Operating Instructions

SED2 VFD Operation & Maintenance Manual
138 Siemens Building Technologies, Inc.
P0759[2] Value x2 of ADC scaling [V/mA]
Min: 50.0 Def: 150.0 Max: 150.0
Level 2
Index: P0759[0] : IN000 Analog input 1 (ADC 1) P0759[1] : IN001 Analog input 2 (ADC 2)
P0760[2] Value y2 of ADC scaling
Min: -99999.9 Def: 100.0 Max: 99999.9
Level 2
Index: P0760[0] : IN000 Analog input 1 (ADC 1) P0760[1] : IN001 Analog input 2 (ADC 2)
Dependency: Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be
generated.
P0761[2] Width of ADC deadband [V/mA]
Min: 0 Def: 0 Max: 150.0
Level 2
Index: P0761[0] : IN000 Analog input 1 (ADC 1) P0761[1] : IN001 Analog input 2 (ADC 2)
Note: P0761[x]=0 : No deadband active.
Deadband starts from 0V to value of P0761, if both values of P0758 and P0760 (y coordinates of ADC scaling)
are positive or negative respectively. However, deadband is active in both directions from point of intersection (x
axis with ADC scaling curve), if sign of P0758 and P0760 are opposite.
Fmin (P1080) should be zero when using center zero setup. There is no hysteresis at the end of the deadband.
P0771[2] CI: DAC
Min: 0:0 Def: 21:0 Max: 4000:0
Level 2
Settings: 21 CO: Act. frequency (scaled to P2000)
24 CO: Act. output frequency (scaled to P2000)
25 CO: Act. output voltage (scaled to P2001)
26 CO: Act. DC-link voltage (scaled to P2001)
27 CO: Act. output current (scaled to P2002)
Index: P0771[0] : IN000 Analog output 1 (DAC 1) P0771[1] : IN001 Analog output 2 (DAC 2)
P0773[2] Smooth time DAC
Min: 0 Def: 2 Max: 1000
Level 3
Index: P0773[0] : IN000 Analog output 1 (DAC 1) P0773[1] : IN001 Analog output 2 (DAC 2)
Dependency: P0773=0: Deactivates filter.
r0774[2] Act. DAC value [V] or [mA]
Min: - Def: - Max: -
Level 2
Index: r0774[0] : IN000 Analog output 1 (DAC 1) r0774[1] : IN001 Analog output 2 (DAC 2)
P0776 Type of DAC
Min: 0 Def: 1 Max: 1
Level 3
Setting: 0=Current output 1=Voltage output