Operating Instructions
Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 129
Stop drive first (that is, disable all pulses) before you change this parameter.
P0010=1 (commissioning mode) enables changes to be made.
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor
parameters (see P0340-calculation of motor parameters).
Note: P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see table
above).
r0200 Act. power stack code number (per following table)
Min: - Def: - Max: -
Level 3
Note: Parameter r0200=0 indicates that no power stack has been identified.
r0206 Rated inverter power [kW]/[hp]
Min: - Def: - Max: -
Level 2
Dependency: Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe/North America).
r0207 Rated inverter current
Min: - Def: - Max: -
Level 2
r0208 Rated inverter voltage
Min: - Def: - Max: -
Level 2
Value: r0208=230 : 200-240V +/- 10% r0208=400 : 380-480V +/- 10% r0208=575 : 500-600V +/- 10%
r0209 Maximum inverter current
Min: - Def: - Max: -
Level 2
P0304 Rated motor voltage
Min: 10 Def: 230 Max: 2000
Level 1
Dependency: Changeable only when P0010=1 (quick commissioning).
P0305 Rated motor current
Min: 0.01 Def: 3.25 Max: 10000.00
Level 1
Dependency: Changeable only when P0010=1 (quick commissioning).
Depends also on P0320 (motor magnetization current).
Note: For asynchronous motors, the maximum value is defined as the maximum inverter current (r0209).
For synchronous motors, the maximum value is defined as twice the maximum inverter current (r0209)
The minimum value is defined as 1/32 times inverter rated current (r0207).