Operating Instructions

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 123
P0006 Display mode for r0000
Min: 0 Def: 2 Max: 4
Level 3
Enum: 0=In Ready state alternate between setpoint and output
freq. In run display output freq.
1=In Ready state display setpoint. In run display output
freq.
2=In Ready state alternate between P0005 value and
r0020 value. In run display P0005 value.
3=In Ready state alternate between r0002 value and
r0020 value. In run display r0002 value
4=In all states just display P0005
Note: When inverter is not running, the display alternates between the values for "Not Running" and "Running".
Per default, the setpoint and actual frequency values are displayed alternately.
P0010 Commissioning parameter filter
Min: 0 Def: 0 Max: 30
Level 1
Enum: 0=Ready
1=Quick commissioning
2=Inverter
29 =Download
30 =Factory setting
Dependency: Reset to 0 for interter to run.
P0003 (user access level) also determines access to parameters.
Note: If P3900 is not 0 (0 is the default value), this parameter is automatically reset to 0.
P0011 Lock for user-defined parameter
Min: 0 Def: 0 Max: 65535
Level 3
Details: See P0013 (user-defined parameter).
P0012 Key for user-defined parameter
Min: 0 Def: 0 Max: 65535
Level 3
Details: See P0013 (user-defined parameter).
P0013[20] User-defined parameter
Min: 0 Def: 0 Max: 65535
Level 3
Instructions: Step 1: Set P0003=3 (expert user)
Step 2: Go to P0013 indices 0 to 16 (user list)
Step 3: Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The following
values are fixed and cannot be changed:
- P0013 index 19=12 (key for user-defined parameter)
- P0013 index 18=10 (commissioning parameter filter)
- P0013 index 17= 3 (user access level)
Step 4: Set P0003=0 to activate the user-defined parameter.