Operating Instructions
Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 145
P1001 Fixed frequency 1
Min: -650.0 Def: 0.00 Max: 650.00
Level 2
There are three types of fixed frequencies:
Direct selection (P0701-P0706=15)
In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are active together, the selected
frequencies are summed, for example, FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
Direct selection + ON command (P0701-P0706=16)
The fixed frequency selection combines the fixed frequencies with an ON command. In this mode of operation 1
digital input selects 1 fixed frequency. If several inputs are active together, the selected frequencies are summed,
for example, FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
Binary coded selection + ON command (P0701-P0706=17)
Select up to 16 fixed frequencies using this method. Select the fixed frequencies according to the following table:
DIN4 DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive Inactive
P1001 FF1 Inactive Inactive Inactive Active
P1002 FF2 Inactive Inactive Active Inactive
P1003 FF3 Inactive Inactive Active Active
P1004 FF4 Inactive Active Inactive Inactive
P1005 FF5 Inactive Active Inactive Active
P1006 FF6 Inactive Active Active Inactive
P1007 FF7 Inactive Active Active Active
P1008 FF8 Active Inactive Inactive Inactive
P1009 FF9 Active Inactive Inactive Active
P1010 FF10 Active Inactive Active Inactive
P1011 FF11 Active Inactive Active Active
P1012 FF12 Active Active Inactive Inactive
P1013 FF13 Active Active Inactive Active
P1014 FF14 Active Active Active Active
Data:
P1015 FF15 Active Active Active Active
Dependency: Select fixed frequency operation (using P1000).
Inverter requries ON command to start in the case of direct selection (P0701 – P0706=15).
Note: Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.
P1002-P1015 Fixed frequency 2 through 15
Min: -650.00 Def: See Note below Max: 650.00
Level 2
Details: See P1001 (fixed frequency 1).
Default fixed frequency setpoint values are as follows:
Fixed Frequency Default Fixed Frequency Default Fixed Frequency Default
1 0.00 6 25.00 11 50.00
Note:
2 5.00 7 30.00 12 55.00