Operating Instructions

SED2 VFD Operation & Maintenance Manual
112 Siemens Building Technologies, Inc.
Drive Features (P0004=12)
Parameter Description Unit
User
Setting
Min Default
Max
Access
Level
r0000 Drive display (defined
in P0005)
- - - - X
P0003 User access level to
parameters
- 0 1 4 1
P0004 Parameter filter - 0 0 22 1
P0005 Display selection for
r0000
- 2 21 2294 2
P0006 Display mode for r0000 - 0 2 4 3
P0010 Commissioning
parameter filter
- 0 0 30 1
P0011 Lock for user-defined
parameter
- 0 0 65535 3
P0012 Key for user-defined
parameter
- 0 0 65535 3
P0013 User-defined parameter - 0 0 65535 3
P1200 Flying start - 0 0 6 2
P1202 Motor-current: Flying
start
% 50 100 200 3
P1203 Search rate: Flying start % 50 100 200 3
P1210 Automatic restart - 0 1 5 2
P1211 Number of restart
attempts
- 0 3 10 3
P1212 Time to first restart s 0 30 1000 2
P1213 Restart time increment s 0 30 1000 2
P1232 DC braking current % 0 100 250 2
P1233 Duration of DC braking s 0 0 250 2
P1236 Compound braking
current