Operating Instructions
SED2 VFD Operation & Maintenance Manual
142 Siemens Building Technologies, Inc.
r0967 Control word 1
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 ON/OFF1 0 NO, 1 YES
Bit01 OFF2: Electrical stop 0 YES, 1 NO
Bit02 OFF3: Fast stop 0 YES, 1 NO
Bit03 Pulse enable 0 NO, 1 YES
Bit04 RFG enable 0 NO, 1 YES
Bit05 RFG start 0 NO, 1 YES
Bit06 Setpoint enable 0 NO, 1 YES
Bit07 Fault acknowledge 0 NO, 1 YES
Bit08 JOG right 0 NO, 1 YES
Bit09 JOG left 0 NO, 1 YES
Bit10 Control from PLC 0 NO, 1 YES
Bit11 Reverse (setpoint inversion) 0 NO, 1 YES
Bit13 Motor potentiometer MOP up 0 NO, 1 YES
Bit14 Motor potentiometer MOP down 0 NO, 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO, 1 YES
r0968 Statue word 1
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 Drive ready 0 NO, 1 YES
Bit01 Drive ready to run 0 NO, 1 YES
Bit02 Drive running 0 NO, 1 YES
Bit03 Drive fault active 0 NO, 1 YES
Bit04 OFF2 active 0 YES, 1 NO
Bit05 OFF3 active 0 YES, 1 NO
Bit06 ON inhibit active 0 NO, 1 YES
Bit07 Drive warning active 0 NO, 1 YES
Bit08 Deviation setp./act. value 0 YES, 1 NO
Bit09 PZD control 0 NO, 1 YES
Bit10 Maximum frequency reached 0 NO, 1 YES
Bit11 Warning: Motor current limit 0 YES, 1 NO
Bit12 Motor holding brake active 0 NO, 1 YES
Bit13 Motor overload 0 YES, 1 NO
Bit14 Motor runs direction right 0 NO, 1 YES
Bit15 Inverter overload 0 YES, 1 NO
P0970 Factory reset
Min: 0 Def: 0 Max: 1
Level 1
Enum: 0=Disabled 1=Parameter reset