Operating Instructions

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 143
Dependency: First set P0010=30 (factory settings)
Stop drive (that is, disable all pulses) before you can reset parameters to default values.
Note: The following parameters retain their values after a factory reset:
P0918 (CB address)
P2010 (USS baud rate)
P2011 (USS address)
P0971 Transfer data from RAM to EEPROM
Min: 0 Def: 0 Max: 1
Level 3
Enum: 0=Disabled 1=Start transfer
Note: All values in RAM are transferred to EEPROM.
Parameter is automatically reset to 0 (default) after successful transfer.
P1000[2] Selection of frequency setpoint
Min: 0 Def: index dependent Max: 77
Level 1
Data: Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from the
least significant digit (that is, 0 to 6) and any additional setpoint from the most significant digit (that is, x0 through
to x6).
Example: Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the motor
potentiometer.
Settings: 1 Motor potentiometer setpoint
(keypad)
2 Analog input
3 Fixed frequency setpoint
4 USS on BOP link/AOP
5 USS on COM link
6 Communication board (CB) on
COM link/P1-N2 communications