P0307 Rated motor power
Min: 0.01 Def: 0.75 Max: 2000.00
Level 1
Dependency: If P0100=1 ([kW],frequency default 50 Hz), values will be in [hp]-see diagram P0304 (rating plate).
Changeable only when P0010=1 (quick commissioning).
P0308 Rated motor cosPhi
Min: 0.000 Def: 0.000 Max: 1.000
Level 2
Dependency: Changeable only when P0010=1 (quick commissioning).
Visible only when P0100=0 or 2, (motor power entered in [kW]).
Setting 0 causes internal calculation of value (see r0332).
P0309 Rated motor efficiency
Min: 0.0 Def: 0.0 Max: 99.9
Level 2
Dependency: Changeable only when P0010=1 (quick commissioning).
Visible only when P0100=1, (that is, motor power entered in [hp]).
Setting 0 causes internal calculation of value (see r0332).
Note: P0309=100% corresponds to superconducting
P0310 Rated motor frequency
Min: 12.00 Def: 50.00 or 60.00 Max: 650.00
Level 1
Dependency: Changeable only when P0010=1 (quick commissioning).
Pole pair number recalculated automatically if parameter is changed.
P0311 Rated motor speed
Min: 0 Def: 0 Max: 40000
Level 1
Dependency: Changeable only when P0010=1 (quick commissioning).
Setting 0 causes internal calculation of value.
Required for vector control and V/f control with speed controller.
Slip compensation in V/f control requires rated motor speed for correct operation.
Pole pair number recalculated automatically if parameter is changed.
r0313 Motor pole pairs
Min: - Def: - Max: -
Level 3
Value: r0313=1 : 2-pole motor r0313=2 : 4-pole motor, etc.
Dependency: Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed.