SED2 VFD Operation & Maintenance Manual
134 Siemens Building Technologies, Inc.
P0703[2] Function of digital input 3
Min: 0 Def: 9 Max: 99
Level 2
Detail: See P0701 (function of digital input1).
P0704[2] Function of digital input 4
Min: 0 Def: 15 Max: 99
Level 2
Detail: See P0701 (function of digital input1).
P0705[2] Function of digital input 5
Min: 0 Def: 15 Max: 99
Level 2
Detail: See P0701 (function of digital input1).
P0706[2] Function of digital input 6
Min: 0 Def: 15 Max: 99
Level 2
Detail: See P0701 (function of digital input1).
P0707[2] Function of digital input 7
Min: 0 Def: 0 Max: 99
Level 2
Enum: 0=Digital input disabled
1=ON/OFF1
2=ON reverse /OFF1
3=OFF2 -coast to standstill
4=OFF3 -quick ramp-down
9=Fault acknowledge
10 =JOG right
11 =JOG left
12 =Reverse
13 =MOP up (increase freq.)
14 =MOP down (decrease freq.)
25 =DC brake enable
26 =Enable Essential Service
29 =External trip
33 =Disable additional freq setpoint
99 =Enable BICO parameterization
Index: P0707[0] : IN000 (AUTO) 1st. Command data set
(CDS)
P0707[1] : IN001 (HAND) 2nd. Command data set (CDS)
Dependency: Signals about 4V are active, signals below 1.6V are inactive.
Details: See P0701 (function of digital input 1).
P0708[2] Function of digital input 8
Min: 0 Def: 0 Max: 99
Level 2
Detail: See P0707 (function of digital input7).
P0718 CO/BO: Hand/Auto
Min: 0 Def: 0 Max: 1
Level 2
r0722 CO/BO: Binary input values
Min: - Def: - Max: -
Level 2