128 Siemens Building Technologies, Inc.
r0056 CO/BO: Status of motor control
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 Init. control finished 0 NO, 1 YES
Bit01 Motor demagnetizing finished 0 NO, 1 YES
Bit02 Pulses enabled 0 NO, 1 YES
Bit03 Voltage soft start select 0 NO, 1 YES
Bit04 Motor excitation finished 0 NO, 1 YES
Bit05 Starting boost active 0 NO, 1 YES
Bit06 Acceleration boost active 0 NO, 1 YES
Bit07 Frequency is negative 0 NO, 1 YES
Bit08 Field weakening active 0 NO, 1 YES
Bit09 Volts setpoint limited 0 NO, 1 YES
Bit10 Slip frequency limited 0 NO, 1 YES
Bit11 F_out > F_max Freq. limited 0 NO, 1 YES
Bit12 Phase reversal selected 0 NO, 1 YES
Bit13 I-max controller active 0 NO, 1 YES
Bit14 Vdc-max controller active 0 NO, 1 YES
Bit15 Vdc-min controller active 0 NO, 1 YES
Details: See description of seven segment display.
r0061 CO: Act. rotor speed
Min: - Def: - Max: -
Level 3
r0086 CO: Act. active current
Min: - Def: - Max: -
Level 3
Dependency: Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
P0100 Europe/North America power settings [kW or hp]
Min: 0 Def: 0 Max: 2
Level 1
Enum: 0=Europe [kW], frequency default 50 Hz
1=North America [hp], frequency default 60 Hz
2=North America [kW], frequency default 60 Hz
The setting of DIP switch 2 under the I/O board determines the validity of settings 0 and 1 for P0100 according to
the following table:
DIP 2 Setting Meaning P0100 Setting Meaning
Off [kW], frequency default 50
[Hz]
Overwrites 1 [hp], frequency default 60
[Hz]
Dependency:
On [hp], frequency default 60
[Hz]
Overwrites 0 [kW], frequency default 50
[Hz]