Operating Instructions

SED2 VFD Operation & Maintenance Manual
158 Siemens Building Technologies, Inc.
Note: The control words can be viewed as bit parameters r2032 and r2033.
P2051[8] CI: PZD to CB
Min: 0:0 Def: 52:0 Max: 4000:0
Level 3
Settings: Status word 1=52
CO/BO: Act. status word 1 (see r0052)
Actual value 1= 21 inverter output frequency (see r0021)
Other BICO settings are possible
Index: P2051[0] : Transmitted word 0
P2051[1] : Transmitted word 1
P2051[2] : Transmitted word 2
P2051[3] : Transmitted word 3
P2051[4] : Transmitted word 4
P2051[5] : Transmitted word 5
P2051[6] : Transmitted word 6
P2051[7] : Transmitted word 7
r2053[5] CB identification
Min: - Def: - Max: -
Level 3
Enum: 0=No CB option board
1=PROFIBUS DP
2=DeviceNet
56 not defined
Index: r2053[0] : CB type (PROFIBUS=1)
r2053[1] : Firmware version
r2053[2] : Firmware version detail
r2053[3] : Firmware date (year)
r2053[4] : Firmware date (day/month)
r2054[7] CB diagnosis
Min: - Def: - Max: -
Level 3
Index: r2054[0] : CB diagnosis 0
r2054[1] : CB diagnosis 1
r2054[2] : CB diagnosis 2
r2054[3] : CB diagnosis 3
r2054[4] : CB diagnosis 4
r2054[5] : CB diagnosis 5
r2054[6] : CB diagnosis 6
Note: See relevant communications board manual.
P2100[3] Alarm number selection
Min: 0 Def: 0 Max: 65535
Level 3
Example: If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0]=5, then select the desired reaction in
P2101[0] (in this case, set P2101[0]=3).
Note: All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (for example,
overcurrent) cannot be changed from the default reactions.