Operating Instructions
SED2 VFD Operation & Maintenance Manual
122 Siemens Building Technologies, Inc.
Parameter List
r0000 Drive display (defined in P0005)
Min: - Def: - Max: -
Level X
Note: Pressing the "Fn" button for 2 seconds allows you to view the values of DC link voltage, output current, output
frequency, and chosen r0000 setting (defined in P0005).
r0002 Drive state (actual)
Min: - Def: - Max: -
Level 2
Enum: 0=Commissioning mode (P0010=0)
1=Drive ready
2=Drive fault active
3=Drive starting (DC-link precharging)
4=Drive running
5=Stopping (ramping down)
Dependency: State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003 User access level to parameters
Min: 0 Def: 1 Max: 4
Level 1
Enum: 0=User-defined parameter list-see P0013 for
details
1=Standard: Access into frequently used
parameters.
2=Extended: Access to for example, inverter I/O
functions.
3=Expert: For expert use only.
4=Service: Only for use by authorized service personal-
password protected.
P0004 Parameter filter
Min: 0 Def: 0 Max: 22
Level 1
Example: P0004=22 specifies that only PID parameters will be visible.
Enum: 0=All parameters
2=Inverter
3=Motor
4=Speed sensor
5=Technol.
application/units
7=Commands, binary I/O
8=ADC and DAC
10 =Setpoint
channel/RFG
12 =Drive features
13 =Motor control
20 =Communication
21 =Alarms/warnings/monitoring
22 =Technology controller (for
example, PID)
Dependency: Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010=1 (Quick
Commissioning).
Note: The inverter will start with any setting of P0004.
P0005 Display selection for r0000
Min: 2 Def: 21 Max: 2294
Level 2
Enum: 21=Actual frequency 25=Output voltage 26=DC link voltage 27=Output current
Note: These settings refer to read only parameter numbers ("rxxxx").
Details: See relevant "rxxxx" parameter descriptions.