frequency Hz 0.00 50.00 650.00 1
P1091 Skip frequency 1 Hz 0.00 0.00 650.00 3
P1092 Skip frequency 2 Hz 0.00 0.00 650.00 3
P1093 Skip frequency 3 Hz 0.00 0.00 650.00 3
P1094 Skip frequency 4 Hz 0.00 0.00 650.00 3
P1101 Skip frequency
bandwidth
Hz 0.00 2.00 10.00 3
P1120 Ramp-up time s 0.00 10.00 650.00 1
P1121 Ramp-down time s 0.00 10.00 650.00 1
P1135 OFF3 ramp-down time s 0.00 5.00 650.00 2